1SDA100526R1 ABB XT5H 400 Ekip Dip LS/I 250A 4-Pole Moulded Case Circuit Breaker

1SDA100526R1 ABB XT5H 400 Ekip Dip LS/I 250A 4-Pole Moulded Case Circuit Breaker

ABB 1SDA100526R1 XT5H 400 Ekip Dip LS/I is a 250 A four-pole fixed moulded-case circuit breaker with front terminals, electronic long-time and short-time or instantaneous protection and a 70 kA ultimate breaking capacity at 380–415 V AC for demanding low-voltage distribution systems.

SKU: 1SDA100526R1MPN: 1SDA100526R1
Price
List Price £1,757.00 ex VAT
Your Price (ex VAT) Save 25%
£1,317.75 25% OFF
You save £439.25 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,317.75
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,317.75

Why Choose the ABB XT5H 400 Ekip Dip LS/I 1SDA100526R1 Circuit Breaker?

The ABB 1SDA100526R1 is a high-performance SACE Tmax XT5H moulded-case circuit breaker (MCCB) designed for dependable protection and switching in demanding low-voltage AC power distribution systems. This fixed four-pole circuit breaker features front terminals and an Ekip Dip LS/I solid-state electronic trip unit, providing configurable overload and short-circuit protection.

As part of the ABB SACE Tmax XT series, the XT5H 400 combines compact construction with high short-circuit interruption capability and electronic protection. The Ekip Dip LS/I release provides Long-time (L) overload protection together with selectable Short-time (S) or Instantaneous (I) short-circuit protection, enabling the breaker to be coordinated with feeders, cables and downstream protective devices.

The 1SDA100526R1 has a 250 A rated current on the XT5 400 A frame and a four-pole configuration. Its XT5H interruption class provides an ultimate short-circuit breaking capacity of 70 kA at 380–415 V AC, with additional high breaking performance across its operating-voltage range, making it suitable for transformer, generator and installation protection.

Key Advantages

  • High-performance ABB SACE Tmax XT5H moulded-case circuit breaker.
  • 250 A rated current on the XT5 400 A frame.
  • Ekip Dip LS/I solid-state electronic trip unit for configurable protection.
  • Long-time overload protection with selectable short-time or instantaneous short-circuit protection.
  • Four-pole configuration for three-phase distribution systems requiring four-pole switching.
  • 70 kA ultimate short-circuit breaking capacity at 380–415 V AC.
  • Fixed construction with front terminals for straightforward switchboard integration.

Key Features

  • ABB SACE Tmax XT5H 400 moulded-case circuit breaker.
  • 250 A rated current (In).
  • 400 A rated uninterrupted current (Iu).
  • Ekip Dip LS/I electronic release.
  • Long-time (L) overload protection.
  • Short-time / Instantaneous (S/I) short-circuit protection.
  • Four-pole circuit-breaker configuration.
  • Fixed mounting design.
  • Front terminals for main-circuit connections.
  • H short-circuit performance level.
  • Rated operational voltage up to 690 V AC.
  • Rated insulation voltage of 1000 V.
  • Rated impulse withstand voltage of 8 kV.
  • Designed to IEC 60947-2 requirements.

Advanced Electronic Protection for High-Fault-Level Distribution

The ABB Ekip Dip LS/I release provides electronic protection for applications requiring dependable overload and short-circuit response. Long-time protection monitors sustained overcurrent conditions, while the S/I functionality allows short-circuit protection to be configured for Short-time or Instantaneous operation according to the coordination requirements of the electrical installation.

Combined with the XT5H platform's high interruption capability, including an Icu of 70 kA at 380–415 V AC, the 1SDA100526R1 is well suited to distribution points with substantial prospective fault currents. Its four-pole design, fixed construction and front terminals make it a practical solution for transformer, generator and general power-distribution switchboards.

Typical Applications

  • Industrial low-voltage power distribution systems.
  • Main and sub-distribution switchboards.
  • Transformer protection and transformer-fed distribution.
  • Generator protection and generator distribution systems.
  • High-fault-level four-pole feeder protection.
  • Manufacturing and process installations.
  • Commercial and infrastructure electrical distribution.

Technical Specifications

Series SACE Tmax XT
Frame size XT5
Order code 1SDA100526R1
Alternate catalogue number XT5HE425AEFF000XXX
Product type Moulded-case circuit breaker (MCCB)
Rated current (In) 250 A
Rated uninterrupted current (Iu) 400 A
Number of poles 4
Trip unit Ekip Dip LS/I
Release type Electronic (EL)
Protection functions Long-time (L) and Short-time / Instantaneous (S/I)
Ultimate short-circuit breaking capacity (Icu) at 220–240 V AC 100 kA
Ultimate short-circuit breaking capacity (Icu) at 380–415 V AC 70 kA
Ultimate short-circuit breaking capacity (Icu) at 440 V AC 65 kA
Ultimate short-circuit breaking capacity (Icu) at 500–525 V AC 50 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 40 kA
Rated short-time withstand current (Icw) 5 kA
Rated operational voltage up to 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Short-circuit performance level H
Current type AC
Mounting type Fixed
Terminal position Front
Electrical durability 7000 cycles
Mechanical durability 20000 cycles
Power loss 8 W
Standard IEC 60947-2
Net weight 6.4 kg
GTIN / UPC 8056221006026

Frequently Asked Questions

What is the ABB 1SDA100526R1 used for?

The ABB 1SDA100526R1 is a 250 A four-pole moulded-case circuit breaker designed for power distribution, transformer, generator and installation protection where configurable electronic overload and short-circuit protection is required.

What is the rated current of the ABB XT5H 400 Ekip Dip LS/I?

The 1SDA100526R1 has a rated current of 250 A and a rated uninterrupted current of 400 A.

What does Ekip Dip LS/I mean?

The Ekip Dip LS/I electronic release provides Long-time (L) overload protection together with Short-time or Instantaneous (S/I) short-circuit protection, allowing the breaker to be configured according to the protection and selectivity requirements of the installation.

How many poles does the ABB 1SDA100526R1 have?

The 1SDA100526R1 is a four-pole circuit breaker supplied in a fixed configuration with front terminals.

What is the breaking capacity of the ABB XT5H 400?

This XT5H configuration provides an ultimate short-circuit breaking capacity (Icu) of 70 kA at 380–415 V AC, 65 kA at 440 V AC, 50 kA at 500–525 V AC and 40 kA at 690 V AC.

Trusted ABB Circuit Protection Technology

ABB SACE Tmax XT moulded-case circuit breakers combine dependable switching, configurable electronic protection and high short-circuit interruption performance for demanding transformer, generator, industrial and commercial low-voltage distribution applications.