1SDA101157R1 ABB XT7S 1600 Ekip G Touch LSIG In1600 4p FF Circuit Breaker

1SDA101157R1 ABB XT7S 1600 Ekip G Touch LSIG In1600 4p FF Circuit Breaker

ABB 1SDA101157R1 XT7S 1600 Ekip G Touch LSIG four-pole fixed moulded case circuit breaker with a 1600 A rated current, 50 kA breaking capacity at 400 V AC, front terminals and advanced electronic generator protection.

SKU: 1SDA101157R1MPN: 1SDA101157R1
Price
List Price £12,231.67 ex VAT
Your Price (ex VAT) Save 25%
£9,173.75 25% OFF
You save £3,057.92 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £9,173.75
Trade pricing is personalised to your account

Manufacturer Lead Time

£9,173.75

Why Choose the ABB XT7S 1600 Ekip G Touch LSIG In1600 4p FF Circuit Breaker?

The ABB XT7S 1600 Ekip G Touch LSIG In1600 4p FF, order code 1SDA101157R1, is a high-performance four-pole moulded case circuit breaker (MCCB) designed for generator protection and demanding low-voltage electrical distribution systems. Part of the ABB SACE Tmax XT series, it combines a 1600 A rated uninterrupted current with the advanced Ekip G Touch LSIG electronic trip unit.

The Ekip G Touch LSIG solid-state release provides long-time, short-time, instantaneous and ground-fault protection functions, delivering comprehensive electronic protection for generator-fed and industrial electrical networks. Adjustable protection settings allow the circuit breaker to be coordinated with generators, cables, switchgear and downstream equipment while providing effective protection against overload and short-circuit conditions.

The XT7S version provides a rated ultimate short-circuit breaking capacity of 50 kA at 400 V AC, 50 Hz. Its four-pole, fixed configuration with front terminals and lever operating mechanism makes the 1SDA101157R1 a robust solution for generator switchboards, industrial distribution boards and other high-current low-voltage assemblies.

Key Advantages

  • High-performance 1600 A moulded case circuit breaker for generator and power distribution protection.
  • Four-pole configuration for demanding three-phase electrical systems.
  • Advanced Ekip G Touch LSIG electronic trip unit.
  • Provides long-time, short-time, instantaneous and ground-fault protection.
  • Adjustable electronic protection supports effective system coordination.
  • 50 kA ultimate short-circuit breaking capacity at 400 V AC, 50 Hz.
  • Fixed installation with front terminals for switchboard integration.
  • Part of the advanced ABB SACE Tmax XT circuit breaker platform.

Key Features

  • ABB SACE Tmax XT7S moulded case circuit breaker.
  • 1600 A rated uninterrupted current (Iu).
  • 1600 A rated trip-unit current (In).
  • Four-pole construction.
  • Ekip G Touch LSIG solid-state electronic release.
  • LSIG functions for long-time, short-time, instantaneous and ground-fault protection.
  • 690 V AC rated voltage.
  • 50 kA Icu at 400 V AC, 50 Hz.
  • Overload adjustment from 640–1600 A.
  • Short-time delayed short-circuit adjustment from 960–16000 A.
  • Instantaneous short-circuit adjustment from 2400–24000 A.
  • IP20 protection rating.

Advanced LSIG Protection for Generator Applications

Generator-fed electrical systems require carefully coordinated protection because their operating and fault-current characteristics can differ from conventional utility-fed networks. The ABB Ekip G Touch LSIG trip unit provides long-time, short-time, instantaneous and ground-fault protection, giving the circuit breaker a comprehensive set of electronic protection functions for generators and associated electrical distribution equipment.

The XT7S platform combines this generator-focused electronic protection with robust high-current circuit breaker performance. With its 1600 A rating, four-pole construction, 690 V AC rated voltage and 50 kA Icu at 400 V AC, the 1SDA101157R1 is well suited to generator switchboards, standby power systems and demanding industrial power distribution applications.

Typical Applications

  • Generator protection systems.
  • Generator control and distribution switchboards.
  • Standby and emergency power installations.
  • Industrial low-voltage switchboards.
  • Main and sub-main power distribution.
  • Manufacturing and process plants.
  • High-current generator feeders.
  • Electrical systems requiring advanced LSIG electronic protection.

Technical Specifications

Series SACE Tmax XT
Order code / Product ID 1SDA101157R1
Product type Moulded case circuit breaker (MCCB)
Frame XT7
Breaking-performance version XT7S
Application Generator and low-voltage distribution protection
Rated uninterrupted current (Iu) 1600 A
Rated current (In) 1600 A
Number of poles 4
Trip unit Ekip G Touch LSIG
Release type Solid-state electronic release
Protection functions Long-time, short-time, instantaneous and ground fault (LSIG)
Rated voltage 690 V AC
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz 50 kA
Overload release adjustment range 640–1600 A
Short-time delayed short-circuit release adjustment range 960–16000 A
Instantaneous short-circuit release adjustment range 2400–24000 A
Power dissipation 94 W
Protection rating IP20
Installation Fixed
Main circuit connection Bolt connection
Terminal position Front
Operating mechanism Lever
Complete device with protection unit Yes
Integrated motor operator No
Optional motor operator Yes
EAN 8056221014601

Frequently Asked Questions

What is the ABB 1SDA101157R1 used for?

The ABB 1SDA101157R1 is a 1600 A four-pole moulded case circuit breaker equipped with an Ekip G Touch LSIG electronic trip unit for generator protection and demanding low-voltage electrical distribution applications.

What is the rated current of the ABB XT7S 1SDA101157R1?

The circuit breaker has a rated uninterrupted current and trip-unit current of 1600 A.

Which trip unit is fitted to the ABB 1SDA101157R1?

The 1SDA101157R1 is fitted with an Ekip G Touch LSIG solid-state electronic trip unit providing long-time, short-time, instantaneous and ground-fault protection.

What is the breaking capacity of the ABB XT7S 1600 1SDA101157R1?

The circuit breaker has a rated ultimate short-circuit breaking capacity of 50 kA at 400 V AC, 50 Hz.

How is the ABB XT7S 1SDA101157R1 installed?

The 1SDA101157R1 is a fixed four-pole circuit breaker with front terminals, bolt-connected main circuit connections and a lever operating mechanism. A motor operator is not integrated but can be fitted as an option.

Trusted Generator Protection from ABB

ABB SACE Tmax XT moulded case circuit breakers with Ekip G electronic protection combine advanced generator protection, configurable LSIG functions and robust short-circuit performance for demanding industrial and commercial low-voltage power systems.