1SDA100209R1 ABB XT4S 160 Ekip Dip LSIG In=160A 3p F F MCCB

1SDA100209R1 ABB XT4S 160 Ekip Dip LSIG In=160A 3p F F MCCB

ABB 1SDA100209R1 is a Tmax XT4S 160 three-pole fixed moulded case circuit breaker with front terminals, a 160 A Ekip Dip LSIG electronic trip unit and 50 kA breaking capacity at 415 V AC.

SKU: 1SDA100209R1MPN: 1SDA100209R1
Price
List Price £2,074.34 ex VAT
Your Price (ex VAT) Save 25%
£1,555.76 25% OFF
You save £518.59 per unit
Manufacturer Lead Time Estimated Delivery 3 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,555.76
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,555.76

Why Choose the ABB XT4S 160 Ekip Dip LSIG In=160A 3p F F 1SDA100209R1?

The ABB 1SDA100209R1 is a high-performance Tmax XT4S moulded case circuit breaker (MCCB) designed for reliable protection of low-voltage AC electrical distribution systems. Supplied as a three-pole circuit breaker with an Ekip Dip LSIG electronic trip unit, it combines a 160 A rated current with configurable electronic protection for industrial, commercial and infrastructure applications.

Part of the advanced ABB SACE Tmax XT series, the XT4S 160 provides long-time, short-time, instantaneous and ground-fault protection through its Ekip Dip LSIG release. These LSIG functions provide comprehensive protection against overloads, short circuits and earth faults, while electronic trip technology supports effective selectivity and protection coordination throughout the electrical distribution system.

The 1SDA100209R1 is configured as a fixed three-pole breaker with front terminals and a rated current of 160 A. With a rated operational voltage of 690 V AC, rated insulation voltage of 1000 V AC and rated ultimate short-circuit breaking capacity of 50 kA at 415 V AC, it provides robust protection for demanding low-voltage switchboards and power distribution installations.

Key Advantages

  • Complete ABB Tmax XT4S 160 moulded case circuit breaker for low-voltage power distribution.
  • 160 A Ekip Dip electronic trip unit for accurate and configurable circuit protection.
  • LSIG protection functions covering overload, short-time short-circuit, instantaneous short-circuit and ground-fault conditions.
  • 50 kA Icu and Ics at 415 V AC for dependable short-circuit protection.
  • Three-pole fixed configuration with front terminals for straightforward switchboard installation.
  • 690 V AC rated operational voltage supports demanding industrial electrical distribution applications.

Key Features

  • ABB SACE Tmax XT4S 160 circuit breaker.
  • 160 A rated current (In).
  • Three-pole configuration.
  • Ekip Dip LSIG electronic trip unit.
  • LSIG protection: long-time, short-time, instantaneous and ground-fault functions.
  • 50 kA rated ultimate breaking capacity at 415 V AC.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 8 kV rated impulse withstand voltage.
  • Fixed mounting with front terminals.

Advanced LSIG Protection for Electrical Distribution

Moulded case circuit breakers protect electrical installations by automatically interrupting current when overloads or electrical faults occur. The ABB Ekip Dip electronic release provides configurable protection characteristics, allowing the circuit breaker to be coordinated with the requirements of the installation and other protective devices throughout the distribution system.

With LSIG functionality, the 1SDA100209R1 provides long-time protection against sustained overloads, short-time protection for coordinated short-circuit response, instantaneous protection against severe short circuits and ground-fault protection for earth-fault conditions. Combined with the XT4S performance level and its 50 kA breaking capacity at 415 V AC, this makes the breaker well suited to demanding feeder and distribution protection applications.

Typical Applications

  • Industrial low-voltage switchboards.
  • Main and sub-distribution panels.
  • Commercial electrical distribution systems.
  • Manufacturing and process industry power systems.
  • Feeder and distribution circuit protection.
  • Plant and machinery electrical distribution.

Technical Specifications

Series SACE Tmax XT
Product group T-Max XT 250 Range
ABB order code 1SDA100209R1
EAN 8056221002639
Product type Moulded case circuit breaker (MCCB)
Frame XT4
Frame designation XT4S 160
Short-circuit performance level S
Trip unit Ekip Dip LSIG
Release type Electronic / solid-state
Protection functions LSIG
Long-time protection L
Short-time protection S
Instantaneous protection I
Ground-fault protection G
Rated current (In) 160 A
Rated uninterrupted current (Iu) 160 A
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 8 kV
Rated frequency 50 / 60 Hz
Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC 50 kA
Rated service short-circuit breaking capacity (Ics) at 415 V AC 50 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC 36 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 12 kA
Number of poles 3
Mounting Fixed
Terminal arrangement Front terminals
Current type AC
Power loss at rated operating conditions 8.90 W per pole
Mechanical durability 25,000 cycles
Electrical durability 8,000 cycles
Dimensions (H × W × D) 160 × 105 × 82.5 mm
Weight approx. 2.5 kg
Standard IEC
Application Low-voltage circuit protection and power distribution

Frequently Asked Questions

What is the ABB 1SDA100209R1?

The ABB 1SDA100209R1 is a Tmax XT4S 160 three-pole moulded case circuit breaker with a 160 A Ekip Dip LSIG electronic trip unit, fixed mounting and front terminals.

What protection functions does the Ekip Dip LSIG trip unit provide?

The Ekip Dip LSIG provides long-time, short-time, instantaneous and ground-fault protection, helping protect electrical circuits against overloads, short circuits and earth faults.

What is the rated current of the ABB 1SDA100209R1?

The ABB 1SDA100209R1 has a rated current, In, of 160 A.

What is the breaking capacity of the ABB XT4S 160 1SDA100209R1?

The XT4S 160 has a rated ultimate short-circuit breaking capacity of 50 kA at 415 V AC, with a rated service short-circuit breaking capacity of 50 kA at the same voltage.

How is the ABB XT4S 160 1SDA100209R1 installed?

This model is supplied in a fixed three-pole configuration with front terminals, making it suitable for installation within low-voltage switchboards and electrical distribution panels.

Trusted Circuit Protection from ABB

ABB SACE Tmax XT moulded case circuit breakers combine compact construction with advanced electronic protection to provide dependable circuit protection and power distribution for modern industrial, commercial and infrastructure electrical installations.