Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA100895R1 XT7H 1000 is a 1000 A three-pole fixed moulded case circuit breaker with an Ekip Dip LSI electronic trip unit and 70 kA breaking capacity at 415 V AC for demanding transformer, generator and low-voltage electrical installation protection.
£3,331.84
The ABB 1SDA100895R1, type XT7H 1000 Ekip Dip LSI In=1000A 3p F F, is a high-performance moulded case circuit breaker (MCCB) for transformer, generator and electrical installation protection. Part of the ABB SACE Tmax XT range, this XT7H breaker combines a 1000 A rated uninterrupted current with an Ekip Dip LSI solid-state electronic trip unit for dependable protection of demanding low-voltage power distribution systems.
The Ekip Dip LSI electronic release provides long-time, short-time and instantaneous protection functions. This combination provides overload protection together with delayed and instantaneous short-circuit protection, supporting selective coordination between upstream and downstream protective devices while protecting cables, busbars, transformers and other connected equipment.
The XT7H performance level delivers an ultimate short-circuit breaking capacity of 70 kA at 415 V AC, with additional breaking capability across operating voltages up to 690 V AC. Its fixed three-pole construction, front terminals, bolted main-circuit connections and lever operating mechanism provide a robust configuration for industrial switchboards, generator systems and high-current electrical distribution assemblies.
The ABB Ekip Dip LSI electronic trip unit combines long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection in a solid-state release. The addition of short-time protection supports improved selectivity between protective devices, helping engineers coordinate fault-clearing characteristics throughout complex low-voltage distribution networks while maintaining rapid interruption of severe faults.
The XT7H version is designed for installations where substantial short-circuit performance is required. With its 1000 A rating, 70 kA breaking capability at 415 V AC and fixed front-terminal configuration, the 1SDA100895R1 is particularly suited to industrial switchboards, transformer and generator protection, main distribution panels and high-current feeder circuits.
| Series | SACE Tmax XT |
|---|---|
| Frame size | XT7 |
| Order code / MPN | 1SDA100895R1 |
| Product type | Moulded case circuit breaker |
| Application | Transformer, generator and electrical installation protection |
| Rated current (In) | 1000 A |
| Rated uninterrupted current (Iu) | 1000 A |
| Rated voltage | 690 V |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | Ekip Dip LSI |
| Release type | Solid-state electronic |
| Protection functions | L, S, I |
| Integrated earth-fault protection | No |
| Short-circuit performance level | H |
| Ultimate breaking capacity at 240 V AC | 100 kA |
| Ultimate breaking capacity at 380 V AC | 70 kA |
| Ultimate breaking capacity at 415 V AC | 70 kA |
| Ultimate breaking capacity at 440 V AC | 65 kA |
| Ultimate breaking capacity at 500 V AC | 50 kA |
| Ultimate breaking capacity at 525 V AC | 50 kA |
| Ultimate breaking capacity at 690 V AC | 42 kA |
| Mounting type | Fixed |
| Terminal position | Front |
| Main circuit connection | Bolted connection |
| Operating mechanism | Lever |
| Complete device with protection unit | Yes |
| Integrated motor operator | No |
| Motor operator | Optional |
| Degree of protection | IP20 |
| Power loss | 37 W |
| Dimensions (W × H × D) | 210 × 268 × 166 mm |
| Net weight | 9.7 kg |
| Standard | IEC 60947 |
| EAN / GTIN | 8056221009492 |
The ABB 1SDA100895R1 is a 1000 A moulded case circuit breaker designed for transformer, generator and electrical installation protection in demanding low-voltage power distribution systems.
The breaker is fitted with an Ekip Dip LSI solid-state electronic trip unit, providing long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.
The ABB 1SDA100895R1 has a rated uninterrupted current of 1000 A and is designed for high-current low-voltage distribution applications.
The XT7H provides a short-circuit breaking capacity of 70 kA at 415 V AC. Its breaking capability is 100 kA at 240 V AC, 65 kA at 440 V AC, 50 kA at 500–525 V AC and 42 kA at 690 V AC.
This model is a fixed, three-pole circuit breaker with front terminals, bolted main-circuit connections and a lever operating mechanism for integration into low-voltage switchboards and power distribution assemblies.
ABB SACE Tmax XT circuit breakers combine configurable electronic protection with high short-circuit performance, providing panel builders and electrical engineers with dependable protection for transformer, generator and demanding industrial low-voltage distribution applications.