ABB 1SDA100064R1 XT2H 160 is a 160 A three-pole fixed moulded case circuit breaker with front terminals, an Ekip Dip LSI electronic trip unit, a 64–160 A long-time setting range and 70 kA ultimate breaking capacity at 400–415 V AC.
£1,121.37
The ABB 1SDA100064R1 is a high-performance three-pole moulded case circuit breaker (MCCB) from the ABB SACE Tmax XT2 range, designed for reliable protection of transformers, generators and low-voltage electrical installations. Rated at 160 A, it combines the compact XT2H 160 frame with an Ekip Dip LSI electronic trip unit for configurable overload and short-circuit protection.
The Ekip Dip LSI release provides long-time (L), short-time (S) and instantaneous (I) protection functions. The long-time current threshold can be adjusted from 64–160 A, while the short-time and instantaneous thresholds provide adjustable protection up to 10 × In, enabling effective coordination with downstream circuits and connected equipment.
The 1SDA100064R1 is supplied as a fixed three-pole circuit breaker with front terminals. Its XT2H performance level provides an ultimate short-circuit breaking capacity of 70 kA at 400–415 V AC, making it particularly suitable for industrial and commercial distribution systems where high prospective fault currents require substantial interruption capability in a compact MCCB.
The ABB Ekip Dip LSI trip unit combines three complementary electronic protection functions within the compact Tmax XT2 platform. Long-time protection responds to sustained overload conditions, short-time protection supports selective coordination during fault conditions, and instantaneous protection provides rapid interruption of severe short circuits. The 64–160 A long-time setting range allows the breaker to be configured around the requirements of the protected circuit.
The XT2H version is designed for installations requiring greater fault interruption capability than lower performance levels of the XT2 family. With an ultimate breaking capacity of 70 kA at 400–415 V AC, a 160 A Ekip Dip LSI release and fixed front-terminal construction, the 1SDA100064R1 provides a compact solution for demanding switchboards and distribution assemblies with high prospective short-circuit currents.
| Series | SACE Tmax XT / T-Max XT 250 Range |
|---|---|
| ABB order code | 1SDA100064R1 |
| Product type | Moulded case circuit breaker |
| Frame | XT2H 160 |
| Frame size | XT2 |
| Frame current | 160 A |
| Rated current (In) | 160 A |
| Trip unit | Ekip Dip LSI electronic release |
| Protection functions | Long-time (L), short-time (S) and instantaneous (I) |
| Long-time current adjustment | 64–160 A |
| Short-time protection adjustment | 1–10 × In |
| Instantaneous protection adjustment | 1–10 × In |
| Instantaneous current range | 160–1600 A |
| Number of poles | 3 |
| Performance level | H |
| Ultimate breaking capacity (Icu) at 400–415 V AC | 70 kA |
| Mounting / execution | Fixed |
| Terminal position | Front |
| Release technology | Solid-state / microprocessor electronic |
| Application | AC electrical distribution |
| Typical protection applications | Transformer, generator and installation protection |
| GTIN / EAN | 8056221001182 |
| Product net weight | 1.2 kg |
| Customs tariff number | 85362090 |
The ABB 1SDA100064R1 is a 160 A three-pole moulded case circuit breaker designed for transformer, generator and installation protection in demanding low-voltage AC distribution systems.
The Ekip Dip LSI electronic trip unit provides long-time (L), short-time (S) and instantaneous (I) protection against overload and short-circuit conditions.
The long-time current protection can be adjusted from 64–160 A, while the short-time and instantaneous thresholds are adjustable from 1–10 × In. The instantaneous range therefore extends from 160–1600 A.
The XT2H performance level provides an ultimate short-circuit breaking capacity of 70 kA at 400–415 V AC, making it suitable for installations with substantial prospective fault currents.
The 1SDA100064R1 is supplied as a fixed three-pole circuit breaker with front terminals for integration into compatible low-voltage switchboards, distribution panels and electrical assemblies.
ABB SACE Tmax XT moulded case circuit breakers combine compact construction, configurable electronic protection and robust short-circuit performance, with the XT2H platform providing high interruption capability for demanding transformer, generator, industrial and commercial power distribution applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.