Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA100355R1 SACE Tmax XT5N 630 A three-pole fixed moulded case circuit breaker with front terminals and an Ekip Dip LS/I electronic trip unit.
£1,519.79
The ABB 1SDA100355R1 is a high-performance 630 A moulded case circuit breaker (MCCB) designed to protect industrial and commercial low-voltage power distribution systems against overloads and short circuits. Part of the advanced ABB SACE Tmax XT range, this three-pole circuit breaker combines compact construction, dependable interruption performance and an electronic protection release.
The circuit breaker is equipped with an Ekip Dip LS/I solid-state trip unit, providing adjustable long-time overload protection together with selective and instantaneous short-circuit protection. This electronic release supports precise protection settings, helping engineers coordinate the breaker with cables, downstream equipment and other protective devices.
With a rated uninterrupted current of 630 A, an operating voltage of up to 690 V AC and a breaking capacity of 36 kA at 380–415 V AC, the ABB XT5N 630 is suitable for demanding switchboards, distribution panels and industrial power systems. Its fixed three-pole configuration and front terminals enable straightforward installation and cable access.
Moulded case circuit breakers such as the ABB XT5N 630 interrupt excessive current before it can damage cables, machinery or electrical distribution equipment. The electronic Ekip Dip LS/I release continuously monitors the circuit and operates the breaker when configured overload or short-circuit thresholds are exceeded.
The adjustable long-time, selective short-circuit and instantaneous protection functions support coordinated system design. This makes the ABB 1SDA100355R1 suitable for installations where reliable fault isolation, operational continuity and protection accuracy are essential.
Tick the specs you need, then view products that match.
| Mounting Type | Fixed | |
|---|---|---|
| Application | Power distribution | |
| Trip Unit | LS/I | |
| Current | 630 A | |
| Phase | Three Phase | |
| Poles | 3-pole | |
| Device Type | MCCB | |
| Breaking Capacity | 36 kA | |
| Manufacturer | ABB | |
| Series | SACE Tmax XT | |
| Model | XT5N 630 Ekip Dip LS/I In=630 3p F F | |
| Product ID | 1SDA100355R1 | |
| Product type | Moulded case circuit breaker | |
| Frame size | XT5 | |
| Rated current | 630 A | |
| Number of poles | 3 | |
| Trip unit | Ekip Dip LS/I electronic release | |
| Rated operating voltage | Up to 690 V AC | |
| Rated insulation voltage | 1000 V | |
| Rated impulse withstand voltage | 8 kV | |
| Breaking capacity at 380–415 V AC | 36 kA | |
| Breaking capacity at 500–525 V AC | 25 kA | |
| Breaking capacity at 690 V AC | 20 kA | |
| Rated short-time withstand current | 6 kA | |
| Mounting version | Fixed | |
| Terminal connection | Front terminals | |
| Power loss | 45 W | |
| Electrical durability | 5,000 operating cycles | |
| Mechanical durability | 20,000 operating cycles | |
| Standards | IEC 60947-2 | |
| Dimensions (H × W × D) | 205 × 140 × 103.5 mm | |
| Weight | Approx. 4.82 kg | |
| EAN | 8056221004329 | |
| HS Code | 85362090 | |
| Country of Manufacture | Italy |
The ABB 1SDA100355R1 protects industrial and commercial low-voltage power circuits against overloads and short circuits.
The XT5N circuit breaker has a rated uninterrupted current of 630 A.
It is fitted with an Ekip Dip LS/I electronic trip unit, providing long-time overload, selective short-circuit and instantaneous protection.
The breaker has a rated short-circuit breaking capacity of 36 kA at 415 V AC.
This model is a fixed three-pole circuit breaker with front terminals for installation inside switchboards and electrical distribution panels.
ABB SACE Tmax XT moulded case circuit breakers are widely used by electrical engineers, panel builders and industrial operators to provide accurate, dependable protection for modern low-voltage power distribution systems.