Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA100552R1 SACE Tmax XT5N 400 A frame-size fixed four-pole breaking part with front terminals for assembly with a compatible ABB XT5 trip unit.
£498.92
The ABB 1SDA100552R1 is a 400 A frame-size breaking part for ABB SACE Tmax XT5 moulded case circuit breaker assemblies. Designed as part of the ABB Tmax XT5N range, it features a fixed four-pole configuration with front terminals for integration into industrial and commercial low-voltage distribution systems.
Unlike a complete moulded case circuit breaker, the ABB 1SDA100552R1 is supplied as the breaker body or breaking part and does not include a protection trip unit. A compatible ABB XT5 trip unit must be selected separately according to the required rated current, protection functions and system-coordination requirements.
The four-pole construction allows all three phase conductors and the neutral conductor to be switched together. With its normal XT5N interruption-performance level, robust operating mechanism and compact format, this breaking part provides a flexible foundation for building a customised circuit protection solution.
The ABB 1SDA100552R1 provides the switching and interruption mechanism required for an XT5N circuit breaker assembly. Its modular design allows engineers and panel builders to pair the breaking part with a compatible trip unit selected for the electrical characteristics of the installation.
Available trip-unit options within the wider XT5 platform can provide thermal-magnetic or electronic protection functions. Correct selection depends on factors such as the load current, conductor capacity, prospective fault current and required coordination with upstream and downstream protective devices.
The four-pole configuration enables the three phases and neutral conductor to be switched as part of the same assembly. This format is commonly selected for three-phase, four-wire distribution systems where neutral isolation is required for operational, maintenance or installation-design purposes.
Its fixed mounting arrangement is intended for permanent installation inside a suitable switchboard or distribution enclosure. Front-facing terminals support practical cable or busbar connection while maintaining access during assembly and servicing.
Tick the specs you need, then view products that match.
| Mounting Type | Fixed | |
|---|---|---|
| Application | Power distribution | |
| Current | 400 A | |
| Phase | Three Phase | |
| Poles | 4-pole | |
| Device Type | MCCB | |
| Breaking Capacity | 36 kA | |
| Manufacturer | ABB | |
| Series | SACE Tmax XT | |
| Extended product type | XT5N 400 BREAKING PART 4p F F | |
| Product ID | 1SDA100552R1 | |
| EAN / GTIN | 8056221006286 | |
| Product type | Moulded case circuit breaker breaking part | |
| Frame size | XT5 | |
| Maximum frame current | 400 A | |
| Number of poles | 4 | |
| Interruption-performance level | N | |
| Typical breaking capacity at 415 V AC | 36 kA | |
| Rated operational voltage | Up to 690 V AC | |
| Rated insulation voltage | 1000 V | |
| Rated impulse withstand voltage | 8 kV | |
| Mounting type | Fixed | |
| Terminal type | Front terminals | |
| Trip unit included | No | |
| Compatible trip-unit platform | ABB XT5 | |
| Product width | 186 mm | |
| Product height | 205 mm | |
| Product depth | 103.5 mm | |
| Net weight | Approx. 4.55 kg | |
| Customs tariff code | 85389099 | |
| HS Code | 85389099 | |
| Country of Manufacture | Italy |
The ABB 1SDA100552R1 is an XT5N 400 fixed four-pole breaking part with front terminals, designed for use as the main body of a compatible ABB Tmax XT5 circuit breaker assembly.
No. It is supplied as a breaking part and requires a compatible ABB XT5 trip unit to provide overload and short-circuit protection.
The breaking part is based on the ABB XT5 400 A frame. The actual protection rating and settings depend on the compatible trip unit installed.
The ABB 1SDA100552R1 has four poles, allowing the phase and neutral conductors of a three-phase, four-wire system to be switched together.
This model has a fixed mounting configuration with front terminals for installation within a suitable low-voltage switchboard or distribution panel.
ABB SACE Tmax XT components provide panel builders and electrical engineers with a modular platform for configuring dependable low-voltage circuit protection systems around specific installation requirements.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.