Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA080850R1 is a fixed four-pole SACE Tmax XT1H moulded case circuit breaker rated at 16 A with front terminals, a TMF thermal-magnetic release, a 450 A instantaneous short-circuit setting and 70 kA ultimate breaking capacity at 415 V AC.
£373.34
The ABB XT1H 160 TMF 16-450 4p F F 1SDA080850R1 is a 4-pole moulded case circuit breaker (MCCB) from the ABB SACE Tmax XT range, designed for dependable overload and short-circuit protection in low-voltage power distribution systems. Built on the compact XT1 160 frame, it combines a 16 A rated current with ABB's H short-circuit performance level.
Protection is provided by a TMF thermal-magnetic trip unit. The thermal protection is fixed at the breaker's 16 A rated current, while the instantaneous magnetic short-circuit setting is 450 A, providing automatic protection against sustained overloads and high-current short circuits.
The breaker is supplied in a fixed, 4-pole configuration with front terminals and supports operational voltages up to 690 V AC and 500 V DC. Its XT1H performance level provides an ultimate short-circuit breaking capacity of 70 kA at 415 V AC, making it suitable for industrial, commercial and OEM distribution systems where high fault-current capability and four-pole protection are required.
The TMF thermal-magnetic trip unit combines thermal overload protection with instantaneous magnetic short-circuit protection. For this 16 A version, the thermal protection setting is fixed at 16 A, providing protection against sustained currents above the intended circuit rating.
The magnetic element operates at an instantaneous short-circuit setting of 450 A. Combined with the XT1H's 70 kA Icu at 415 V AC and four-pole construction, this makes the 1SDA080850R1 particularly suitable for distribution systems where compact dimensions, four-conductor isolation and high short-circuit interruption capability are important.
| Series | SACE Tmax XT |
|---|---|
| Product group | T-Max XT 250 Range |
| Order code | 1SDA080850R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame size | XT1 |
| Short-circuit performance level | H |
| Rated current (In) | 16 A |
| Rated uninterrupted current (Iu) | 160 A |
| Trip unit | TMF thermal-magnetic |
| Thermal setting | 16 A |
| Instantaneous short-circuit setting (Ii) | 450 A |
| Number of poles | 4 |
| Version | Fixed |
| Terminal connection | Front |
| Current type | AC/DC |
| Rated operational voltage | 690 V AC / 500 V DC |
| Rated insulation voltage (Ui) | 800 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Ultimate breaking capacity (Icu) at 220–240 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 380 V AC | 70 kA |
| Ultimate breaking capacity (Icu) at 415 V AC | 70 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 65 kA |
| Ultimate breaking capacity (Icu) at 500 V AC | 50 kA |
| Ultimate breaking capacity (Icu) at 525 V AC | 35 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 10 kA |
| Service breaking capacity (Ics) at 380 V AC | 52.5 kA |
| Service breaking capacity (Ics) at 415 V AC | 37.5 kA |
| Service breaking capacity (Ics) at 440 V AC | 32.5 kA |
| Service breaking capacity (Ics) at 500 V AC | 25 kA |
| Standard | IEC 60947-2 |
| Protection degree | IP20 |
| Dimensions (W × H × D) | 101.6 × 130 × 70 mm |
| Net weight | approx. 1.3 kg |
| Mechanical endurance | 25,000 operations |
| Electrical endurance | 8,000 operations |
| EAN / GTIN | 8015644873783 |
The ABB 1SDA080850R1 has a rated current of 16 A and is built on the XT1 frame, which has a rated uninterrupted current of 160 A.
It uses a TMF thermal-magnetic trip unit, providing fixed thermal overload protection at 16 A together with instantaneous magnetic short-circuit protection.
The instantaneous magnetic short-circuit setting is 450 A.
The breaker has an ultimate short-circuit breaking capacity (Icu) of 70 kA at 380 V AC and 70 kA at 415 V AC. Breaking capacity varies according to the applied voltage.
Yes. The 1SDA080850R1 is a fixed 4-pole moulded case circuit breaker with front terminals, making it suitable for compatible three-phase and neutral distribution applications requiring four-pole switching and protection.
ABB SACE Tmax XT moulded case circuit breakers combine compact construction, dependable thermal-magnetic protection and high short-circuit performance, making them a proven choice for industrial, commercial and OEM low-voltage electrical distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.