ABB 1SDA100441R1 is a 320 A three-pole fixed SACE Tmax XT5S 400 moulded case circuit breaker with front terminals and an Ekip M Dip LIU electronic release providing overload, short-circuit, phase-loss and phase-imbalance protection for motor applications.
£1,409.42
The ABB XT5S 400 Ekip M Dip LIU In=320A 3p F F 1SDA100441R1 is a fixed three-pole SACE Tmax XT5 moulded case circuit breaker designed for demanding motor-protection applications. It combines the XT5S 400 frame with a 320 A Ekip M Dip LIU electronic release and front-terminal connections.
The Ekip M Dip LIU release provides advanced motor protection against overload, short circuit, phase loss and phase imbalance. Its overload setting can be adjusted from 128–320 A, while the instantaneous short-circuit threshold spans 1920–4160 A, providing flexibility for coordination with motor starting characteristics.
The XT5S breaking-performance class provides an ultimate short-circuit breaking capacity of 50 kA at 415 V AC. Combined with fixed construction and three-pole operation, this makes the 1SDA100441R1 well suited to motor control centres, industrial machinery and process installations.
The Ekip M Dip LIU release is designed around the protection requirements of three-phase motors. In addition to overload and short-circuit protection, it detects phase loss and phase imbalance, helping protect motors against electrical conditions that can cause overheating, reduced performance and premature failure.
The 128–320 A overload setting range and 1920–4160 A instantaneous short-circuit setting range provide flexibility for coordinating the breaker with the characteristics of the protected motor. The XT5S platform adds a 50 kA Icu at 415 V AC for dependable fault interruption in industrial installations.
| Series | SACE Tmax XT |
|---|---|
| Product group | T-Max XT 250 Range |
| ABB order code | 1SDA100441R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Application | Motor protection |
| Frame size | XT5 |
| Frame | XT5S 400 |
| Breaking-performance class | S |
| Rated current (In) | 320 A |
| Number of poles | 3 |
| Trip unit | Ekip M Dip LIU |
| Release technology | Solid-state electronic |
| Protection functions | Overload, short circuit, phase loss and phase imbalance |
| Overload current setting | 128–320 A |
| Instantaneous short-circuit setting | 1920–4160 A |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 50 kA |
| Rated voltage | 690 V |
| Current type | AC |
| Mounting | Fixed |
| Terminal arrangement | Front terminals |
| Degree of protection | IP20 |
| Power loss | 11.6 W |
| Standard | IEC |
| EAN | 8056221005180 |
The ABB 1SDA100441R1 is an XT5S 400 fixed three-pole moulded case circuit breaker with front terminals and a 320 A Ekip M Dip LIU electronic release designed for motor protection.
The Ekip M Dip LIU provides protection against overload, short circuit, phase loss and phase imbalance, addressing key electrical risks encountered by three-phase motors.
The overload current setting is adjustable from 128–320 A.
The instantaneous short-circuit protection is adjustable from 1920–4160 A.
The XT5S configuration provides an ultimate short-circuit breaking capacity of 50 kA at 415 V AC.
ABB SACE Tmax XT moulded case circuit breakers with Ekip M electronic releases combine configurable motor-protection functions, compact construction and dependable fault-interruption performance for industrial motor circuits and machinery.
We use cookies