1SDA100040R1 ABB XT2S 160 Ekip Dip LIG 10 A 3-Pole Circuit Breaker

1SDA100040R1 ABB XT2S 160 Ekip Dip LIG 10 A 3-Pole Circuit Breaker

ABB 1SDA100040R1 XT2S 160 is a 10 A three-pole fixed moulded case circuit breaker with an Ekip Dip LIG electronic trip unit, adjustable overload and instantaneous protection and 50 kA ultimate breaking capacity at 400 V AC.

SKU: 1SDA100040R1MPN: 1SDA100040R1
Price
List Price £1,380.41 ex VAT
Your Price (ex VAT) Save 25%
£1,035.31 25% OFF
You save £345.10 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,035.31
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,035.31

Why Choose the ABB XT2S 160 Ekip Dip LIG In=10A 3p F F Circuit Breaker?

The ABB 1SDA100040R1 is a compact three-pole moulded case circuit breaker (MCCB) from the ABB SACE Tmax XT2 range, designed for protection of transformers, generators and low-voltage electrical installations. Rated at 10 A, it combines the XT2S 160 frame with an Ekip Dip LIG electronic trip unit for configurable overload, instantaneous short-circuit and ground-fault protection.

The Ekip Dip LIG release provides long-time (L), instantaneous (I) and ground-fault (G) protection functions. The overload protection setting range is 4–10 A, while the instantaneous short-circuit protection can be adjusted from 10–100 A, allowing the protection characteristics to be matched to the requirements of the protected circuit.

The 1SDA100040R1 is supplied as a fixed three-pole breaker with front terminals and is rated for operation at up to 690 V AC. The XT2S performance level provides an ultimate short-circuit breaking capacity of 50 kA at 400 V AC, making this MCCB suitable for industrial, commercial and infrastructure distribution systems where compact dimensions and substantial fault interruption capability are required.

Key Advantages

  • 10 A electronic MCCB for transformer, generator and installation protection.
  • Ekip Dip LIG electronic trip unit provides long-time, instantaneous and ground-fault protection functions.
  • Adjustable overload protection range of 4–10 A.
  • Adjustable instantaneous short-circuit protection from 10–100 A.
  • High 50 kA ultimate breaking capacity at 400 V AC.
  • Compact three-pole XT2 construction with fixed mounting and front terminals.

Key Features

  • ABB SACE Tmax XT2S 160 moulded case circuit breaker.
  • 10 A rated current.
  • Three-pole configuration.
  • Ekip Dip LIG electronic release.
  • Long-time (L) overload protection.
  • Instantaneous (I) short-circuit protection.
  • Ground-fault (G) protection function.
  • S performance level with 50 kA Icu at 400 V AC.
  • Rated voltage of 690 V AC.
  • Fixed execution with front terminals.

Electronic LIG Protection with High Breaking Capacity

The ABB Ekip Dip LIG trip unit combines three complementary protection functions within the compact Tmax XT2 platform. Long-time protection responds to sustained overload conditions, instantaneous protection rapidly disconnects severe short circuits, and the ground-fault function supports protection against earth-fault conditions. Adjustable settings allow the breaker to be coordinated with the electrical characteristics of the protected installation.

The XT2S version provides greater short-circuit interruption capability than the XT2N performance level while retaining the compact XT2 frame. With a 50 kA Icu at 400 V AC, a 10 A electronic release and fixed front-terminal construction, the 1SDA100040R1 is well suited to distribution panels requiring low-current protection combined with substantial prospective fault-current capability.

Typical Applications

  • Transformer protection.
  • Generator protection.
  • Industrial low-voltage power distribution.
  • Commercial building electrical distribution.
  • Switchboards and distribution panels requiring electronic protection.
  • OEM machinery and electrical distribution assemblies.

Technical Specifications

Series SACE Tmax XT / T-Max XT 250 Range
ABB order code 1SDA100040R1
Product type Moulded case circuit breaker
Frame XT2S 160
Frame size XT2
Rated current (In) 10 A
Trip unit Ekip Dip LIG electronic release
Protection functions Long-time (L), instantaneous (I) and ground-fault (G)
Overload protection adjustment 4–10 A
Instantaneous short-circuit protection adjustment 10–100 A
Number of poles 3
Rated voltage 690 V AC
Ultimate breaking capacity (Icu) at 400 V AC 50 kA
Mounting / execution Fixed
Terminal position Front
Main circuit connection Bolt connection
Operating element Toggle / handle
Complete device with protection unit Yes
Integrated motor operator No
Optional motor operator Yes
Degree of protection IP20
Power loss 0.1 W
EAN 8056221000949
Customs tariff number 85362090

Frequently Asked Questions

What is the ABB 1SDA100040R1 used for?

The ABB 1SDA100040R1 is a 10 A three-pole moulded case circuit breaker designed for transformer, generator and installation protection in low-voltage AC distribution systems.

What protection functions does the Ekip Dip LIG trip unit provide?

The Ekip Dip LIG electronic trip unit provides long-time (L), instantaneous (I) and ground-fault (G) protection functions.

What is the overload adjustment range of the ABB 1SDA100040R1?

The overload protection setting can be adjusted from 4–10 A, allowing the long-time protection threshold to be matched to the protected circuit.

What is the breaking capacity of the ABB XT2S 160 1SDA100040R1?

The XT2S version provides an ultimate short-circuit breaking capacity of 50 kA at 400 V AC.

How is the ABB 1SDA100040R1 installed?

The 1SDA100040R1 is supplied as a fixed three-pole circuit breaker with front terminals for integration into compatible low-voltage switchboards, distribution panels and electrical assemblies.

Trusted ABB Electronic Circuit Protection for Power Distribution

ABB SACE Tmax XT moulded case circuit breakers combine compact construction, configurable electronic protection and robust short-circuit performance, with the XT2S platform providing dependable protection for transformers, generators and industrial or commercial low-voltage distribution systems.