ABB 1SDA100759R1 is a 1000 A four-pole fixed SACE Tmax XT6S moulded-case circuit breaker with front terminals and an Ekip Dip LSIG electronic trip unit providing long-time, short-time, instantaneous and ground-fault protection.
£2,956.87
The ABB 1SDA100759R1 is a SACE Tmax XT6S 1000 moulded-case circuit breaker equipped with an Ekip Dip LSIG electronic trip unit. Designed in a fixed four-pole configuration with front terminals, it has a 1000 A rated current and provides comprehensive electronic protection for demanding low-voltage power-distribution systems.
The Ekip Dip LSIG release combines long-time, short-time, instantaneous and ground-fault protection. This comprehensive protection package allows the breaker to respond to sustained overloads, selective short-circuit conditions, severe high-current faults and ground faults, supporting effective coordination across industrial and commercial electrical installations.
The XT6S 1000 Ekip Dip LSIG In=1000 4p F F combines ABB's XT6 frame with the S performance level, corresponding to a 50 kA breaking-capacity class. Its four-pole architecture, fixed execution and front-terminal arrangement make it suitable for high-current three-phase, four-wire distribution systems requiring advanced electronic circuit protection.
LSIG electronic protection provides multiple levels of circuit protection within a single trip unit. Long-time protection responds to sustained overloads, short-time protection enables selective coordination during fault conditions, instantaneous protection rapidly clears severe short circuits, and ground-fault protection responds to current flowing through unintended paths to earth.
This combination makes the ABB 1SDA100759R1 particularly suitable for important high-current feeders where protection coordination and ground-fault detection are required. The Ekip Dip platform provides configurable electronic protection while retaining straightforward local settings, helping engineers tailor the circuit breaker to the requirements of the electrical installation.
| Series | SACE Tmax XT |
|---|---|
| ABB order code | 1SDA100759R1 |
| Product type | Moulded-case circuit breaker (MCCB) |
| Frame size | XT6 |
| Performance level | XT6S |
| Rated current (In) | 1000 A |
| Number of poles | 4 |
| Trip unit | Ekip Dip LSIG |
| Trip-unit technology | Electronic |
| Protection functions | LSIG |
| Long-time protection | L |
| Short-time protection | S |
| Instantaneous protection | I |
| Ground-fault protection | G |
| Breaking-capacity class | 50 kA |
| Installation | Fixed |
| Terminal configuration | Front terminals |
| 1000 A terminal requirement | EF, ES, R or FC CuAl terminals |
| Product net weight | 12 kg |
| ABB product group | T-Max XT 250 Range |
The ABB 1SDA100759R1 is a 1000 A four-pole SACE Tmax XT6S moulded-case circuit breaker equipped with an Ekip Dip LSIG electronic trip unit in a fixed, front-terminal configuration.
The Ekip Dip LSIG provides long-time (L), short-time (S), instantaneous (I) and ground-fault (G) protection for comprehensive overload and fault protection.
The ABB 1SDA100759R1 has a rated current of 1000 A and uses the ABB Tmax XT6 frame.
XT6 identifies the ABB Tmax XT frame size, while the S performance level identifies this configuration's 50 kA breaking-capacity class.
Yes. ABB specifies that the 1000 A XT6 configuration is to be ordered and used with suitable EF, ES, R or FC CuAl terminals.
ABB SACE Tmax XT moulded-case circuit breakers and Ekip electronic trip units combine high-current switching capability with configurable protection functions, supporting reliable and coordinated low-voltage power distribution across industrial, commercial and infrastructure installations.