ABB 1SDA100071R1 is an XT2H 160 three-pole moulded case circuit breaker with a 25 A Ekip Dip LIG electronic trip unit, 70 kA breaking capacity at 415 V AC and fixed front-terminal construction.
£1,218.60
The ABB XT2H 160 Ekip Dip LIG In=25A 3p F F, order code 1SDA100071R1, is a compact and high-performance moulded case circuit breaker (MCCB) designed for low-voltage AC power distribution and circuit protection. As part of the ABB SACE Tmax XT2 range, it combines a 160 A frame with a 25 A Ekip Dip LIG electronic trip unit for dependable overload, short-circuit and earth-fault protection.
This XT2H breaker features a 3-pole configuration, fixed mounting and front terminals, making it suitable for integration into industrial and commercial switchboards. The Ekip Dip LIG solid-state release provides L, I and G protection functions, covering long-time overload, instantaneous short-circuit and ground-fault protection.
With a rated current of 25 A and an ultimate short-circuit breaking capacity of 70 kA at 415 V AC, the 1SDA100071R1 provides high fault-interruption performance for demanding distribution applications. Its rated operational voltage extends to 690 V AC, while the compact XT2 frame helps optimise available switchboard space.
Moulded case circuit breakers such as the ABB Tmax XT2 protect electrical circuits and connected equipment against abnormal current conditions. The Ekip Dip LIG electronic release combines long-time overload protection with instantaneous short-circuit and earth-fault protection, helping provide coordinated protection for low-voltage AC distribution systems.
The Tmax XT2H platform combines compact dimensions with high short-circuit interruption capability and electronic protection technology. Its three-pole construction, fixed mounting and front-terminal arrangement make the XT2H 160 suitable for industrial switchboards, distribution panels and equipment feeders requiring dependable protection.
| Series | SACE Tmax XT2 |
|---|---|
| ABB order code | 1SDA100071R1 |
| Product type | Moulded case circuit breaker |
| Frame size | XT2 160 |
| Performance level | H |
| Rated uninterrupted current (Iu) | 160 A |
| Rated current (In) | 25 A |
| Trip unit | Ekip Dip LIG |
| Release type | Electronic / solid-state |
| Protection functions | LIG |
| Number of poles | 3 |
| Rated ultimate short-circuit breaking capacity (Icu) | 70 kA at 415 V AC |
| Rated service short-circuit breaking capacity (Ics) | 70 kA at 415 V AC |
| Rated operational voltage | Up to 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Current type | AC |
| Mounting | Fixed |
| Terminal arrangement | Front terminals |
| Dimensions (H × W × D) | 130 × 90 × 82.5 mm |
| Net weight | 1.12 kg |
| EAN | 8056221001250 |
It is a 3-pole moulded case circuit breaker designed to protect low-voltage AC distribution circuits against overload, short-circuit and earth-fault conditions.
This circuit breaker has a 25 A rated current and is built on the ABB XT2 frame with a rated uninterrupted current of 160 A.
The Ekip Dip LIG electronic trip unit provides long-time overload, instantaneous short-circuit and earth-fault protection.
The XT2H version provides an ultimate short-circuit breaking capacity of 70 kA at 415 V AC.
This model is a fixed three-pole circuit breaker with front terminals, designed for installation in low-voltage switchboards and distribution panels.
ABB SACE Tmax XT moulded case circuit breakers combine compact construction, high fault-interruption capability and dependable electronic protection for industrial, commercial and OEM low-voltage power distribution systems.
We use cookies