Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA101173R1 XT7H 1600 Ekip Dip LS/I four-pole fixed moulded case circuit breaker with a 1600 A rated current, 70 kA breaking capacity at 415 V AC, front terminals and adjustable electronic overload and instantaneous short-circuit protection.
£5,617.03
The ABB XT7H 1600 Ekip Dip LS/I In=1600A 4p F F, order code 1SDA101173R1, is a high-performance four-pole moulded case circuit breaker (MCCB) from the ABB SACE Tmax XT range. Designed for demanding low-voltage power distribution applications, it combines a 1600 A rated current with an Ekip Dip LS/I solid-state electronic trip unit and the high-breaking-capacity XT7H performance level.
The Ekip Dip LS/I electronic release provides adjustable long-time overload and instantaneous short-circuit protection. Its long-time protection can be set from 0.4–1 × In, while instantaneous protection is adjustable from 1–10 × In, allowing the protective response to be coordinated with the characteristics of the electrical installation.
As an XT7H version, the 1SDA101173R1 provides a rated ultimate short-circuit breaking capacity of 70 kA at 415 V AC. Its four-pole fixed construction, front terminals and lever operating mechanism make it particularly suitable for high-current industrial and commercial switchboards where substantial fault-interruption capability is required.
The ABB Ekip Dip LS/I trip unit combines adjustable long-time overload protection with instantaneous short-circuit protection. On this 1600 A model, the overload threshold can be adjusted across 640–1600 A, while instantaneous protection spans 1600–16000 A, allowing the circuit breaker's response to be matched to the protection requirements of the installation.
The XT7H platform is designed for electrical systems requiring increased short-circuit interruption capability. With 70 kA Icu and Ics at 415 V AC, a 20 kA short-time withstand rating and a 690 V AC rated operational voltage, the 1SDA101173R1 provides robust protection for high-current feeders, main distribution boards and demanding industrial power systems.
| Series | SACE Tmax XT |
|---|---|
| Order code / Product ID | 1SDA101173R1 |
| Alternate catalogue number | XT7HE416FEFF000XXX |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame size | XT7 |
| Breaking-performance version | XT7H |
| Rated uninterrupted current (Iu) | 1600 A |
| Rated current (In) | 1600 A |
| Number of poles | 4 |
| Trip unit | Ekip Dip LS/I |
| Release type | Solid-state electronic release |
| Protection functions | Long-time overload and instantaneous short circuit (LS/I) |
| Overload release setting | 0.4–1 × In |
| Overload release adjustment range | 640–1600 A |
| Instantaneous short-circuit setting | 1–10 × In |
| Instantaneous short-circuit adjustment range | 1600–16000 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Rated short-time withstand current (Icw) | 20 kA |
| Interruption rating | H |
| Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC | 70 kA |
| Rated service short-circuit breaking capacity (Ics) at 415 V AC | 70 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC | 50 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 42 kA |
| Power loss at rated operating conditions per pole | 94 W |
| Electrical durability | 3000 cycles |
| Mechanical durability | 10000 cycles |
| Installation | Fixed |
| Terminal position | Front |
| Operating mechanism | Lever |
| Current type | AC |
| Standard | IEC |
| GTIN / EAN | 8056221014762 |
The ABB 1SDA101173R1 is a 1600 A four-pole moulded case circuit breaker designed for demanding low-voltage power distribution systems requiring adjustable electronic overload and short-circuit protection with high fault-breaking performance.
The circuit breaker has a rated current of 1600 A. Its long-time overload setting is adjustable from 0.4–1 × In, corresponding to 640–1600 A.
The 1SDA101173R1 is fitted with an Ekip Dip LS/I solid-state electronic trip unit providing adjustable long-time overload and instantaneous short-circuit protection.
The XT7H circuit breaker has a rated ultimate short-circuit breaking capacity of 70 kA at 415 V AC. Its Icu is 50 kA at 500 V AC and 42 kA at 690 V AC.
The 1SDA101173R1 is a fixed four-pole circuit breaker with front terminals and a lever operating mechanism, designed for integration into low-voltage switchboards and high-current power distribution assemblies.
ABB SACE Tmax XT moulded case circuit breakers combine configurable electronic protection, high short-circuit breaking performance and robust construction for demanding industrial, commercial and infrastructure low-voltage power distribution systems.
We use cookies