1SDA100945R1 ABB XT7H 1600 Ekip G Hi-Touch LSIG 1600 A 3-Pole MCCB

1SDA100945R1 ABB XT7H 1600 Ekip G Hi-Touch LSIG 1600 A 3-Pole MCCB

ABB 1SDA100945R1 is a 1600 A three-pole fixed XT7H moulded-case circuit breaker with an Ekip G Hi-Touch LSIG electronic trip unit and 70 kA breaking capacity at 415 V AC for advanced generator and low-voltage power distribution protection.

SKU: 1SDA100945R1MPN: 1SDA100945R1
Price
List Price £11,735.54 ex VAT
Your Price (ex VAT) Save 25%
£8,801.66 25% OFF
You save £2,933.89 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8,801.66
Trade pricing is personalised to your account

Manufacturer Lead Time

£8,801.66

Why Choose the ABB 1SDA100945R1 XT7H 1600 Circuit Breaker?

The ABB 1SDA100945R1 is a high-performance three-pole moulded-case circuit breaker (MCCB) engineered for generator protection and demanding low-voltage power distribution systems. Part of the ABB SACE Tmax XT7 range, this fixed circuit breaker combines a 1600 A rated current with an Ekip G Hi-Touch LSIG electronic trip unit for sophisticated and configurable electrical protection.

The integrated Ekip G Hi-Touch LSIG electronic trip unit provides long-time overload, selective short-time, instantaneous short-circuit and ground-fault protection functions. Its generator-focused protection capabilities make the breaker particularly suitable for alternators, generator-fed networks and critical power systems where precise protection settings and effective coordination are essential.

The XT7H version provides high short-circuit performance, with a rated ultimate breaking capacity of 70 kA at 415 V AC. The 1SDA100945R1 features a fixed three-pole construction with front terminals, providing a robust high-current solution for integration into generator switchboards, industrial distribution panels and critical electrical infrastructure.

Key Advantages

  • High-performance ABB SACE Tmax XT7H moulded-case circuit breaker.
  • 1600 A rated current for demanding high-current applications.
  • Advanced Ekip G Hi-Touch LSIG electronic trip unit.
  • Designed for sophisticated generator and power distribution protection.
  • LSIG functionality provides overload, selective short-time, instantaneous and ground-fault protection.
  • 70 kA ultimate breaking capacity at 415 V AC for systems with high prospective fault currents.
  • Adjustable protection characteristics support coordination with other protective devices.
  • Fixed three-pole construction with front terminals for switchboard integration.

Key Features

  • ABB SACE Tmax XT7H circuit breaker.
  • 1600 A rated current (In).
  • 1600 A rated uninterrupted current (Iu).
  • Three-pole configuration.
  • Ekip G Hi-Touch LSIG electronic trip unit.
  • Long-time overload (L) protection.
  • Selective short-time (S) protection.
  • Instantaneous short-circuit (I) protection.
  • Ground-fault (G) protection.
  • Long-time protection setting I1: 0.4–1 × In.
  • Short-time protection setting I2: 0.6–10 × In.
  • Instantaneous protection setting I3: 1.5–10 × In.
  • H performance level for high short-circuit breaking capability.
  • 70 kA Icu at 415 V AC.
  • Fixed construction with front terminal connections.

Advanced Generator and Power Distribution Protection

Moulded-case circuit breakers used for generator protection must respond effectively to overloads, short circuits and ground faults while accommodating the operating characteristics of generating equipment. The ABB Ekip G Hi-Touch LSIG electronic trip unit provides configurable protection functions specifically suited to generator and advanced distribution applications, supporting precise fault protection and coordination throughout the electrical network.

The XT7H performance level is designed for installations requiring substantial short-circuit breaking capability. Combined with its 1600 A current rating, advanced Ekip G Hi-Touch protection and fixed front-terminal construction, the 1SDA100945R1 provides a dependable solution for generator switchboards, industrial plants, critical infrastructure and high-current power distribution networks.

Typical Applications

  • Generator protection and generator-fed distribution systems.
  • Generator control and synchronisation switchboards.
  • Industrial low-voltage power distribution systems.
  • Main and sub-distribution switchboards.
  • High-current feeder and cable protection.
  • Installations with high prospective short-circuit currents.
  • Manufacturing and process industry electrical systems.
  • Critical infrastructure and high-availability power systems.
  • OEM switchgear and electrical panel building.

Technical Specifications

Series SACE Tmax XT
Order code 1SDA100945R1
Product type Moulded-case circuit breaker (MCCB)
Primary application Generator and power distribution protection
Frame XT7
Performance level H
Trip unit Ekip G Hi-Touch LSIG
Release type Electronic trip unit
Protection functions L, S, I and G
Rated current (In) 1600 A
Rated uninterrupted current (Iu) 1600 A
Number of poles 3
Rated ultimate breaking capacity (Icu) at 415 V AC 70 kA
Long-time protection setting (I1) 0.4–1 × In
Short-time protection setting (I2) 0.6–10 × In
Instantaneous protection setting (I3) 1.5–10 × In
Version Fixed
Terminal connection Front
EAN 8056221009997
Standard EN / IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA100945R1 used for?

The ABB 1SDA100945R1 is a 1600 A moulded-case circuit breaker designed for advanced generator protection and demanding low-voltage power distribution applications.

What trip unit is fitted to the ABB 1SDA100945R1?

The circuit breaker is fitted with an Ekip G Hi-Touch LSIG electronic trip unit, providing long-time overload, selective short-time, instantaneous short-circuit and ground-fault protection functions.

What does LSIG mean on the Ekip G Hi-Touch trip unit?

LSIG denotes long-time overload (L), selective short-time (S), instantaneous short-circuit (I) and ground-fault (G) protection functions.

What is the breaking capacity of the ABB XT7H 1600?

The XT7H 1600 provides a rated ultimate short-circuit breaking capacity of 70 kA at 415 V AC, making it suitable for installations with substantial prospective fault currents.

Is the ABB 1SDA100945R1 suitable for generator protection?

Yes. The 1SDA100945R1 incorporates the Ekip G Hi-Touch LSIG electronic trip unit and is specifically designed for advanced generator and power distribution protection applications.

Trusted ABB Circuit Protection Technology

ABB SACE Tmax XT circuit breakers combine high-performance fault interruption with advanced Ekip electronic protection technology, providing configurable protection and flexible integration for generator, industrial and critical low-voltage power distribution systems.