ABB 1SDA101511R1 XT7L M 1000 is a 1000 A three-pole fixed moulded case circuit breaker with front terminals, 120 kA ultimate breaking capacity at 415 V AC and an Ekip Touch LSIG electronic trip unit for advanced low-voltage distribution protection.
£6,506.06
The ABB XT7L M 1000 Ekip Touch LSIG, order code 1SDA101511R1, is a high-performance three-pole moulded case circuit breaker (MCCB) designed for demanding low-voltage power distribution applications. Part of the ABB SACE Tmax XT7 family, it combines a 1000 A rated uninterrupted current with an advanced Ekip Touch LSIG solid-state electronic trip unit and the high short-circuit performance of the XT7L platform.
The Ekip Touch LSIG trip unit provides long-time, short-time, instantaneous and ground-fault protection functions, delivering comprehensive electronic protection against overload, short-circuit and earth-fault conditions. Its advanced protection architecture supports effective coordination in industrial, infrastructure and commercial electrical systems where dependable protection and continuity of service are essential.
With a 1000 A rating, three-pole configuration, fixed construction, front terminals and a stored-energy operating mechanism, the 1SDA101511R1 is engineered for high-current switchboard applications. The XT7L provides an ultimate short-circuit breaking capacity of 120 kA at 415 V AC, with high breaking performance maintained across a wide range of low-voltage system voltages.
High-current electrical distribution systems require protection against multiple fault conditions while maintaining appropriate selectivity between upstream and downstream devices. The ABB Ekip Touch LSIG trip unit combines long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection within an advanced electronic platform, enabling comprehensive protection of feeders and distribution circuits.
The 1SDA101511R1 is particularly suited to installations with high prospective short-circuit currents, providing an ultimate breaking capacity of 120 kA at 415 V AC and 50 kA at 690 V AC. Combined with its 1000 A current rating, fixed front-terminal construction and stored-energy operating mechanism, this makes the XT7L M 1000 a robust choice for demanding industrial and commercial switchboards.
| Series | SACE Tmax XT |
|---|---|
| Order code | 1SDA101511R1 |
| EAN | 8056221015554 |
| Product type | Moulded case circuit breaker |
| Frame / sub-type | XT7M |
| Short-circuit performance level | L |
| Rated uninterrupted current (Iu) | 1000 A |
| Number of poles | 3 |
| Trip unit | Ekip Touch LSIG |
| Trip-unit technology | Solid-state electronic |
| Protection functions | Long-time, short-time, instantaneous and ground fault |
| Ultimate breaking capacity (Icu) at 415 V AC | 120 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 500 V AC | 85 kA |
| Ultimate breaking capacity (Icu) at 525 V AC | 65 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 50 kA |
| Installation | Fixed |
| Terminal configuration | Front terminals |
| Operating mechanism | Stored-energy and lever operating mechanism |
| Standard | IEC 60947 |
| Product dimensions | 210 mm wide × 268 mm high × 178 mm deep |
| Product net weight | approx. 9.7 kg |
The ABB 1SDA101511R1 is a 1000 A three-pole moulded case circuit breaker designed for protection and switching of demanding low-voltage power distribution circuits, including systems with high prospective short-circuit currents.
The breaker is fitted with an Ekip Touch LSIG solid-state electronic trip unit providing long-time, short-time, instantaneous and ground-fault protection functions.
The ABB 1SDA101511R1 has a rated uninterrupted current of 1000 A and is configured as a three-pole breaker for high-current low-voltage distribution applications.
The ABB XT7L M 1000 provides an ultimate short-circuit breaking capacity of 120 kA at 415 V AC, 100 kA at 440 V AC, 85 kA at 500 V AC, 65 kA at 525 V AC and 50 kA at 690 V AC.
The 1SDA101511R1 is a fixed three-pole circuit breaker with front terminals and incorporates stored-energy and lever operating mechanisms for integration into low-voltage distribution switchboards.