Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA100491R1 SACE Tmax XT5H 630 A three-pole fixed moulded case circuit breaker with front terminals and an Ekip Dip LS/I electronic trip unit.
£1,614.26
The ABB 1SDA100491R1 is a high-performance 630 A moulded case circuit breaker (MCCB) designed to protect industrial and commercial low-voltage power distribution systems against overloads and short circuits. Part of the ABB SACE Tmax XT5H range, this three-pole breaker combines high fault-interruption capability with accurate electronic protection in a compact, fixed configuration.
The circuit breaker is fitted with an Ekip Dip LS/I electronic trip unit, providing adjustable long-time overload protection alongside short-circuit and instantaneous protection. This configuration supports dependable fault isolation and effective coordination with other protective devices throughout the electrical installation.
With a rated uninterrupted current of 630 A, an operational voltage of up to 690 V AC and a rated ultimate breaking capacity of 70 kA at 415 V AC, the ABB 1SDA100491R1 is suitable for demanding switchboards, motor control centres, distribution panels and OEM electrical systems.
The ABB XT5H 630 monitors current flowing through the connected circuit and disconnects the supply when hazardous overload or short-circuit conditions are detected. This helps prevent damage to cables, switchgear, transformers and connected equipment while improving the overall safety of the installation.
Its Ekip Dip LS/I trip unit enables protection parameters to be matched to the electrical system and connected load. Adjustable long-time and short-circuit protection can help engineers achieve effective coordination while limiting unnecessary disruption to unaffected parts of the installation.
The XT5H performance level is intended for installations with elevated prospective fault currents. Its ultimate breaking capacity of 70 kA at 415 V AC makes the ABB 1SDA100491R1 suitable for use near transformers, main distribution points and industrial supplies where robust interruption performance is essential.
Tick the specs you need, then view products that match.
| Mounting Type | Fixed | |
|---|---|---|
| Application | Power distribution | |
| Trip Unit | LS/I | |
| Current | 630 A | |
| Phase | Three Phase | |
| Poles | 3-pole | |
| Device Type | MCCB | |
| Breaking Capacity | 100 kA | |
| Manufacturer | ABB | |
| Series | SACE Tmax XT | |
| Model | XT5H 630 Ekip Dip LS/I In=630 3p F F | |
| Product ID | 1SDA100491R1 | |
| EAN | 8056221005685 | |
| Product type | Moulded case circuit breaker | |
| Frame size | XT5 | |
| Rated uninterrupted current | 630 A | |
| Number of poles | 3 | |
| Trip unit | Ekip Dip LS/I electronic release | |
| Short-circuit performance level | H | |
| Rated operational voltage | Up to 690 V AC | |
| Rated insulation voltage | 1000 V | |
| Rated impulse withstand voltage | 8 kV | |
| Ultimate breaking capacity at 220–240 V AC | 100 kA | |
| Ultimate breaking capacity at 380–415 V AC | 70 kA | |
| Ultimate breaking capacity at 440 V AC | 65 kA | |
| Ultimate breaking capacity at 500–525 V AC | 50 kA | |
| Ultimate breaking capacity at 690 V AC | 40 kA | |
| Service breaking capacity at 415 V AC | 70 kA | |
| Service breaking capacity at 690 V AC | 30 kA | |
| Rated short-time withstand current | 6 kA | |
| Mounting type | Fixed | |
| Terminal type | Front terminals | |
| Current type | AC | |
| Protection rating | IP20 | |
| Power loss | 45 W | |
| Electrical durability | 5,000 operating cycles | |
| Mechanical durability | 20,000 operating cycles | |
| Standards | IEC 60947 | |
| Dimensions (H × W × D) | 205 × 140 × 103.5 mm | |
| Weight | Approx. 4.82 kg | |
| HS Code | 85362090 | |
| Country of Manufacture | Italy |
The ABB 1SDA100491R1 protects industrial and commercial low-voltage circuits against overloads and short circuits.
The breaker has a rated uninterrupted current of 630 A.
It is fitted with an Ekip Dip LS/I electronic trip unit, providing adjustable long-time overload and short-circuit protection.
The ABB XT5H 630 has an ultimate short-circuit breaking capacity of 70 kA at 415 V AC.
This model is a fixed three-pole circuit breaker with front terminals for installation within low-voltage switchboards and distribution panels.
ABB SACE Tmax XT moulded case circuit breakers are widely specified by electrical engineers and panel builders for dependable protection, high interruption performance and long-term reliability in demanding power distribution systems.
We use cookies