Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA101264R1 XT7L 1250 is a fixed four-pole 1250 A moulded case circuit breaker with front terminals, 120 kA ultimate short-circuit breaking capacity at 400 V AC and an Ekip G Dip LS/I electronic trip unit designed for generator and low-voltage circuit protection.
£5,496.49
The ABB 1SDA101264R1 is a high-performance SACE Tmax XT moulded case circuit breaker (MCCB) designed for generator, transformer and installation protection in demanding low-voltage electrical distribution systems. Identified as XT7L 1250 Ekip G Dip LS/I In=1250A 4p F F, this four-pole circuit breaker combines fixed construction, front terminals, lever operation and ABB's Ekip G Dip LS/I electronic trip unit.
As part of the ABB SACE Tmax XT7 range, the breaker is specifically configured with the Ekip G Dip LS/I release for generator protection applications. Its electronic protection functions provide long-time overload and instantaneous short-circuit protection, helping safeguard generators and associated distribution circuits against damaging overcurrent conditions.
With a rated uninterrupted current of 1250 A, rated voltage of 690 V and an ultimate short-circuit breaking capacity of 120 kA at 400 V AC, 50 Hz, the 1SDA101264R1 is suited to high-capacity generator systems, industrial switchboards and critical power distribution installations. Its fixed four-pole construction with front terminals provides practical integration into low-voltage switchgear assemblies.
Generator circuit breakers protect generating equipment and associated distribution networks against abnormal current conditions while providing reliable switching and isolation. Generator applications can have different fault-current characteristics from utility-fed distribution systems, making appropriately configured electronic protection important for dependable operation and equipment protection.
ABB's Ekip G Dip LS/I trip unit is designed for generator protection applications and combines adjustable long-time overload protection with short-circuit protection functions. When integrated with the high-breaking-capacity XT7L platform, it provides a robust solution for generator feeders, standby power systems and industrial installations where dependable circuit protection is essential.
| Series | SACE Tmax XT |
|---|---|
| Frame size | XT7 |
| Order code / MPN | 1SDA101264R1 |
| Product group | T-Max XT 250 Range |
| Product type | Moulded case circuit breaker (MCCB) |
| Primary application | Generator, transformer and installation protection |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated current (In) | 1250 A |
| Rated voltage | 690 V |
| Number of poles | 4 |
| Trip unit | Ekip G Dip LS/I |
| Trip unit technology | Electronic / solid-state |
| Protection functions | Long-time overload and instantaneous short-circuit protection (LS/I) |
| Overload release current setting | 500–1250 A |
| Short-time delayed short-circuit setting | 750–12500 A |
| Instantaneous short-circuit setting | 1250–12500 A |
| Integrated earth-fault protection | No |
| Interruption rating | L |
| Ultimate short-circuit breaking capacity (Icu) | 120 kA at 400 V AC, 50 Hz |
| Power loss | 57 W |
| Mounting type | Fixed |
| Terminal position | Front |
| Main circuit connection | Bolted connection |
| Operating mechanism | Lever / toggle |
| Motor drive | Optional |
| Protection rating | IP20 |
| EAN | 8056221010825 |
The ABB 1SDA101264R1 is a four-pole moulded case circuit breaker equipped with an Ekip G Dip LS/I electronic trip unit and is particularly suited to generator protection as well as transformer and installation protection applications.
The XT7L 1250 has a rated uninterrupted current of 1250 A, making it suitable for high-current generator and low-voltage power distribution applications.
The Ekip G Dip LS/I electronic trip unit provides configurable long-time overload and short-circuit protection functions designed to protect generators and associated electrical distribution circuits.
The ABB XT7L version has an ultimate short-circuit breaking capacity of 120 kA at 400 V AC, 50 Hz, providing high fault-interruption capability for demanding electrical installations.
The 1SDA101264R1 is a fixed four-pole circuit breaker with front terminals and a lever / toggle operating mechanism, designed for installation within low-voltage switchboards, generator panels and industrial electrical assemblies.
ABB SACE Tmax XT circuit breakers provide dependable low-voltage circuit protection for generator, industrial and infrastructure applications, combining electronic trip technology, high breaking performance and flexible integration into modern electrical distribution systems.