1SDA101258R1 ABB XT7L 800 Ekip Hi-Touch LSIG 800A 4-Pole Circuit Breaker

1SDA101258R1 ABB XT7L 800 Ekip Hi-Touch LSIG 800A 4-Pole Circuit Breaker

ABB 1SDA101258R1 XT7L 800 is a fixed four-pole 800 A moulded case circuit breaker with front terminals, 120 kA ultimate short-circuit breaking capacity at 415 V AC and an Ekip Hi-Touch LSIG electronic trip unit for advanced overload, short-circuit and ground-fault protection.

SKU: 1SDA101258R1MPN: 1SDA101258R1
Price
List Price £11,300.16 ex VAT
Your Price (ex VAT) Save 25%
£8,475.12 25% OFF
You save £2,825.04 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8,475.12
Trade pricing is personalised to your account

Manufacturer Lead Time

£8,475.12

Why Choose the ABB 1SDA101258R1 XT7L 800 Circuit Breaker?

The ABB 1SDA101258R1 is a high-performance SACE Tmax XT moulded case circuit breaker (MCCB) designed for dependable protection and switching in demanding low-voltage electrical distribution systems. Identified as XT7L 800 Ekip Hi-Touch LSIG In=800A 4p F F, this four-pole circuit breaker combines fixed construction, front terminals, lever operation and ABB's advanced Ekip Hi-Touch LSIG electronic trip unit.

As part of the ABB SACE Tmax XT7 range, the breaker provides comprehensive configurable electronic protection against overload, short-circuit and earth-fault conditions. The Ekip Hi-Touch LSIG trip unit incorporates long-time, short-time, instantaneous and ground-fault protection functions, making the breaker suitable for sophisticated power distribution systems where advanced protection and effective coordination are required.

With a rated uninterrupted current of 800 A, rated operational voltage up to 690 V AC and an ultimate short-circuit breaking capacity of 120 kA at 415 V AC, the 1SDA101258R1 is well suited to industrial switchboards, high-current distribution feeders, infrastructure systems and other demanding electrical installations. Its fixed four-pole construction with front terminals supports practical integration into low-voltage switchboards and distribution assemblies.

Key Advantages

  • High-performance ABB SACE Tmax XT7L moulded case circuit breaker for demanding power distribution applications.
  • 800 A rated uninterrupted current suitable for high-current electrical installations.
  • Four-pole configuration for three-phase distribution systems requiring four-pole switching and protection.
  • Advanced Ekip Hi-Touch LSIG electronic trip unit for configurable circuit protection.
  • Long-time, short-time, instantaneous and ground-fault protection functions.
  • 120 kA ultimate short-circuit breaking capacity at 415 V AC for installations with high prospective fault currents.
  • Fixed construction with front terminals simplifies integration into switchboards and distribution panels.

Key Features

  • ABB SACE Tmax XT7L series.
  • 800 A rated uninterrupted current.
  • Four-pole circuit breaker.
  • Ekip Hi-Touch LSIG electronic trip unit.
  • Long-time overload protection.
  • Short-time short-circuit protection.
  • Instantaneous short-circuit protection.
  • Ground-fault protection through the LSIG trip unit.
  • 690 V AC rated operational voltage.
  • 1000 V rated insulation voltage.
  • 8 kV rated impulse withstand voltage.
  • 120 kA ultimate and service breaking capacity at 415 V AC.
  • 20 kA rated short-time withstand current.
  • Fixed circuit-breaker construction.
  • Front terminal connection.
  • Lever operating mechanism for manual switching.

Advanced Ekip Hi-Touch LSIG Protection for Power Distribution

Moulded case circuit breakers such as the ABB XT7L protect electrical circuits against damaging overload, short-circuit and earth-fault conditions while providing reliable switching and isolation. The XT7L's high interruption capability makes it particularly suitable for industrial installations and major distribution systems where prospective fault currents can be substantial.

The Ekip Hi-Touch LSIG electronic trip unit combines long-time, short-time, instantaneous and ground-fault protection functions within ABB's advanced electronic protection platform. Configurable protection characteristics support effective coordination while helping safeguard conductors, equipment and critical low-voltage distribution networks.

Typical Applications

  • Industrial low-voltage switchboards and distribution panels.
  • Main and sub-main electrical distribution circuits.
  • High-current incoming and distribution feeders.
  • Transformer and generator distribution systems.
  • Manufacturing plants and production facilities.
  • Commercial and infrastructure power distribution.
  • Electrical systems requiring comprehensive LSIG protection.
  • OEM switchgear and electrical panel building.

Technical Specifications

Series SACE Tmax XT
Frame size XT7
Order code / MPN 1SDA101258R1
Product group T-Max XT 250 Range
Product type Moulded case circuit breaker (MCCB)
Rated uninterrupted current (Iu) 800 A
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Number of poles 4
Trip unit Ekip Hi-Touch LSIG
Trip unit technology Electronic / solid-state
Protection functions Long-time, short-time, instantaneous and ground-fault protection (LSIG)
Interruption rating L
Ultimate short-circuit breaking capacity (Icu) 120 kA at 415 V AC
Service short-circuit breaking capacity (Ics) 120 kA at 415 V AC
Rated short-time withstand current (Icw) 20 kA
Power loss 24 W per pole at rated operating conditions
Mounting type Fixed
Terminal type Front terminals
Main circuit connection Bolted connection
Operating mechanism Lever / toggle
Motor drive Optional
Protection rating IP20
EAN 8056221010764
Dimensions (W × H × D) 280 × 268 × 166 mm
Net weight 12.5 kg

Frequently Asked Questions

What is the ABB 1SDA101258R1 used for?

The ABB 1SDA101258R1 is a four-pole moulded case circuit breaker used to protect and switch high-current low-voltage electrical distribution circuits in industrial, commercial and infrastructure applications.

What is the rated current of this circuit breaker?

The XT7L 800 has a rated uninterrupted current of 800 A, making it suitable for demanding high-current power distribution applications.

What protection does the Ekip Hi-Touch LSIG trip unit provide?

The Ekip Hi-Touch LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection for connected circuits and electrical equipment.

What is the breaking capacity of the ABB XT7L 800?

The XT7L 800 provides an ultimate short-circuit breaking capacity of 120 kA at 415 V AC, with a service short-circuit breaking capacity of 120 kA at the same voltage.

How is the ABB 1SDA101258R1 installed?

The 1SDA101258R1 is a fixed four-pole circuit breaker with front terminals and a lever operating mechanism, designed for installation within low-voltage switchboards, distribution panels and industrial electrical assemblies.

Trusted Industrial Circuit Protection from ABB

ABB SACE Tmax XT circuit breakers are widely used by panel builders, electrical engineers and industrial operators for reliable low-voltage circuit protection, high breaking performance and flexible integration into modern power distribution systems.