1SDA100042R1 ABB XT2S 160 Ekip Dip LIG 63A 3P F F Circuit Breaker

1SDA100042R1 ABB XT2S 160 Ekip Dip LIG 63A 3P F F Circuit Breaker

ABB 1SDA100042R1 is a 63 A three-pole SACE Tmax XT2S 160 moulded case circuit breaker with Ekip Dip LIG electronic overload, instantaneous short-circuit and ground-fault protection, fixed mounting, front terminals and 50 kA short-circuit performance.

SKU: 1SDA100042R1MPN: 1SDA100042R1
Price
List Price £1,592.78 ex VAT
Your Price (ex VAT) Save 25%
£1,194.59 25% OFF
You save £398.20 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,194.59
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,194.59

Why Choose the ABB XT2S 160 Ekip Dip LIG 63A 3P Circuit Breaker?

The ABB XT2S 160 Ekip Dip LIG In=63A 3P F F, order code 1SDA100042R1, is a three-pole moulded case circuit breaker (MCCB) from the ABB SACE Tmax XT range. Built on the compact XT2 160 A frame, it combines the S short-circuit performance level with an electronic protection system for industrial and commercial low-voltage power distribution.

This circuit breaker has a 63 A rated current and incorporates an Ekip Dip LIG solid-state electronic trip unit. The LIG configuration provides long-time overload (L), instantaneous short-circuit (I) and ground-fault (G) protection, providing comprehensive electronic protection for compatible AC distribution circuits.

The 1SDA100042R1 is supplied as a fixed three-pole circuit breaker with front terminals. It has a rated operational voltage of up to 690 V AC, a 160 A rated uninterrupted current and a service short-circuit breaking capacity of 50 kA at 415 V AC, making it suitable for demanding switchboard and equipment-protection applications.

Key Advantages

  • 63 A three-pole MCCB from the ABB SACE Tmax XT range.
  • Compact XT2 160 A frame for space-efficient electrical panels.
  • S short-circuit performance level for demanding distribution applications.
  • Ekip Dip LIG electronic trip unit provides comprehensive electronic protection.
  • Long-time (L) protection for sustained overload conditions.
  • Instantaneous (I) protection for high short-circuit currents.
  • Ground-fault (G) protection for earth-fault conditions.
  • 50 kA service breaking capacity at 415 V AC.
  • Fixed mounting with front terminals for practical switchboard integration.

Key Features

  • ABB SACE Tmax XT series.
  • XT2 frame size.
  • S short-circuit performance level.
  • 160 A rated uninterrupted current (Iu).
  • 63 A rated current (In).
  • Ekip Dip LIG electronic release.
  • L, I and G protection functions.
  • Three-pole configuration.
  • Fixed installation.
  • Front terminals.
  • Rated operational voltage up to 690 V AC.
  • 1000 V rated insulation voltage.
  • 8 kV rated impulse withstand voltage.

Electronic LIG Protection with High Short-Circuit Performance

The Ekip Dip LIG release gives the ABB 1SDA100042R1 three complementary electronic protection functions. Long-time protection responds to sustained overloads, instantaneous protection provides rapid interruption during severe short circuits, and the ground-fault function provides dedicated protection against earth-fault conditions.

Combined with the XT2S 50 kA performance platform, this electronic protection makes the breaker suitable for circuits where dependable fault interruption and ground-fault protection are required. Its compact XT2 construction, fixed mounting and front terminals also support efficient integration into compatible low-voltage distribution assemblies.

Typical Applications

  • Industrial low-voltage distribution boards.
  • Commercial electrical distribution systems.
  • Transformer and installation protection.
  • Generator protection circuits.
  • Feeder and cable protection.
  • Electrical switchboards and panel assemblies.
  • Industrial machinery and process equipment.
  • OEM switchgear and electrical distribution assemblies.

Technical Specifications

Series SACE Tmax XT
Product family T-Max XT 250 Range
ABB order code 1SDA100042R1
EAN 8056221000963
Product type Moulded case circuit breaker (MCCB)
Frame XT2
Rated uninterrupted current (Iu) 160 A
Short-circuit performance level S / 50 kA
Rated current (In) 63 A
Trip unit Ekip Dip LIG solid-state electronic release
Release type Electronic (EL)
Protection functions Long-time overload, instantaneous short circuit and ground fault (LIG)
Number of poles 3
Installation Fixed
Terminal configuration Front terminals
Rated operational voltage Up to 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Service short-circuit breaking capacity (Ics) at 380 V AC 50 kA
Service short-circuit breaking capacity (Ics) at 415 V AC 50 kA
Service short-circuit breaking capacity (Ics) at 440 V AC 50 kA
Service short-circuit breaking capacity (Ics) at 500 V AC 36 kA
Service short-circuit breaking capacity (Ics) at 690 V AC 12 kA
Electrical endurance 8,000 cycles
Operating rate 120 cycles per hour
Standard IEC 60947

Frequently Asked Questions

What is the ABB 1SDA100042R1?

The ABB 1SDA100042R1 is an XT2S 160 three-pole moulded case circuit breaker with a 63 A rated current, Ekip Dip LIG electronic protection, fixed mounting and front terminals.

What protection functions does the Ekip Dip LIG release provide?

The Ekip Dip LIG release provides long-time overload protection (L), instantaneous short-circuit protection (I) and ground-fault protection (G).

What is the rated current of the ABB XT2S 1SDA100042R1?

The breaker has a rated current of 63 A and is built on an XT2 frame with a rated uninterrupted current of 160 A.

What is the short-circuit performance of the ABB XT2S 1SDA100042R1?

The XT2S has an S / 50 kA short-circuit performance level. For this model, the rated service short-circuit breaking capacity is 50 kA at 415 V AC.

How is the ABB 1SDA100042R1 installed?

The 1SDA100042R1 is supplied as a fixed three-pole circuit breaker with front terminals for integration into compatible switchboards, distribution panels and electrical assemblies.

Trusted by Electrical Professionals Worldwide

ABB SACE Tmax XT moulded case circuit breakers combine compact construction, configurable electronic protection and dependable short-circuit performance for industrial and commercial low-voltage distribution systems.