Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA101001R1 is an XT7L 1600 A three-pole fixed moulded case circuit breaker with front terminals and an Ekip G Dip LS/I electronic trip unit for generator protection and high-performance low-voltage power distribution.
£5,142.35
The ABB 1SDA101001R1 is a high-performance SACE Tmax XT7L moulded case circuit breaker (MCCB) designed for generator protection and demanding low-voltage electrical distribution applications. Configured as an XT7L 1600 Ekip G Dip LS/I In=1600A 3p F F, it combines a 1600 A rated current with an electronic Ekip G Dip LS/I solid-state trip unit and high short-circuit breaking performance.
As part of the advanced ABB SACE Tmax XT range, this circuit breaker provides reliable protection against overload and short-circuit conditions while offering electronic protection specifically suited to generator applications. The Ekip G Dip LS/I trip unit provides long-time, short-time and instantaneous protection functions, supporting effective protection and coordination within industrial power distribution systems.
With a rated uninterrupted current of 1600 A, an adjustable overload release range of 640–1600 A and an XT7L breaking performance of 120 kA, the 1SDA101001R1 is suitable for high-current installations where dependable fault protection is essential. Its three-pole fixed configuration with front terminals and lever operating mechanism enable straightforward integration into low-voltage switchboards, generator panels and industrial distribution assemblies.
Moulded case circuit breakers such as the ABB XT7L protect electrical circuits, generators and connected equipment against damaging overload and short-circuit currents. The electronic trip unit monitors current conditions and initiates circuit interruption when configured protection thresholds are exceeded, helping maintain safe and dependable operation of the electrical installation.
The Ekip G Dip LS/I release is designed for generator applications requiring accurate electronic protection and dependable short-circuit performance. Combined with the XT7L's high breaking capacity, adjustable overload protection and robust fixed construction, the 1SDA101001R1 is well suited to generator switchboards, industrial power systems and high-current low-voltage distribution assemblies.
| Series | SACE Tmax XT7 |
|---|---|
| Order code | 1SDA101001R1 |
| Product type | Moulded case circuit breaker |
| Application | Generator protection and low-voltage power distribution |
| Rated uninterrupted current (Iu) | 1600 A |
| Overload release adjustment range | 640–1600 A |
| Trip unit | Ekip G Dip LS/I |
| Protection functions | Long-time, short-time and instantaneous |
| Rated voltage | 690 V |
| Short-circuit breaking performance | 120 kA |
| Interruption rating | L |
| Frame size | XT7 |
| Number of poles | 3 |
| Version | Fixed |
| Terminal connection | Front terminals |
| Operating mechanism | Lever |
| Release type | Solid-state electronic release |
| Standard | IEC |
| UPC / EAN | 8056221010559 |
The ABB 1SDA101001R1 is an XT7L moulded case circuit breaker designed for generator protection and high-current low-voltage electrical distribution applications.
The circuit breaker has a rated uninterrupted current of 1600 A, with an adjustable overload release range of 640–1600 A.
The 1SDA101001R1 is fitted with an Ekip G Dip LS/I electronic trip unit, providing long-time, short-time and instantaneous protection functions.
The ABB XT7L version provides a high short-circuit breaking performance of 120 kA, making it suitable for demanding generator and industrial power distribution applications.
This model is a fixed three-pole circuit breaker with front terminals and a lever operating mechanism, designed for installation within low-voltage switchboards, generator panels and industrial power distribution assemblies.
ABB SACE Tmax XT circuit breakers are engineered for dependable low-voltage power protection, combining high breaking performance, advanced electronic trip technology and flexible installation for industrial, commercial and power generation applications.