1SDA100870R1 ABB XT7S 800 Ekip G Dip LS/I 800A 3-Pole Circuit Breaker

1SDA100870R1 ABB XT7S 800 Ekip G Dip LS/I 800A 3-Pole Circuit Breaker

ABB 1SDA100870R1 XT7S 800 is an 800 A three-pole fixed moulded case circuit breaker with an Ekip G Dip LS/I electronic trip unit designed for generator protection in low-voltage power systems.

SKU: 1SDA100870R1MPN: 1SDA100870R1
Price
List Price £2,593.91 ex VAT
Your Price (ex VAT) Save 25%
£1,945.43 25% OFF
You save £648.48 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,945.43
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,945.43

Why Choose the ABB 1SDA100870R1 XT7S 800 Circuit Breaker?

The ABB 1SDA100870R1, type XT7S 800 Ekip G Dip LS/I In=800A 3p F F, is a high-performance moulded case circuit breaker (MCCB) for generator protection designed for demanding low-voltage electrical systems. As part of the ABB SACE Tmax XT range, it combines an 800 A rated current with an Ekip G Dip LS/I electronic trip unit specifically designed to provide dependable protection for generators and associated distribution circuits.

The Ekip G Dip LS/I solid-state release provides long-time, short-time and instantaneous protection functions, enabling the breaker to respond accurately to overload and short-circuit conditions. Its adjustable settings allow protection characteristics to be coordinated with generator operating requirements, while the complete fixed configuration simplifies integration into switchboards and generator control systems.

With a rated uninterrupted current of 800 A, a rated voltage of 690 V AC and an ultimate short-circuit breaking capacity of 50 kA at 415 V AC, the XT7S 800 provides robust protection for high-power installations. The three-pole fixed design incorporates front terminals and a lever operating mechanism for straightforward installation and operation.

Key Advantages

  • High-performance ABB SACE Tmax XT circuit breaker designed for generator protection.
  • 800 A rated uninterrupted current for demanding power generation applications.
  • Ekip G Dip LS/I electronic trip unit with generator-oriented protection characteristics.
  • Adjustable long-time, short-time and instantaneous protection functions.
  • Three-pole fixed configuration with front terminals for switchboard integration.
  • 50 kA ultimate short-circuit breaking capacity at 415 V AC.

Key Features

  • ABB SACE Tmax XT7S series.
  • 800 A rated current.
  • Ekip G Dip LS/I solid-state electronic release.
  • Dedicated design for generator protection.
  • LS/I protection functions for overload and short-circuit protection.
  • 320–800 A adjustable overload protection range.
  • 480–8000 A adjustable short-time short-circuit protection range.
  • 800–8000 A adjustable instantaneous short-circuit protection range.
  • Three-pole fixed-mounted design with front terminals.
  • 690 V AC rated voltage for industrial power systems.

Reliable Generator Protection for Industrial Power Systems

Generator circuits have protection requirements that differ from conventional utility-fed distribution systems because available fault current and operating characteristics are determined by the generator itself. The ABB Ekip G Dip LS/I electronic release is designed to support these applications with adjustable overload, short-time and instantaneous protection functions that allow the circuit breaker to be coordinated with generator characteristics.

The SACE Tmax XT platform combines high breaking performance with flexible electronic protection and a comprehensive accessory system. This makes the XT7S suitable for generator switchboards, standby power systems, industrial power generation installations and other applications requiring reliable protection and isolation of high-current electrical circuits.

Typical Applications

  • Industrial generator protection systems.
  • Standby and emergency power generation.
  • Generator control and distribution switchboards.
  • Commercial and industrial backup power systems.
  • Combined heat and power installations.
  • Infrastructure and critical power systems.
  • Industrial low-voltage electrical distribution.

Technical Specifications

Series SACE Tmax XT
Frame size XT7
Order code / MPN 1SDA100870R1
Product type Moulded case circuit breaker
Application Generator protection
Rated current (In) 800 A
Rated uninterrupted current (Iu) 800 A
Rated voltage 690 V AC
Number of poles 3
Trip unit Ekip G Dip LS/I
Protection functions L, S, I
Overload release adjustment range 320–800 A
Short-time short-circuit release adjustment range 480–8000 A
Instantaneous short-circuit release adjustment range 800–8000 A
Ultimate breaking capacity (Icu) at 415 V AC 50 kA
Short-circuit performance level S
Mounting type Fixed
Terminal connection Front terminals
Main circuit connection Bolted connection
Operating mechanism Lever
Motor operator Optional
Integrated earth-fault protection No
Protection rating IP20
Standard IEC / EN 60947-2
Power loss 24 W
EAN 8056221009249

Frequently Asked Questions

What is the ABB 1SDA100870R1 used for?

The ABB 1SDA100870R1 is an 800 A moulded case circuit breaker designed for generator protection in industrial, commercial and standby power systems.

What trip unit is fitted to the ABB 1SDA100870R1?

The circuit breaker is fitted with an Ekip G Dip LS/I electronic trip unit, providing long-time, short-time and instantaneous protection functions suitable for generator applications.

What is the rated current of this circuit breaker?

The XT7S 800 has a rated uninterrupted current of 800 A, with the overload release adjustable from 320–800 A.

What breaking capacity does the XT7S 800 provide?

The XT7S S-performance version provides an ultimate short-circuit breaking capacity of 50 kA at 415 V AC.

How is the ABB 1SDA100870R1 installed?

This model is a fixed, three-pole circuit breaker with front terminals and a lever operating mechanism, making it suitable for installation in generator switchboards and industrial electrical distribution assemblies.

Trusted by Power Generation Professionals Worldwide

ABB SACE Tmax XT circuit breakers with Ekip G protection are designed for dependable generator and electrical system protection, providing industrial engineers and panel builders with flexible electronic protection for demanding low-voltage power applications.