ABB 1SDA101141R1 XT7S 1600 Ekip Touch Measuring LSIG four-pole fixed moulded case circuit breaker with a 1600 A rated current, front terminals and integrated electronic protection and electrical measurement.
£6,984.17
The ABB XT7S 1600 Ekip Touch Meas.LSIG 1600 4pFF, order code 1SDA101141R1, is a high-performance four-pole moulded case circuit breaker (MCCB) designed for protection and measurement in demanding low-voltage electrical distribution systems. As part of the advanced ABB SACE Tmax XT series, it combines a 1600 A rated current with the intelligent Ekip Touch Measuring LSIG electronic trip unit.
This fixed circuit breaker uses an Ekip Touch Measuring LSIG solid-state release, providing long-time, short-time, instantaneous and ground-fault protection functions together with comprehensive electrical measurement capabilities. This combination enables reliable circuit protection while providing valuable operating data for monitoring and managing modern electrical distribution networks.
With a rated uninterrupted current of 1600 A, a four-pole configuration and a rated operational voltage of up to 690 V AC, the XT7S is designed for high-current industrial and commercial distribution applications. Its fixed construction, front terminals and lever operating mechanism make it suitable for integration into low-voltage switchboards and power distribution assemblies.
Moulded case circuit breakers such as the ABB XT7S protect low-voltage electrical networks against overloads and short circuits while helping isolate faults before they can damage cables, equipment or downstream systems. The Ekip Touch Measuring LSIG trip unit adds configurable ground-fault protection and comprehensive electrical measurements, making the breaker suitable for sophisticated power distribution and energy-management applications.
The Ekip Touch Measuring platform can monitor electrical parameters including phase-to-phase and phase-to-neutral voltage, active, reactive and apparent power, energy, frequency, power factor and phase sequence. Combined with the XT7S circuit breaker's high-current capability, these functions make the 1SDA101141R1 a powerful solution for industrial switchboards and critical low-voltage distribution systems.
| Series | SACE Tmax XT |
|---|---|
| Order code / Product ID | 1SDA101141R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame | XT7S |
| Rated uninterrupted current (Iu) | 1600 A |
| Number of poles | 4 |
| Trip unit | Ekip Touch Measuring LSIG |
| Release type | Electronic / solid-state |
| Protection functions | Long-time, short-time, instantaneous and ground fault (LSIG) |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Rated short-time withstand current (Icw) | 20 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 50 kA |
| Rated service short-circuit breaking capacity (Ics) at 220 V AC | 85 kA |
| Overload release adjustment range | 640–1600 A |
| Short-time short-circuit release adjustment range | 960–16000 A |
| Instantaneous short-circuit release adjustment range | 2400–24000 A |
| Protection rating | IP20 |
| Power dissipation | 94 W |
| Electrical durability | 3000 cycles |
| Installation | Fixed |
| Terminal type | Front terminals |
| Operating mechanism | Lever operating mechanism |
| Standard | IEC 60947-2 |
| Dimensions (W × H × D) | 280 × 268 × 166 mm |
| Weight | approx. 12.5 kg |
| EAN | 8056221014441 |
The ABB 1SDA101141R1 is a 1600 A four-pole moulded case circuit breaker designed to protect and monitor high-current low-voltage electrical distribution circuits in industrial, commercial and infrastructure applications.
The circuit breaker has a rated uninterrupted current of 1600 A.
The 1SDA101141R1 is fitted with an Ekip Touch Measuring LSIG electronic trip unit, providing long-time, short-time, instantaneous and ground-fault protection together with integrated electrical measurement functionality.
The XT7S S-version has a rated ultimate short-circuit breaking capacity of 50 kA at 400/415 V AC, making it suitable for demanding industrial power distribution systems.
This model is a fixed four-pole circuit breaker with front terminals and a lever operating mechanism, designed for integration into low-voltage switchboards and electrical distribution assemblies.
ABB SACE Tmax XT moulded case circuit breakers combine advanced electronic protection, electrical measurement and flexible installation capabilities to provide dependable circuit protection for modern industrial and commercial low-voltage distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.