Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA100383R1 SACE Tmax XT5N 400 four-pole moulded case circuit breaker with 320 A TMA thermomagnetic release, adjustable thermal overload protection, 1600-3200 A instantaneous magnetic protection, fixed mounting, front terminals and 100% rated neutral. Dimensions 205 x 186 x 103.5 mm.
£1,191.07
The ABB 1SDA100383R1 is a high-performance four-pole moulded case circuit breaker (MCCB) from the ABB SACE Tmax XT range. Its full manufacturer designation is XT5N 400 TMA 320-3200 4p F F InN=100%In. Designed for industrial and commercial low-voltage electrical distribution, it combines a 400 A frame, a 320 A thermomagnetic trip unit and adjustable short-circuit protection.
Featuring ABB's TMA thermomagnetic release, the circuit breaker provides thermal overload protection and adjustable instantaneous magnetic short-circuit protection. Its 320 A rated trip current is complemented by an adjustable magnetic threshold of 1600–3200 A, allowing the instantaneous protection setting to be selected to suit the electrical installation.
The four-pole configuration with a fully rated neutral is particularly valuable in three-phase distribution systems where the neutral conductor requires a protection rating equivalent to the phase conductors. The designation InN=100%In identifies a neutral rating equal to 100% of the rated current.
Supplied in a fixed-mounted configuration with front terminals, the ABB XT5N 400 TMA is suitable for integration into appropriately designed distribution boards, switchboards and electrical control assemblies. Its compact dimensions of 205 × 186 × 103.5 mm and robust moulded case construction make it a practical solution for circuit protection where dependable switching, overload protection and short-circuit interruption are essential.
The ABB XT5N 400 TMA 320-3200 provides both switching and automatic circuit protection within a single moulded case assembly. Unlike a conventional switch-disconnector, this MCCB incorporates a thermomagnetic release that can automatically interrupt the circuit when overload or short-circuit conditions exceed the selected protection settings.
The thermal overload element is designed to respond to sustained overcurrent conditions. Its adjustable setting range of 128–320 A allows the protection threshold to be matched to the protected circuit, subject to conductor ratings, operating conditions and the required protection coordination.
The instantaneous magnetic element provides rapid tripping when the fault current reaches the selected threshold. For this model, ABB specifies an adjustable magnetic range of 1600–3200 A. Selecting the correct setting is important for coordinating downstream protective devices and accommodating permissible starting or inrush currents without compromising fault protection.
The four-pole design provides a switching arrangement for three phase conductors and a neutral conductor. The InN=100%In designation confirms that the neutral is fully rated relative to the circuit breaker's rated current. This makes the model relevant to electrical distribution systems where the neutral may carry significant current, although the suitability of the neutral protection arrangement must be assessed against the installation design.
The fixed-mounted configuration is intended for permanent integration into electrical panels and switchboards. Its front terminals provide a defined connection arrangement for incoming and outgoing power conductors. Correct conductor preparation, terminal torque, clearances and accessory selection must follow ABB's installation documentation.
The XT5N designation identifies the normal breaking-capacity version of ABB's XT5 circuit breaker family. The numerical short-circuit breaking capacity must be checked for the intended operating voltage and current type before installation. The selected MCCB must have sufficient breaking capacity for the prospective fault current at its installation point.
Although the TMA release provides thermal overload and magnetic short-circuit protection, this model does not incorporate integrated earth-fault protection. Where residual-current or earth-fault protection is required, compatible additional protective equipment must be specified as part of the overall electrical system.
The ABB 1SDA100383R1 should be installed by competent electrical personnel in accordance with ABB's instructions and the applicable electrical installation standards. The installation must be designed for the correct operational voltage, prospective short-circuit current, conductor sizes and environmental conditions.
The distinction between the 400 A frame designation and the 320 A rated trip current is essential. This product is an XT5 400-frame circuit breaker fitted with a 320 A TMA release. It should not be described as having a 400 A rated trip current.
The thermal and magnetic protection settings must be selected according to the circuit's electrical design. These settings should account for conductor current-carrying capacity, load characteristics, inrush current, fault levels and the required discrimination or selectivity with upstream and downstream protective devices.
For installations incorporating a neutral conductor, the fully rated neutral arrangement provides a neutral rating equivalent to the phase rating. However, neutral switching and protection requirements must still comply with the relevant earthing system and installation regulations. Protective earth conductors must never be interrupted by the circuit breaker.
The MCCB is supplied with a manual operating mechanism and may be used with compatible ABB accessories where the installation requires additional operating, signalling or control functionality. Accessory compatibility must be confirmed using ABB's XT5 documentation.
Regular inspection and maintenance should follow ABB's published recommendations. Any evidence of overheating, damaged terminals, repeated tripping or mechanical deterioration should be investigated by qualified personnel before the equipment is returned to service.
The ABB 1SDA100383R1 is an XT5N 400 four-pole moulded case circuit breaker with a 320 A TMA thermomagnetic trip unit, adjustable instantaneous protection from 1600 to 3200 A, fixed mounting and front terminals.
It has a 400 A frame designation but a 320 A rated trip current. The 400 A value identifies the frame size, while 320 A is the rated current of the installed TMA release.
TMA identifies an adjustable thermomagnetic trip unit. It combines thermal overload protection with adjustable instantaneous magnetic short-circuit protection.
The thermal overload setting can be adjusted within the range of 128–320 A, subject to ABB's installation and adjustment instructions.
The instantaneous magnetic protection threshold is adjustable from 1600 to 3200 A. The appropriate setting depends on the installation's fault levels, load characteristics and protection coordination requirements.
The circuit breaker has four poles (4P), providing a switching arrangement for three phase conductors and a neutral conductor.
InN=100%In means that the neutral is fully rated at 100% of the circuit breaker's rated current. For this 320 A version, the neutral rating is equivalent to the phase rated current.
XT5 identifies the ABB SACE Tmax XT frame family, while N identifies the normal breaking-capacity version. The actual short-circuit breaking capacity depends on the operating voltage and must be confirmed from ABB's technical ratings.
F F identifies the fixed-mounted configuration with front terminals. This version is designed for permanent installation with power connections at the front of the circuit breaker.
Yes. Its TMA thermomagnetic trip unit provides adjustable thermal overload protection and instantaneous magnetic short-circuit protection. The breaker must be selected and adjusted for the intended circuit.
No. The TMA version provides thermal and magnetic overcurrent protection but does not include integrated earth-fault protection. Separate or compatible additional protection must be specified where required.
ABB identifies this model as suitable for AC and DC applications within its published ratings. The applicable operational voltage, breaking capacity and connection requirements must be checked separately for each application.
The circuit breaker measures 205 × 186 × 103.5 mm (H × W × D) and has an approximate net weight of 5.6 kg.
Both are XT5N 400 TMA 320-3200 four-pole fixed circuit breakers with front terminals. The 1SDA100383R1 has a 100% rated neutral, while the 1SDA100382R1 has a 50% rated neutral. Selection depends on the neutral current requirements of the electrical system.
The ABB order code and product ID are 1SDA100383R1. The EAN / GTIN is 8056221004602, and the full product designation is XT5N 400 TMA 320-3200 4p F F InN=100%In.
The ABB SACE Tmax XT5N 400 TMA 320-3200 four-pole moulded case circuit breaker combines a 400 A frame, 320 A thermomagnetic release, adjustable 1600–3200 A magnetic protection and a fully rated neutral. With fixed mounting, front terminals and proven ABB circuit breaker technology, the 1SDA100383R1 provides a dependable protection and switching solution for professionally designed low-voltage electrical distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.