ABB 1SDA100742R1 is a 1000 A three-pole fixed SACE Tmax XT6S moulded-case circuit breaker with front terminals and an Ekip Dip LS/I solid-state electronic trip unit providing adjustable overload and short-circuit protection.
£2,314.28
The ABB 1SDA100742R1 is a SACE Tmax XT6S 1000 moulded-case circuit breaker equipped with an Ekip Dip LS/I solid-state electronic trip unit. Designed as a fixed three-pole breaker with front terminals, it has a 1000 A rated current and provides configurable electronic overload and short-circuit protection for demanding low-voltage AC distribution systems.
As part of the ABB SACE Tmax XT family, the XT6S combines high-current switching performance with ABB's Ekip Dip electronic protection technology. The LS/I release provides adjustable long-time overload and short-circuit protection, allowing the breaker settings to be coordinated with conductors, loads and other protective devices throughout an electrical installation.
The XT6S 1000 Ekip Dip LS/I In=1000 3p F F provides an overload adjustment range of 0.4–1 × In, corresponding to 400–1000 A, and short-circuit adjustment from 1–10 × In, corresponding to 1000–10000 A. The XT6S performance level provides a 50 kA breaking-capacity class, making this breaker suitable for high-current industrial, commercial and infrastructure distribution applications.
Electronic trip technology allows protection thresholds to be matched more closely to the requirements of the protected circuit than fixed protection characteristics. The ABB Ekip Dip LS/I monitors circuit current electronically and provides adjustable overload and short-circuit protection, helping engineers coordinate the breaker with conductors, equipment and other protective devices.
With its 1000 A rating, three-pole fixed construction and 50 kA XT6S performance class, the 1SDA100742R1 is designed for high-current distribution circuits where robust fault interruption and configurable protection are required. Front terminals support practical integration into compatible low-voltage switchboards and distribution assemblies.
| Series | SACE Tmax XT |
|---|---|
| ABB order code | 1SDA100742R1 |
| Product type | Moulded-case circuit breaker (MCCB) |
| Frame size | XT6 |
| Performance level | XT6S |
| Rated current (In) | 1000 A |
| Rated operational voltage | Up to 690 V AC |
| Number of poles | 3 |
| Trip unit | Ekip Dip LS/I |
| Trip-unit technology | Solid-state electronic |
| Protection functions | LS/I |
| Long-time overload adjustment | 0.4–1 × In |
| Long-time current adjustment | 400–1000 A |
| Short-circuit adjustment | 1–10 × In |
| Short-circuit current adjustment | 1000–10000 A |
| Breaking-capacity class | 50 kA |
| Current type | AC |
| Installation | Fixed |
| Terminal configuration | Front terminals |
| Standard | IEC |
| EAN / GTIN | 8056221003674 |
| ABB product group | T-Max XT 250 Range |
The ABB 1SDA100742R1 is a 1000 A three-pole SACE Tmax XT6S moulded-case circuit breaker with an Ekip Dip LS/I solid-state electronic trip unit, fixed installation and front terminals.
The Ekip Dip LS/I provides adjustable long-time overload and short-circuit protection, allowing the breaker characteristics to be coordinated with the protected circuit and other protective devices.
The long-time overload setting is adjustable from 0.4–1 × In. With a rated current of 1000 A, this corresponds to an adjustment range of 400–1000 A.
The short-circuit protection is adjustable from 1–10 × In, corresponding to 1000–10000 A for this 1000 A circuit breaker.
XT6 identifies the ABB Tmax XT frame size, while the S performance level identifies the 50 kA breaking-capacity class of this configuration.
ABB SACE Tmax XT moulded-case circuit breakers and Ekip electronic trip units combine high-current switching performance with configurable circuit protection, supporting reliable industrial, commercial and infrastructure low-voltage distribution systems.
We use cookies