1SDA101160R1 ABB XT7S 1250 Ekip G Hi-Touch LSIG 1250 4p FF Circuit Breaker

1SDA101160R1 ABB XT7S 1250 Ekip G Hi-Touch LSIG 1250 4p FF Circuit Breaker

ABB 1SDA101160R1 XT7S 1250 Ekip G Hi-Touch LSIG four-pole fixed moulded case circuit breaker with a 1250 A rated current, 50 kA breaking-performance class, front terminals and advanced electronic generator protection.

SKU: 1SDA101160R1MPN: 1SDA101160R1
Price
List Price £11,743.98 ex VAT
Your Price (ex VAT) Save 25%
£8,807.99 25% OFF
You save £2,936.00 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8,807.99
Trade pricing is personalised to your account

Manufacturer Lead Time

£8,807.99

Why Choose the ABB XT7S 1250 Ekip G Hi-Touch LSIG 1250 4p FF Circuit Breaker?

The ABB XT7S 1250 Ekip G Hi-Touch LSIG 1250 4p FF, order code 1SDA101160R1, is a high-performance four-pole moulded case circuit breaker (MCCB) designed for generator protection and demanding low-voltage electrical distribution systems. Part of the ABB SACE Tmax XT series, it combines a 1250 A rated uninterrupted current with the advanced Ekip G Hi-Touch LSIG electronic trip unit.

The Ekip G Hi-Touch LSIG solid-state release provides sophisticated electronic protection for generator-fed electrical networks. Its LSIG functionality supports long-time, short-time, instantaneous and ground-fault protection, helping protect generators, cables, switchgear and connected equipment while enabling accurate protection coordination within complex installations.

The XT7S version provides a 50 kA breaking-performance class and is designed for systems with a rated voltage of 690 V. Its four-pole fixed construction, front terminals and lever operating mechanism provide a robust solution for integration into generator switchboards, industrial distribution boards and other high-current electrical assemblies.

Key Advantages

  • High-performance 1250 A moulded case circuit breaker for generator and power distribution protection.
  • Four-pole configuration suitable for demanding three-phase systems.
  • Advanced Ekip G Hi-Touch LSIG electronic trip unit.
  • LSIG functionality for comprehensive electronic circuit protection.
  • 500–1250 A overload release adjustment range.
  • 50 kA XT7S breaking-performance class.
  • Fixed installation with front terminals for switchboard integration.
  • Part of the advanced ABB SACE Tmax XT circuit breaker platform.

Key Features

  • ABB SACE Tmax XT7S moulded case circuit breaker.
  • 1250 A rated uninterrupted current.
  • Four-pole construction.
  • Ekip G Hi-Touch LSIG solid-state electronic release.
  • Designed for generator protection and demanding power distribution applications.
  • 690 V rated voltage.
  • Overload adjustment from 500–1250 A.
  • Short-time delayed short-circuit adjustment from 750–12500 A.
  • Instantaneous short-circuit adjustment from 1875–18750 A.
  • IP20 protection rating.
  • Fixed installation with front main-circuit connections.
  • Optional motor operator capability.

Advanced Hi-Touch Protection for Generator Applications

Generator-fed electrical systems require carefully coordinated protection because their operating and fault-current characteristics can differ from conventional utility-fed networks. The ABB Ekip G Hi-Touch LSIG platform provides advanced electronic protection capabilities for generator applications, combining long-time, short-time, instantaneous and ground-fault functions to support comprehensive protection of the generator and associated electrical distribution system.

The XT7S platform combines this advanced generator-focused protection with robust high-current moulded case circuit breaker construction. With its 1250 A rating, four-pole design, 690 V rated voltage and 50 kA breaking-performance class, the 1SDA101160R1 is well suited to generator switchboards, standby power installations and demanding industrial power distribution applications.

Typical Applications

  • Generator protection systems.
  • Generator control and distribution switchboards.
  • Standby and emergency power installations.
  • Industrial low-voltage switchboards.
  • Main and sub-main power distribution.
  • Manufacturing and process plants.
  • High-current generator feeders.
  • Electrical systems requiring advanced LSIG electronic protection.

Technical Specifications

Series SACE Tmax XT
Order code / Product ID 1SDA101160R1
Alternate catalogue number XT7SE412EZFF000XXX
Product type Moulded case circuit breaker (MCCB)
Frame size XT7
Breaking-performance version XT7S
Application Generator and low-voltage distribution protection
Rated uninterrupted current (Iu) 1250 A
Rated current (In) 1250 A
Number of poles 4
Trip unit Ekip G Hi-Touch LSIG
Release type Solid-state electronic release
Protection functions Long-time, short-time, instantaneous and ground fault (LSIG)
Rated voltage 690 V
Breaking-performance class 50 kA
Overload release adjustment range 500–1250 A
Short-time delayed short-circuit release adjustment range 750–12500 A
Instantaneous short-circuit release adjustment range 1875–18750 A
Power dissipation 57 W
Protection rating IP20
Installation Fixed
Main circuit connection Bolt connection
Terminal position Front
Operating mechanism Lever
Complete device with protection unit Yes
Integrated motor operator No
Optional motor operator Yes
Standard IEC
EAN 8056221014632

Frequently Asked Questions

What is the ABB 1SDA101160R1 used for?

The ABB 1SDA101160R1 is a 1250 A four-pole moulded case circuit breaker equipped with an Ekip G Hi-Touch LSIG electronic trip unit for generator protection and demanding low-voltage electrical distribution applications.

What is the rated current of the ABB XT7S 1SDA101160R1?

The circuit breaker has a rated uninterrupted current and trip-unit current of 1250 A.

Which trip unit is fitted to the ABB 1SDA101160R1?

The 1SDA101160R1 is fitted with an Ekip G Hi-Touch LSIG solid-state electronic trip unit providing advanced long-time, short-time, instantaneous and ground-fault protection functions.

What is the breaking-performance class of the ABB XT7S 1250 1SDA101160R1?

The ABB 1SDA101160R1 is an XT7S 50 kA circuit breaker, providing robust short-circuit performance for demanding generator and low-voltage power distribution systems.

How is the ABB XT7S 1SDA101160R1 installed?

The 1SDA101160R1 is a fixed four-pole circuit breaker with front terminals, bolt-connected main circuit connections and a lever operating mechanism. An electric motor operator can be fitted as an option.

Trusted Generator Protection from ABB

ABB SACE Tmax XT moulded case circuit breakers with Ekip G Hi-Touch electronic protection combine advanced generator protection, configurable LSIG functionality and robust short-circuit performance for demanding industrial and commercial low-voltage power systems.