The ABB XT7S 1600 Ekip G Dip LS/I In1600A 4p F F, order code 1SDA101153R1, is a high-performance four-pole moulded case circuit breaker (MCCB) engineered for generator protection and demanding low-voltage power distribution applications. Part of the ABB SACE Tmax XT series, it combines a 1600 A rated current with the Ekip G Dip LS/I electronic trip unit and the XT7S 50 kA performance level.
The Ekip G Dip LS/I solid-state release is designed for generator applications and provides adjustable long-time overload, short-time delayed and instantaneous short-circuit protection. Its electronic protection characteristics allow the circuit breaker to be coordinated with generator-fed networks while protecting conductors, switchgear and connected equipment against damaging overcurrent conditions.
With a rated uninterrupted current of 1600 A, four-pole construction and a rated operational voltage of 690 V AC, the XT7S is suitable for substantial generator and industrial distribution systems. Fixed construction, front terminals and a lever operating mechanism provide a robust configuration for integration into low-voltage switchboards and generator distribution assemblies.
Generator-fed electrical systems require carefully coordinated protection because their fault-current characteristics can differ from conventional utility-fed networks. The ABB Ekip G Dip LS/I trip unit is intended for generator protection, providing adjustable long-time overload, short-time delayed and instantaneous short-circuit functions that allow the protective response to be matched to the generator and associated electrical installation.
The XT7S platform combines this generator-focused electronic protection with robust high-current circuit breaker performance. With its 1600 A rating, four-pole construction, 690 V AC operational voltage and 50 kA Icu at 415 V AC, the 1SDA101153R1 is well suited to generator switchboards, standby power systems and demanding industrial power distribution applications.
| Series | SACE Tmax XT |
|---|---|
| Order code / Product ID | 1SDA101153R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame | XT7 |
| Application | Generator protection |
| Rated uninterrupted current (Iu) | 1600 A |
| Rated current (In) | 1600 A |
| Number of poles | 4 |
| Trip unit | Ekip G Dip LS/I |
| Release type | Electronic (EL) |
| Protection functions | Long-time, short-time and instantaneous (LS/I) |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Rated short-time withstand current (Icw) | 20 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 380–440 V AC | 50 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–525 V AC | 45 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 30 kA |
| Overload release adjustment range | 640–1600 A |
| Short-time delayed short-circuit release adjustment range | 960–16000 A |
| Instantaneous short-circuit release adjustment range | 1600–16000 A |
| Integrated earth-fault protection | No |
| Short-circuit performance level | S |
| Protection rating | IP20 |
| Power loss at rated operating conditions per pole | 94 W |
| Electrical durability | 3000 cycles |
| Mechanical durability | 10000 cycles |
| Installation | Fixed |
| Main circuit connection | Bolt connection |
| Terminal position | Front |
| Operating mechanism | Lever |
| Optional motor operator | Yes |
| Standard | IEC 60947-2 |
| EAN | 8056221014564 |
The ABB 1SDA101153R1 is a 1600 A four-pole moulded case circuit breaker equipped with an Ekip G Dip LS/I electronic trip unit for generator protection and demanding low-voltage electrical distribution applications.
The circuit breaker has a rated uninterrupted current and rated trip-unit current of 1600 A.
The 1SDA101153R1 is fitted with an Ekip G Dip LS/I electronic trip unit designed for generator protection, with adjustable long-time overload, short-time delayed and instantaneous short-circuit protection.
The XT7S 1SDA101153R1 has a rated ultimate short-circuit breaking capacity of 50 kA at 380–440 V AC, reducing to 45 kA at 500–525 V AC and 30 kA at 690 V AC.
The 1SDA101153R1 is a fixed four-pole circuit breaker with front terminals, bolt-connected main circuit connections and a lever operating mechanism, designed for integration into low-voltage switchboards and generator distribution assemblies.
ABB SACE Tmax XT moulded case circuit breakers with Ekip G electronic protection combine configurable generator protection, high short-circuit performance and robust construction for demanding industrial and commercial low-voltage power systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.