1SDA100235R1 ABB XT4H 250 Ekip Dip LSI 250 A 3-Pole MCCB

1SDA100235R1 ABB XT4H 250 Ekip Dip LSI 250 A 3-Pole MCCB

ABB 1SDA100235R1 XT4H 250 Ekip Dip LSI 250 A 3-pole fixed moulded case circuit breaker with front terminals and 70 kA breaking capacity at 415 V AC for configurable electronic overload and short-circuit protection.

SKU: 1SDA100235R1MPN: 1SDA100235R1
Price
List Price £2,196.38 ex VAT
Your Price (ex VAT) Save 25%
£1,647.29 25% OFF
You save £549.10 per unit
Manufacturer Lead Time Estimated Delivery 3 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,647.29
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,647.29

Why Choose the ABB 1SDA100235R1 XT4H 250 Ekip Dip LSI Circuit Breaker?

The ABB 1SDA100235R1 is a Tmax XT4H 250 moulded case circuit breaker (MCCB) equipped with an Ekip Dip LSI electronic trip unit. Rated at 250 A and configured as a 3-pole fixed circuit breaker with front terminals, it provides dependable electronic overload and short-circuit protection for AC low-voltage electrical distribution systems.

As part of the ABB Tmax XT range, the XT4 platform combines compact construction with configurable electronic protection for industrial and commercial power distribution. The Ekip Dip LSI trip unit provides long-time, short-time and instantaneous protection functions, helping protect cables, feeders and electrical equipment against sustained overloads and different levels of short-circuit current.

With a rated current and rated uninterrupted current of 250 A, a rated operational voltage of 690 V AC and the high-performance H breaking-capacity class, the 1SDA100235R1 is suited to demanding distribution systems. It provides a rated service and ultimate short-circuit breaking capacity of 70 kA at 415 V AC, while its fixed three-pole construction and front terminals facilitate integration into switchboards and electrical assemblies.

Key Advantages

  • High-performance ABB Tmax XT4H 250 moulded case circuit breaker for low-voltage power distribution.
  • 250 A rated current and 250 A rated uninterrupted current.
  • Ekip Dip LSI electronic trip unit provides configurable overload and short-circuit protection.
  • Long-time, short-time and instantaneous protection functions support effective circuit coordination.
  • 70 kA short-circuit breaking capacity at 415 V AC for demanding fault levels.
  • 3-pole fixed configuration with front terminals for straightforward switchboard integration.

Key Features

  • ABB Tmax XT4H 250 circuit-breaker platform.
  • 250 A rated current (In).
  • 250 A rated uninterrupted current (Iu).
  • Ekip Dip LSI electronic trip unit.
  • 690 V AC rated operational voltage.
  • 1,000 V AC rated insulation voltage (Ui).
  • 8 kV rated impulse withstand voltage (Uimp).
  • Long-time protection adjustable from 100–250 A.
  • Short-time protection adjustable from 1–10 × In.
  • Instantaneous protection adjustable from 1–10 × In.
  • 3-pole fixed configuration with front terminals.
  • H performance level with 70 kA breaking capacity at 415 V AC.

High-Performance Electronic Protection for Power Distribution

Moulded case circuit breakers equipped with electronic trip units monitor current within the protected circuit and interrupt the supply when configured protection thresholds are exceeded. The ABB Ekip Dip platform uses adjustable protection settings to help coordinate circuit protection with the requirements of cables, feeders and electrical equipment in modern low-voltage distribution systems.

The LSI configuration combines long-time protection against sustained overloads, short-time protection for selective fault coordination and instantaneous protection against severe short circuits. Combined with the XT4H 250 platform and its 70 kA breaking capacity at 415 V AC, these functions make the 1SDA100235R1 particularly suitable for installations where high prospective fault currents require robust circuit protection.

Typical Applications

  • Industrial low-voltage distribution systems.
  • Main and sub-distribution switchboards.
  • Commercial and infrastructure power distribution.
  • Cable and feeder circuit protection.
  • Transformer and generator distribution circuits.
  • Machinery, production equipment and OEM electrical assemblies.

Technical Specifications

Series Tmax XT
Product range T-Max XT 250 Range
Order code 1SDA100235R1
GTIN / EAN 8056221002899
Product type Moulded case circuit breaker (MCCB)
Frame XT4
Frame / rated uninterrupted current (Iu) 250 A
Short-circuit performance level H
Trip unit Ekip Dip LSI
Release type Electronic solid-state release
Protection functions Long-time, short-time and instantaneous (LSI)
Rated current (In) 250 A
Long-time protection setting 100–250 A
Short-time protection setting 1–10 × In
Instantaneous protection setting 1–10 × In
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1,000 V AC
Rated impulse withstand voltage (Uimp) 8 kV
Rated frequency 50 / 60 Hz
Rated service breaking capacity (Ics) at 380 V AC 70 kA
Rated service breaking capacity (Ics) at 415 V AC 70 kA
Rated service breaking capacity (Ics) at 440 V AC 65 kA
Rated service breaking capacity (Ics) at 500 V AC 50 kA
Rated service breaking capacity (Ics) at 690 V AC 15 kA
Rated ultimate breaking capacity (Icu) at 415 V AC 70 kA
Number of poles 3
Installation Fixed
Terminal configuration Front terminals
Standard IEC
Dimensions (H × W × D) 160 × 105 × 82.5 mm
Electrical durability 8,000 cycles
Mechanical durability 25,000 cycles
Power loss 16.4 W per pole at rated operating conditions
Net weight 2.5 kg

Frequently Asked Questions

What is the ABB 1SDA100235R1 used for?

The ABB 1SDA100235R1 is an XT4H 250 moulded case circuit breaker designed to provide configurable electronic overload and short-circuit protection for AC low-voltage electrical distribution systems.

What is the rated current of the ABB 1SDA100235R1?

The circuit breaker and its Ekip Dip LSI electronic trip unit have a rated current of 250 A, with a rated uninterrupted current of 250 A.

What does LSI mean on the Ekip Dip trip unit?

LSI refers to long-time, short-time and instantaneous protection, providing configurable electronic protection against sustained overloads and different levels of short-circuit current.

What is the breaking capacity of the ABB 1SDA100235R1?

The XT4H 250 has an H short-circuit performance level with rated service and ultimate short-circuit breaking capacities of 70 kA at 415 V AC.

How is the ABB XT4H 250 1SDA100235R1 installed?

The 1SDA100235R1 has a fixed 3-pole configuration with front terminals, making it suitable for integration into electrical switchboards, distribution panels and OEM electrical assemblies.

Trusted ABB Circuit Protection Technology

ABB Tmax XT moulded case circuit breakers combine compact construction, configurable electronic protection and high short-circuit performance to provide dependable circuit protection for industrial, commercial and OEM low-voltage electrical distribution systems.