Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA100207R1 SACE Tmax XT4S 160 fixed 3-pole moulded-case circuit breaker with a 63 A Ekip Dip LSIG electronic trip unit, front terminals and 50 kA breaking capacity at 380–415 V AC for comprehensive low-voltage power distribution protection.
£1,461.36
The ABB 1SDA100207R1 is a high-performance SACE Tmax XT4S moulded-case circuit breaker (MCCB) designed for comprehensive protection of low-voltage AC power distribution systems. This fixed, three-pole circuit breaker combines the compact XT4 platform with an Ekip Dip LSIG electronic trip unit rated at 63 A, providing reliable protection against overloads, short circuits and earth faults.
As part of the advanced ABB SACE Tmax XT series, the XT4S combines compact construction with microprocessor-based electronic protection for industrial, commercial and infrastructure applications. The Ekip Dip LSIG release provides long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection, allowing effective protection coordination across feeders, cables and connected electrical equipment.
The 1SDA100207R1 is supplied in a fixed, 3-pole configuration with front terminals. Its S performance class provides a rated ultimate and service short-circuit breaking capacity of 50 kA at 380–415 V AC, while the 63 A electronic release provides instantaneous protection adjustment from approximately 63–630 A, making it suitable for demanding distribution circuits where high fault-interruption capability is required.
The ABB Ekip Dip electronic trip unit uses microprocessor-based technology to monitor current through the circuit breaker and initiate tripping when configured protection thresholds are exceeded. Its LSIG functionality combines long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection, helping safeguard feeders, cables and connected equipment while supporting coordinated distribution-system design.
The SACE Tmax XT4S platform combines compact dimensions with high short-circuit performance and flexible installation. With 50 kA breaking capacity at 380–415 V AC, fixed mounting, front terminals and comprehensive electronic protection, the 1SDA100207R1 is particularly suitable for switchboards and distribution assemblies where high prospective fault currents and dependable circuit isolation must be accommodated.
| Series | SACE Tmax XT |
|---|---|
| Product range | T-Max XT 250 Range |
| Order code | 1SDA100207R1 |
| Product type | Moulded-case circuit breaker (MCCB) |
| Frame | XT4 |
| Short-circuit performance level | S |
| Rated uninterrupted current (Iu) | 160 A |
| Trip unit | Ekip Dip LSIG |
| Trip-unit rated current (In) | 63 A |
| Instantaneous protection range | approx. 63–630 A |
| Number of poles | 3 |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1,000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Rated frequency | 50 / 60 Hz |
| Rated ultimate breaking capacity (Icu) at 380–415 V AC | 50 kA |
| Rated service breaking capacity (Ics) at 380–415 V AC | 50 kA |
| Breaking capacity at 500 V AC | 36 kA |
| Breaking capacity at 690 V AC | 12 kA |
| Protection functions | L, S, I and G |
| Release type | Electronic (EL) |
| Mounting execution | Fixed |
| Terminal arrangement | Front terminals |
| Application | Transformer, generator and installation protection |
| Standards | IEC |
| Net weight | 2.5 kg |
| GTIN / EAN | 8056221002615 |
The ABB 1SDA100207R1 is a SACE Tmax XT4S moulded-case circuit breaker designed to protect low-voltage AC distribution circuits against overloads, short circuits and earth faults.
The breaker has an XT4 frame with 160 A rated uninterrupted current and is equipped with an Ekip Dip LSIG electronic trip unit rated at 63 A.
LSIG provides long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection, giving the breaker comprehensive electronic protection for low-voltage distribution circuits.
The XT4S provides a short-circuit breaking capacity of 50 kA at 380–415 V AC, with 36 kA at 500 V AC and 12 kA at 690 V AC.
The breaker is supplied in a fixed, 3-pole configuration with front terminals for installation in low-voltage switchboards, distribution panels and industrial electrical assemblies.
ABB SACE Tmax XT moulded-case circuit breakers combine compact construction, high short-circuit performance and configurable electronic protection to safeguard modern industrial, commercial and infrastructure power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.