Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA100935R1 is an XT7H 1000 A three-pole fixed moulded case circuit breaker with an Ekip G Dip LS/I electronic trip unit for dependable protection of low-voltage generator circuits and power distribution systems.
£3,049.73
The ABB XT7H 1000 Ekip G Dip LS/I 1SDA100935R1 is a high-performance moulded case circuit breaker (MCCB) for generator protection designed for demanding low-voltage power generation and distribution applications. As part of the ABB SACE Tmax XT series, this three-pole circuit breaker combines the XT7H platform with an Ekip G Dip LS/I electronic trip unit for reliable protection of generator-fed electrical systems.
The Ekip G Dip LS/I release provides long-time, short-time and instantaneous protection functions, helping protect generators, conductors and connected equipment against overload and short-circuit conditions. Its electronic protection technology supports dependable fault protection and coordination within industrial, commercial and infrastructure generator installations.
With a rated uninterrupted current of 1000 A, a rated operational voltage of 690 V AC and a rated ultimate short-circuit breaking capacity of 70 kA at 415 V AC, the 1SDA100935R1 provides robust performance for demanding generator circuits. Its fixed three-pole construction with front bolted connections and toggle operating mechanism supports practical integration into generator switchboards and low-voltage distribution assemblies.
Generator circuits require protection capable of responding reliably to overload and short-circuit conditions while accommodating the operating characteristics of generating equipment. The ABB XT7H provides high fault interruption performance, helping protect generators, cables, switchboards and downstream equipment against damaging electrical faults.
The Ekip G Dip LS/I electronic release provides long-time, short-time and instantaneous protection functions for generator applications. Combined with the XT7H platform's high breaking capacity and 20 kA short-time withstand current, this makes the 1SDA100935R1 suitable for standby generation, distributed generation and industrial power distribution systems requiring dependable protection and coordination.
| Series | SACE Tmax XT |
|---|---|
| Product group | T-Max XT 250 Range |
| Order code | 1SDA100935R1 |
| Product type | Moulded case circuit breaker for generator and installation protection |
| Frame size | XT7 |
| Short-circuit performance level | H |
| Rated uninterrupted current (Iu) | 1000 A |
| Rated current (In) | 1000 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC | 70 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 65 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–525 V AC | 50 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 42 kA |
| Rated short-time withstand current (Icw) | 20 kA |
| Trip unit | Ekip G Dip LS/I |
| Release type | Electronic |
| Protection functions | Long-time, short-time and instantaneous |
| Integrated earth-fault protection | No |
| Number of poles | 3 |
| Installation | Fixed |
| Terminal position | Front |
| Main circuit connection | Bolted connection |
| Operating mechanism | Toggle |
| Protection rating | IP20 |
| Power loss at rated operating conditions per pole | 37 W |
| Electrical durability | 3000 cycles |
| Mechanical durability | 10000 cycles |
| Motor operator | Optional |
| Standard | IEC 60947-2 |
| EAN | 8056221009898 |
The ABB 1SDA100935R1 is an XT7H moulded case circuit breaker suitable for generator and installation protection in high-current low-voltage power systems.
The XT7H 1SDA100935R1 has a rated uninterrupted current of 1000 A and a rated operational voltage of 690 V AC.
The Ekip G Dip LS/I electronic trip unit provides long-time, short-time and instantaneous protection functions for overload and short-circuit protection.
The circuit breaker has a rated ultimate short-circuit breaking capacity of 70 kA at 415 V AC, with ratings of 65 kA at 440 V AC, 50 kA at 500–525 V AC and 42 kA at 690 V AC.