ABB 1SDA100956R1 is an XT7L 1250 A three-pole fixed moulded case circuit breaker with front terminals and an Ekip Dip LS/I solid-state electronic trip unit for high-performance power-distribution protection.
£4,201.28
The ABB 1SDA100956R1 is a high-performance SACE Tmax XT7L moulded case circuit breaker designed for demanding low-voltage power distribution applications. This fixed three-pole breaker has a rated current of 1250 A and incorporates the Ekip Dip LS/I solid-state electronic trip unit.
Part of the ABB SACE Tmax XT series, the XT7L combines high-current switching capability with electronic protection and very high short-circuit interruption performance. The XT7L configuration provides an ultimate short-circuit breaking capacity of 120 kA at 400 V AC, making it particularly suitable for installations with high prospective fault currents.
The XT7L 1250 uses a three-pole fixed configuration with front terminals and a lever operating mechanism. Its 1250 A Ekip Dip LS/I release provides adjustable overload and short-circuit protection for power-distribution circuits, transformers, generators and industrial installations.
The Ekip Dip LS/I electronic trip unit provides adjustable protection for high-current distribution circuits. Its overload and short-circuit settings allow the breaker to be coordinated with cables, transformers, generators and downstream electrical equipment while maintaining reliable fault interruption.
With its 1250 A rated current, 120 kA Icu at 400 V AC and fixed three-pole construction, the 1SDA100956R1 is particularly suited to industrial and commercial installations where high prospective short-circuit currents demand strong interruption performance.
| Series | SACE Tmax XT |
|---|---|
| Frame | XT7 |
| ABB order code | 1SDA100956R1 |
| Product type | Moulded case circuit breaker |
| Application | Power distribution protection |
| Rated current (In) | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Number of poles | 3 |
| Trip unit | Ekip Dip LS/I |
| Trip unit type | Solid-state electronic release |
| Overload current adjustment | 500–1250 A |
| Short-time short-circuit adjustment | 1250–12500 A |
| Instantaneous short-circuit adjustment | 1250–12500 A |
| Ultimate short-circuit breaking capacity at 400 V AC | 120 kA |
| Rated voltage | 690 V |
| Integrated earth-fault protection | No |
| Mounting | Fixed |
| Terminal arrangement | Front terminals |
| Main-circuit connection | Bolt connection |
| Operating mechanism | Lever |
| Degree of protection | IP20 |
| Motor operator | Optional |
| Standard | EN/IEC 60947-2 |
| EAN | 8056221010108 |
It is an ABB SACE Tmax XT7L 1250 moulded case circuit breaker with an Ekip Dip LS/I solid-state electronic trip unit, three poles, fixed mounting and front terminals.
The ABB 1SDA100956R1 has a rated current of 1250 A, with an overload adjustment range of 500–1250 A.
The breaker is equipped with an Ekip Dip LS/I solid-state electronic trip unit providing adjustable overload and short-circuit protection for power-distribution applications.
The XT7L 1250 provides an ultimate short-circuit breaking capacity of 120 kA at 400 V AC, making it suitable for electrical systems with high prospective fault currents.
This version uses a fixed three-pole mounting arrangement with front terminals and a lever operating mechanism for integration into low-voltage switchboards and distribution systems.
ABB SACE Tmax XT moulded case circuit breakers combine advanced electronic protection, robust construction and high short-circuit interruption performance for demanding industrial, commercial and infrastructure power distribution systems.