ABB 1SDA100910R1 is an XT7H 800 three-pole fixed moulded case circuit breaker rated at 800 A with front terminals, 70 kA breaking capacity at 415 V AC and an Ekip Touch Measuring LSI electronic trip unit.
£3,409.10
The ABB XT7H 800 Ekip Touch Measuring LSI In=800A 3p F F is a high-performance moulded case circuit breaker (MCCB) designed for protection, switching and advanced monitoring in demanding low-voltage electrical distribution systems. As part of the ABB SACE Tmax XT7 series, it combines an 800 A three-pole breaker with an advanced Ekip Touch Measuring electronic trip unit.
This XT7H circuit breaker features Ekip Touch Measuring LSI protection, combining long-time, short-time and instantaneous protection functions with integrated measuring capabilities. The electronic trip unit provides a modern interface for protection configuration and electrical measurements, supporting effective supervision and management of industrial power distribution systems.
With a rated current of 800 A, a three-pole configuration and the XT7H performance level, this model is suitable for high-current feeders and distribution circuits. The H performance version provides a rated ultimate short-circuit breaking capacity of 70 kA at 415 V AC, while its fixed execution with front terminals supports straightforward integration into switchboards and electrical panels.
Moulded case circuit breakers such as the ABB Tmax XT7 protect electrical installations against overload and short-circuit conditions. The Ekip Touch Measuring LSI trip unit adds advanced electronic protection and measurement capabilities, enabling electrical parameters to be monitored while providing adjustable protection for critical distribution circuits.
The XT7H platform is engineered for applications with demanding fault levels and high continuous currents. Its combination of electronic protection, integrated measurement and robust breaking performance makes this model particularly suitable for industrial switchboards, main distribution systems and high-current feeder circuits.
| Series | SACE Tmax XT7 |
|---|---|
| ABB order code | 1SDA100910R1 |
| Product type | Moulded case circuit breaker |
| Frame | XT7 |
| Performance level | XT7H |
| Rated current | 800 A |
| Number of poles | 3 |
| Trip unit | Ekip Touch Measuring LSI |
| Protection functions | Long-time, short-time and instantaneous |
| Long-time setting range | 0.4–1 × In |
| Short-time setting range | 1–10 × In |
| Ultimate breaking capacity at 415 V AC | 70 kA |
| Mounting type | Fixed |
| Terminal arrangement | Front terminals |
| Weight | 9.7 kg |
The ABB 1SDA100910R1 is an XT7H 800 three-pole fixed moulded case circuit breaker rated at 800 A and equipped with an Ekip Touch Measuring LSI electronic trip unit.
The Ekip Touch Measuring LSI trip unit provides long-time, short-time and instantaneous protection functions together with integrated electrical measuring capabilities.
The XT7H performance version provides an ultimate short-circuit breaking capacity of 70 kA at 415 V AC.
This specific circuit breaker has a three-pole configuration for use in three-phase low-voltage distribution systems.
The ABB 1SDA100910R1 is supplied as a fixed circuit breaker with front terminals, making it suitable for permanent installation within switchboards and distribution assemblies.
ABB SACE Tmax XT circuit breakers are widely used by electrical engineers, panel builders and industrial operators for dependable circuit protection, advanced power monitoring and efficient low-voltage electrical distribution.