ABB 1SDA100767R1 is an 800 A three-pole SACE Tmax XT6H moulded case circuit breaker with an Ekip Dip LSIG electronic trip unit, 70 kA breaking capacity at 415 V AC, fixed mounting and front terminals for comprehensive low-voltage power distribution protection.
£2,676.65
The ABB 1SDA100767R1 is a high-performance three-pole moulded case circuit breaker (MCCB) designed for comprehensive protection and isolation in demanding industrial and commercial low-voltage power distribution systems. Part of the ABB SACE Tmax XT series, this XT6H 800 model combines fixed installation, front terminals and an Ekip Dip LSIG solid-state electronic trip unit.
Rated at 800 A, the XT6H is engineered for high-current distribution applications requiring advanced electronic protection. Its Ekip Dip LSIG trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection, helping safeguard cables, switchboards and connected electrical equipment against a broad range of overcurrent and earth-fault conditions.
The XT6H high-interruption configuration provides a rated ultimate short-circuit breaking capacity of 70 kA at 415 V AC. Its three-pole construction, fixed mounting and front-terminal configuration make the 1SDA100767R1 particularly suitable for high-current three-phase distribution systems where substantial fault interruption capability and comprehensive LSIG protection are required.
Moulded case circuit breakers such as the ABB XT6H protect electrical distribution systems against abnormal current conditions while also providing circuit switching and isolation. The Ekip Dip electronic release monitors current and operates the breaker according to configured protection settings, helping protect conductors, switchgear and connected electrical equipment.
The LSIG protection configuration makes the 1SDA100767R1 particularly suitable for distribution systems where comprehensive protection and selective coordination are important. Long-time protection responds to sustained overloads, short-time and instantaneous functions address short-circuit currents, while the ground-fault function provides additional protection against earth-fault conditions. Combined with the XT6H's 70 kA breaking capacity at 415 V AC, these functions provide robust protection for demanding electrical installations.
| Series | SACE Tmax XT |
|---|---|
| Frame size | XT6 |
| Order code / SKU | 1SDA100767R1 |
| Product group | T-Max XT 250 Range |
| Product type | Moulded case circuit breaker |
| Rated current (In) | 800 A |
| Rated uninterrupted current (Iu) | 800 A |
| Number of poles | 3 |
| Current type | AC |
| Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC | 70 kA |
| Trip unit | Ekip Dip LSIG |
| Release type | Solid-state electronic |
| Protection functions | LSIG (long-time, short-time, instantaneous and ground fault) |
| Long-time protection adjustment range | 320–800 A |
| Short-time protection adjustment | 1–10 × In |
| Instantaneous protection adjustment | 1–10 × In |
| Ground-fault protection adjustment | 0.2–1.0 × In |
| Interruption performance level | H |
| Mounting version | Fixed |
| Terminal connection | Front |
| Product net weight | 11 kg |
| Standards | IEC |
| EAN / GTIN | 8056221008211 |
The ABB 1SDA100767R1 is an 800 A three-pole moulded case circuit breaker designed to provide overload, short-circuit and ground-fault protection in demanding industrial and commercial low-voltage power distribution systems.
The breaker is fitted with an Ekip Dip LSIG solid-state electronic trip unit, providing long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection.
The XT6H 800 has a rated ultimate short-circuit breaking capacity of 70 kA at 415 V AC, making it suitable for installations with high prospective fault currents.
LSIG refers to long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection, providing comprehensive electronic protection for demanding electrical distribution systems.
This model is a fixed three-pole circuit breaker with front terminals, designed for integration into low-voltage switchboards and electrical distribution panels.
ABB SACE Tmax XT moulded case circuit breakers are engineered for reliable low-voltage power distribution, combining high interruption performance, advanced electronic protection and practical installation options for demanding industrial and commercial electrical systems.