ABB 1SDA100740R1 is an 800 A three-pole SACE Tmax XT6S moulded case circuit breaker with a TMA thermomagnetic trip unit, fixed mounting, front terminals and adjustable overload and short-circuit protection.
£1,763.53
The ABB 1SDA100740R1 is a high-performance three-pole moulded case circuit breaker (MCCB) designed for reliable overload and short-circuit protection in industrial and commercial low-voltage power distribution systems. Part of the established ABB SACE Tmax XT series, this XT6S 800 model combines fixed mounting, front terminals and a TMA thermomagnetic trip unit in a robust circuit protection solution.
Rated at 800 A, the XT6S is engineered for demanding high-current distribution applications. Its TMA thermomagnetic release provides thermal overload protection together with adjustable instantaneous magnetic short-circuit protection, helping safeguard cables, switchboards and connected electrical equipment against damaging overcurrent conditions.
The XT6S performance level provides a rated ultimate short-circuit breaking capacity of 50 kA at 415 V AC. The instantaneous short-circuit release is adjustable from 4000–8000 A, while the thermal overload setting range extends from 560–800 A, allowing the breaker protection to be matched to the requirements of the installation.
Moulded case circuit breakers such as the ABB XT6S protect electrical distribution systems against overloads and short circuits while also providing circuit switching and isolation. The TMA thermomagnetic release combines a thermal element for sustained overload conditions with a magnetic element that rapidly operates the breaker when severe short-circuit currents occur.
The adjustable protection ranges of the 1SDA100740R1 provide flexibility when coordinating the breaker with cables and downstream equipment. Its thermal setting can be adjusted between 560–800 A, while the instantaneous magnetic release can be configured between 4000–8000 A for high-current short-circuit protection.
| Series | SACE Tmax XT |
|---|---|
| Frame size | XT6 |
| Order code / SKU | 1SDA100740R1 |
| Product group | T-Max XT 250 Range |
| Product type | Moulded case circuit breaker |
| Rated current (In) | 800 A |
| Rated uninterrupted current (Iu) | 800 A |
| Number of poles | 3 |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC | 50 kA |
| Rated short-time withstand current (Icw) | 10 kA |
| Trip unit | TMA |
| Release type | Thermomagnetic |
| Thermal overload setting range | 560–800 A |
| Thermal overload adjustment | 0.7–1 × In |
| Instantaneous short-circuit setting range | 4000–8000 A |
| Instantaneous short-circuit adjustment | 5–10 × In |
| Interruption performance level | S |
| Mounting version | Fixed |
| Terminal connection | Front |
| Protection rating | IP20 |
| Electrical durability | 5000 cycles |
| Motor drive | Optional |
| DIN rail mounting | No |
| Power loss | 54.2 W |
| Standards | IEC 60947-2 |
| EAN | 8056221003650 |
The ABB 1SDA100740R1 is an 800 A three-pole moulded case circuit breaker designed to provide overload and short-circuit protection in industrial and commercial low-voltage power distribution systems.
The breaker is fitted with a TMA thermomagnetic trip unit, combining adjustable thermal overload protection with adjustable instantaneous magnetic short-circuit protection.
The XT6S 800 has a rated ultimate short-circuit breaking capacity of 50 kA at 415 V AC.
The thermal overload release can be adjusted from 560–800 A, while the instantaneous short-circuit release is adjustable from 4000–8000 A.
This model is a fixed three-pole circuit breaker with front terminals, designed for integration into low-voltage switchboards and electrical distribution panels.
ABB SACE Tmax XT moulded case circuit breakers are engineered for reliable low-voltage power distribution, combining robust interruption performance, dependable thermomagnetic protection and practical installation options for demanding industrial and commercial electrical systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.