ABB 1SDA100024R1 is a fixed four-pole SACE Tmax XT2N moulded case circuit breaker rated at 160 A with front terminals, a 100% fully rated neutral and an Ekip Dip LSIG electronic trip unit providing overload, short-circuit and ground-fault protection.
£1,510.23
The ABB XT2N 160 Ekip Dip LSIG In=160A 4p FF In=100% 1SDA100024R1 is a 4-pole moulded case circuit breaker (MCCB) from the ABB SACE Tmax XT range, designed for advanced protection of low-voltage AC power distribution systems. Built on the compact XT2 160 frame, it has a 160 A rated current and ABB's N short-circuit performance level.
Protection is provided by an Ekip Dip LSIG electronic trip unit, delivering long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection. The electronic release also incorporates thermal memory and front LED fault indication, providing a versatile protection platform for industrial and commercial power distribution.
The breaker is supplied in a fixed, 4-pole configuration with front terminals and a 100% fully rated neutral. It is rated for operation up to 690 V AC with a rated insulation voltage of 1,000 V AC, while its N performance level provides an ultimate and service short-circuit breaking capacity of 36 kA at 415 V AC.
The Ekip Dip LSIG electronic trip unit provides four key protection functions within the breaker. The L function protects against sustained overloads, the S function provides selective short-time short-circuit protection, the I function responds to severe short-circuit faults, and the G function provides ground-fault protection.
The trip unit also incorporates thermal memory and front LED fault indication. Combined with the breaker's 160 A rating, 100% fully rated neutral and 36 kA Icu/Ics at 415 V AC, these capabilities make the 1SDA100024R1 a versatile protection solution for distribution systems requiring electronic fault protection and four-pole switching.
| Series | SACE Tmax XT |
|---|---|
| Product group | T-Max XT 250 Range |
| Order code | 1SDA100024R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame / subtype | XT2 |
| Short-circuit performance level | N |
| Rated current (In) | 160 A |
| Rated uninterrupted current (Iu) | 160 A |
| Release | Ekip Dip LSIG |
| Release type | Electronic / solid-state |
| Protection functions | L, S, I, G |
| Neutral rating | 100% fully rated neutral |
| Number of poles | 4 |
| Version | Fixed |
| Terminal connection | Front |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated voltage (Ur) | 690 V AC |
| Rated insulation voltage (Ui) | 1,000 V AC |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Rated frequency | 50/60 Hz |
| Ultimate breaking capacity (Icu) at 220–240 V AC | 65 kA |
| Ultimate breaking capacity (Icu) at 380 V AC | 36 kA |
| Ultimate breaking capacity (Icu) at 415 V AC | 36 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 36 kA |
| Ultimate breaking capacity (Icu) at 500 V AC | 30 kA |
| Ultimate breaking capacity (Icu) at 525 V AC | 20 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 10 kA |
| Service breaking capacity (Ics) at 220–240 V AC | 65 kA |
| Service breaking capacity (Ics) at 380 V AC | 36 kA |
| Service breaking capacity (Ics) at 415 V AC | 36 kA |
| Service breaking capacity (Ics) at 440 V AC | 36 kA |
| Service breaking capacity (Ics) at 500 V AC | 30 kA |
| Service breaking capacity (Ics) at 525 V AC | 20 kA |
| Service breaking capacity (Ics) at 690 V AC | 10 kA |
| Power loss at rated operating conditions per pole | 10.80 W |
| Mechanical endurance | 25,000 operations |
| Electrical endurance | 8,000 operations |
| Standard | IEC 60947-2 |
| EAN | 8056221000796 |
The ABB 1SDA100024R1 has a rated current (In) and rated uninterrupted current (Iu) of 160 A.
The Ekip Dip LSIG electronic trip unit provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection.
Yes. This 4-pole version has a 100% fully rated neutral, as indicated by the ABB designation In=100%.
At 415 V AC, the breaker has an ultimate short-circuit breaking capacity (Icu) of 36 kA and a service short-circuit breaking capacity (Ics) of 36 kA.
The 1SDA100024R1 is a fixed, 4-pole moulded case circuit breaker with front terminals, an Ekip Dip LSIG electronic release, a 160 A rated current and a 100% fully rated neutral.
ABB SACE Tmax XT moulded case circuit breakers combine compact construction with advanced electronic protection, providing dependable overload, short-circuit and ground-fault protection for industrial, commercial and OEM low-voltage power distribution systems.