Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA101366R1 XT7S M 800 Ekip Dip LS/I is an 800 A three-pole fixed moulded-case circuit breaker with adjustable electronic LS/I protection, a stored-energy operating mechanism and 50 kA ultimate breaking capacity at 415 V AC.
£2,224.33
The ABB 1SDA101366R1, designated XT7S M 800 Ekip Dip LS/I In=800A 3p F F, is a high-performance three-pole moulded-case circuit breaker (MCCB) designed for reliable protection and switching in demanding low-voltage electrical distribution systems. As part of the ABB SACE Tmax XT7 M range, it combines an 800 A rated current with an Ekip Dip LS/I solid-state electronic trip unit and a stored-energy operating mechanism.
The circuit breaker incorporates an Ekip Dip LS/I electronic trip unit, providing long-time overload protection together with selectable delayed or instantaneous short-circuit protection. Its long-time protection threshold is adjustable from 0.4–1 × In, while short-circuit protection is adjustable from 1–10 × In, allowing the protection characteristics to be configured for the electrical installation.
The XT7S M version provides a rated ultimate short-circuit breaking capacity of 50 kA at 415 V AC. Its fixed three-pole construction, front terminals and stored-energy operating mechanism make it particularly suitable for industrial switchboards and applications requiring motorised or remote switching capability, with the appropriate operating accessories.
Moulded-case circuit breakers such as the ABB XT7S M protect low-voltage electrical installations against overloads and short circuits while providing reliable circuit switching and isolation. The Ekip Dip LS/I electronic trip unit allows the protection thresholds to be adjusted for the characteristics of the connected circuit, helping engineers achieve effective protection coordination across industrial distribution systems.
The XT7 M platform incorporates a stored-energy operating mechanism and is designed for applications where enhanced switching functionality is required. With suitable motor, opening and closing accessories, the platform can support remote switching applications and is suitable for applications such as network-generator transfer and synchronisation systems.
| Series | SACE Tmax XT7 M |
|---|---|
| ABB product group | T-Max XT 250 Range |
| Order code / MPN | 1SDA101366R1 |
| Product type | Moulded-case circuit breaker (MCCB) |
| Frame size | XT7M |
| Performance level | XT7S |
| Rated current (In) | 800 A |
| Number of poles | 3 |
| Trip unit | Ekip Dip LS/I |
| Trip unit technology | Solid-state electronic |
| Protection functions | Long-time and selectable delayed / instantaneous short-circuit protection (LS/I) |
| Long-time protection adjustment | 0.4–1 × In |
| Long-time protection current range | 320–800 A |
| Short-circuit protection adjustment | 1–10 × In |
| Short-circuit protection current range | 800–8000 A |
| Rated ultimate short-circuit breaking capacity (Icu) | 50 kA at 415 V AC |
| Interruption rating | S |
| Installation | Fixed |
| Terminal arrangement | Front terminals (F) |
| Operating mechanism | Stored-energy mechanism |
| Standard | IEC 60947-2 |
| EAN / GTIN | 8056221011846 |
The ABB 1SDA101366R1 is an 800 A three-pole moulded-case circuit breaker designed for protection and switching in demanding low-voltage power distribution systems, including applications requiring advanced stored-energy switching functionality.
This circuit breaker has a rated current of 800 A, with long-time overload protection adjustable from 320–800 A.
The ABB 1SDA101366R1 has a rated ultimate short-circuit breaking capacity of 50 kA at 415 V AC, corresponding to the S performance level of the XT7 platform.
The Ekip Dip LS/I electronic trip unit provides long-time overload protection together with selectable delayed or instantaneous short-circuit protection, with adjustable protection thresholds for coordination with the electrical installation.
This model is a fixed three-pole circuit breaker with front terminals and a stored-energy operating mechanism, designed for integration into low-voltage switchboards and power distribution assemblies.
ABB SACE Tmax XT moulded-case circuit breakers are designed for demanding low-voltage power distribution applications where dependable electronic circuit protection, high breaking performance and flexible switching functionality are essential.