1SDA101245R1 ABB XT7L 1600 Ekip Touch LSIG 1600A 4-Pole Circuit Breaker

1SDA101245R1 ABB XT7L 1600 Ekip Touch LSIG 1600A 4-Pole Circuit Breaker

ABB 1SDA101245R1 XT7L 1600 is a fixed four-pole 1600 A moulded case circuit breaker with front terminals, 120 kA ultimate short-circuit breaking capacity at 400 V AC and an Ekip Touch LSIG electronic trip unit for comprehensive low-voltage circuit protection.

SKU: 1SDA101245R1MPN: 1SDA101245R1
Price
List Price £11,603.29 ex VAT
Your Price (ex VAT) Save 25%
£8,702.47 25% OFF
You save £2,900.82 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8,702.47
Trade pricing is personalised to your account

Manufacturer Lead Time

£8,702.47

Why Choose the ABB 1SDA101245R1 XT7L 1600 Circuit Breaker?

The ABB 1SDA101245R1 is a high-performance SACE Tmax XT moulded case circuit breaker (MCCB) designed for dependable protection and switching of high-current low-voltage electrical distribution systems. Identified as XT7L 1600 Ekip Touch LSIG In=1600A 4p F F, this four-pole circuit breaker combines fixed mounting, front terminals, a lever operating mechanism and ABB's advanced Ekip Touch LSIG solid-state electronic trip unit.

As part of the ABB SACE Tmax XT7 range, the breaker provides comprehensive electronic protection for demanding industrial and commercial power distribution applications. The Ekip Touch LSIG release incorporates long-time, short-time, instantaneous and ground-fault protection functions, providing configurable protection for cables, equipment and downstream electrical systems.

With a rated uninterrupted current of 1600 A, a rated voltage of 690 V and an ultimate short-circuit breaking capacity of 120 kA at 400 V AC, the 1SDA101245R1 is ideal for high-capacity switchboards, transformer and generator protection, industrial distribution panels and infrastructure systems. Its fixed four-pole construction with front terminals enables straightforward integration into low-voltage electrical assemblies.

Key Advantages

  • High-performance ABB SACE Tmax XT7L moulded case circuit breaker for demanding power distribution applications.
  • 1600 A rated uninterrupted current suitable for high-current electrical installations.
  • Four-pole configuration for three-phase distribution systems requiring four-pole switching and protection.
  • Advanced Ekip Touch LSIG electronic trip unit for configurable circuit protection.
  • Long-time, short-time, instantaneous and ground-fault protection functions.
  • 120 kA ultimate short-circuit breaking capacity at 400 V AC for installations with high prospective fault currents.
  • Fixed mounting with front terminals simplifies integration into switchboards and distribution panels.

Key Features

  • ABB SACE Tmax XT7L series.
  • 1600 A rated uninterrupted current.
  • Four-pole circuit breaker.
  • Ekip Touch LSIG solid-state electronic trip unit.
  • Long-time overload protection.
  • Short-time short-circuit protection.
  • Instantaneous short-circuit protection.
  • Ground-fault protection functionality through the LSIG trip unit.
  • 690 V rated voltage.
  • 120 kA ultimate breaking capacity at 400 V AC.
  • Fixed circuit-breaker construction.
  • Front terminal connection.
  • Lever operating mechanism for manual switching.
  • Suitable for transformer, generator and installation protection.

Advanced LSIG Protection for Power Distribution

Moulded case circuit breakers such as the ABB XT7L protect electrical circuits against damaging overload, short-circuit and earth-fault conditions while providing reliable switching and isolation. The XT7L's high interruption capability makes it particularly suitable for industrial installations and major distribution systems where prospective fault currents can be substantial.

The Ekip Touch LSIG electronic trip unit combines long-time, short-time, instantaneous and ground-fault protection with ABB's advanced electronic protection platform. This comprehensive protection helps safeguard conductors, transformers, generators, equipment and distribution networks while providing the configurable protection required for modern low-voltage systems.

Typical Applications

  • Industrial low-voltage switchboards and distribution panels.
  • Main and sub-main electrical distribution circuits.
  • High-current incoming and distribution feeders.
  • Transformer and generator protection.
  • Manufacturing plants and production facilities.
  • Commercial and infrastructure power distribution.
  • Electrical systems requiring comprehensive LSIG protection.
  • OEM switchgear and electrical panel building.

Technical Specifications

Series SACE Tmax XT
Frame size XT7
Order code / MPN 1SDA101245R1
Product group T-Max XT 250 Range
Product type Moulded case circuit breaker (MCCB)
Rated uninterrupted current (Iu) 1600 A
Rated voltage 690 V
Number of poles 4
Trip unit Ekip Touch LSIG
Trip unit technology Electronic / solid-state
Protection functions Long-time, short-time, instantaneous and ground-fault protection (LSIG)
Interruption rating L
Ultimate short-circuit breaking capacity (Icu) 120 kA at 400 V AC, 50 Hz
Overload release current setting range 640–1600 A
Short-time delayed short-circuit setting range 960–16000 A
Instantaneous short-circuit setting range 2400–24000 A
Power loss 94 W
Mounting type Fixed
Terminal type Front terminals
Main circuit connection Bolted connection
Operating mechanism Lever
Protection rating IP20
EAN 8056221015486
Dimensions (W × H × D) 280 × 268 × 166 mm
Weight 12.5 kg

Frequently Asked Questions

What is the ABB 1SDA101245R1 used for?

The ABB 1SDA101245R1 is a four-pole moulded case circuit breaker designed to protect and switch high-current low-voltage electrical distribution circuits, including transformer, generator and installation protection applications.

What is the rated current of this circuit breaker?

The XT7L 1600 has a rated uninterrupted current of 1600 A, making it suitable for demanding high-current power distribution applications.

What protection does the Ekip Touch LSIG trip unit provide?

The Ekip Touch LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection for connected circuits and electrical equipment.

What is the breaking capacity of the ABB XT7L 1600?

The XT7L version provides an ultimate short-circuit breaking capacity of 120 kA at 400 V AC, 50 Hz, making it suitable for electrical distribution systems with high prospective fault currents.

How is the ABB 1SDA101245R1 installed?

The 1SDA101245R1 is a fixed four-pole circuit breaker with front terminals and a lever operating mechanism, designed for installation within low-voltage switchboards, distribution panels and industrial electrical assemblies.

Trusted Industrial Circuit Protection from ABB

ABB SACE Tmax XT circuit breakers are widely used by panel builders, electrical engineers and industrial operators for reliable low-voltage circuit protection, high breaking performance and flexible integration into modern power distribution systems.