ABB 1SDA101452R1 XT7H M 1250 is a fixed three-pole 1250 A SACE Tmax XT moulded-case circuit breaker with front terminals, stored-energy operation and an Ekip Touch Measuring LSI electronic trip unit.
£5,375.84
The ABB XT7H M 1250 Ekip Touch Measuring LSI, order code 1SDA101452R1, is a high-performance three-pole moulded-case circuit breaker from the ABB SACE Tmax XT7 range, designed for protection, switching and electrical measurement in demanding low-voltage power-distribution systems. This fixed circuit breaker combines a 1250 A rated current with ABB’s advanced Ekip Touch Measuring LSI electronic trip unit.
The Ekip Touch Measuring LSI release provides long-time, short-time and instantaneous protection together with integrated electrical measurement capabilities. The measuring platform supports monitoring of key network quantities including voltage, active, reactive and apparent power, energy, frequency and power factor, giving operators valuable information for power management and system supervision.
The XT7H M configuration incorporates a stored-energy operating mechanism together with lever operation and is supplied as a three-pole fixed breaker with front terminals. Rated for operation up to 690 V AC, the breaker provides an ultimate short-circuit breaking capacity of 70 kA at 415 V AC, making it suitable for high-current feeders, main distribution boards and demanding industrial switchgear.
Moulded-case circuit breakers such as the ABB SACE Tmax XT7 protect low-voltage electrical installations against overload and short-circuit conditions. The electronic trip unit monitors current in the protected circuit and initiates disconnection according to configured protection settings, helping safeguard cables, switchgear and connected electrical equipment.
The Ekip Touch Measuring LSI release extends this protection with integrated electrical measurement functions, enabling monitoring of quantities such as voltage, active, reactive and apparent power, energy, frequency and power factor. This combination of protection and measurement makes the 1SDA101452R1 particularly suitable for modern switchboards where system visibility, energy monitoring and dependable high-current protection are important.
| Series | SACE Tmax XT7 |
|---|---|
| Order code / MPN | 1SDA101452R1 |
| Product type | Moulded-case circuit breaker |
| Frame size | XT7M |
| Performance level | H |
| Rated uninterrupted current | 1250 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V |
| Rated impulse withstand voltage | 8 kV |
| Number of poles | 3 |
| Trip unit | Ekip Touch Measuring LSI |
| Release type | Solid-state electronic release |
| Protection functions | Long-time, short-time and instantaneous |
| Long-time protection adjustment | 0.4–1 × In |
| Short-time protection adjustment | 1–10 × In |
| Rated ultimate breaking capacity at 415 V AC | 70 kA |
| Rated service breaking capacity at 415 V AC | 70 kA |
| Rated short-time withstand current | 20 kA |
| Integrated earth-fault protection | No |
| Mounting configuration | Fixed |
| Main-circuit connection position | Front |
| Main-circuit connection type | Bolt connection |
| Operating mechanism | Stored-energy and lever operating mechanism |
| Motor operator | Optional |
| Protection rating | IP20 |
| Standard | IEC 60947-2 |
| EAN | 8056221012669 |
The ABB 1SDA101452R1 is a SACE Tmax XT7H M moulded-case circuit breaker designed for high-current low-voltage circuit protection, switching and electrical measurement.
This XT7H M circuit breaker has a rated uninterrupted current of 1250 A.
The Ekip Touch Measuring LSI trip unit provides long-time, short-time and instantaneous protection together with electrical measurement capabilities for monitoring the distribution system.
The XT7H configuration provides a rated ultimate short-circuit breaking capacity of 70 kA at 415 V AC.
The 1SDA101452R1 is a three-pole fixed circuit breaker with front bolted main-circuit connections and stored-energy and lever operating mechanisms.
ABB SACE Tmax XT circuit breakers are widely used in industrial and commercial power-distribution systems where dependable protection, advanced electrical measurement and robust high-current switching performance are required.