1SDA080849R1 ABB XT1S 160 TMD 40-450 4p F F

1SDA080849R1 ABB XT1S 160 TMD 40-450 4p F F

ABB 1SDA080849R1 is a fixed four-pole SACE Tmax XT1S moulded case circuit breaker rated at 40 A with front terminals, an adjustable 28–40 A TMD thermal-magnetic release and a 450 A instantaneous short-circuit setting.

SKU: 1SDA080849R1Alt SKU: XT1S 160MPN: 1SDA080849R1
Price
List Price £448.07 ex VAT
Your Price (ex VAT) Save 25%
£336.05 25% OFF
You save £112.02 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £336.05
Trade pricing is personalised to your account

Manufacturer Lead Time

£336.05

Why Choose the ABB XT1S 160 TMD 40-450 4p F F Circuit Breaker?

The ABB XT1S 160 TMD 40-450 4p F F 1SDA080849R1 is a 4-pole moulded case circuit breaker (MCCB) from the ABB SACE Tmax XT range, designed for dependable overload and short-circuit protection in low-voltage power distribution systems. Built on the compact XT1 160 frame, it has a 40 A rated current and ABB's S short-circuit performance level.

Protection is provided by a TMD thermal-magnetic trip unit. The thermal overload setting is adjustable across 28–40 A, while the instantaneous magnetic short-circuit setting is 450 A, providing protection against sustained overload conditions and high-current short circuits.

The breaker is supplied in a fixed, 4-pole configuration with front terminals and has a rated voltage of 690 V. The XT1S performance level provides an ultimate short-circuit breaking capacity of 50 kA at 415 V AC, making this MCCB suitable for industrial, commercial and OEM electrical distribution applications requiring four-pole switching and protection.

Key Advantages

  • Thermal-magnetic protection against overload and short-circuit conditions.
  • Adjustable thermal setting range of 28–40 A.
  • Instantaneous magnetic short-circuit setting of 450 A.
  • 50 kA ultimate breaking capacity at 415 V AC.
  • 4-pole configuration for applications requiring switching and protection across four conductors.
  • Compact XT1 160 frame for space-efficient panel installation.
  • Fixed construction with front terminals for straightforward integration.
  • IEC-certified ABB SACE Tmax XT circuit protection.

Key Features

  • ABB SACE Tmax XT1S moulded case circuit breaker.
  • 40 A rated current (In).
  • XT1 frame with 160 A frame capacity.
  • TMD thermal-magnetic release.
  • Thermal setting range: 28–40 A.
  • Instantaneous short-circuit setting: 450 A.
  • 4-pole configuration.
  • Fixed circuit breaker version.
  • Front terminal connections.
  • Rated voltage: 690 V.
  • Rated insulation voltage: 800 V.
  • Rated impulse withstand voltage: 8 kV.

Four-Pole Thermal-Magnetic Protection for Low-Voltage Distribution

The TMD thermal-magnetic trip unit combines two complementary protection functions. Its thermal element responds to sustained overload conditions and can be adjusted between 28 A and 40 A, allowing the overload protection setting to be matched to the requirements of the connected circuit.

For high-current short circuits, the magnetic element provides rapid operation at an instantaneous setting of 450 A. Combined with the breaker's 4-pole configuration and XT1S short-circuit performance, this makes the 1SDA080849R1 suitable for three-phase distribution systems where switching and protection of an additional neutral conductor is required by the system design.

Typical Applications

  • Industrial low-voltage distribution boards.
  • Commercial electrical distribution systems.
  • Three-phase and neutral feeder protection.
  • Four-pole electrical distribution circuits.
  • Machinery and industrial control panels.
  • OEM electrical equipment and assemblies.
  • Switchboards and distribution enclosures.

Technical Specifications

Series SACE Tmax XT
Product group T-Max XT 250 Range
Order code 1SDA080849R1
Alternate catalogue number XT1SE4040AFF000XXX
Product type Moulded case circuit breaker (MCCB)
Frame size XT1
Short-circuit performance level S
Rated current (In) 40 A
Frame capacity 160 A
Trip unit TMD thermal-magnetic
Thermal setting range 28–40 A
Instantaneous short-circuit setting 450 A
Number of poles 4
Version Fixed
Terminal connection Front
Rated voltage 690 V
Rated operational voltage up to 690 V AC / 500 V DC
Rated insulation voltage (Ui) 800 V
Rated impulse withstand voltage (Uimp) 8 kV
Ultimate breaking capacity (Icu) at 380 V AC 50 kA
Ultimate breaking capacity (Icu) at 415 V AC 50 kA
Service breaking capacity (Ics) at 380 V AC 50 kA
Service breaking capacity (Ics) at 415 V AC 37.5 kA
Service breaking capacity (Ics) at 440 V AC 25 kA
Service breaking capacity (Ics) at 500 V AC 18 kA
Certification IEC
Dimensions (W × H × D) 101.6 × 130 × 70 mm
Net weight approx. 1.3 kg
Mechanical endurance 25,000 operations
Electrical endurance 8,000 operations
Country of origin Italy
EAN / UPC 8015644873776

Frequently Asked Questions

What is the rated current of the ABB 1SDA080849R1?

The ABB 1SDA080849R1 has a rated current of 40 A and is built on the ABB SACE Tmax XT1 160 frame.

What protection does the XT1S 160 TMD 40-450 provide?

It uses a TMD thermal-magnetic trip unit, providing adjustable thermal overload protection and instantaneous magnetic short-circuit protection.

What are the protection settings of the ABB 1SDA080849R1?

The thermal overload setting is adjustable from 28–40 A, while the instantaneous magnetic short-circuit setting is 450 A.

What is the breaking capacity of the ABB XT1S 1SDA080849R1?

The XT1S has an ultimate short-circuit breaking capacity (Icu) of 50 kA at 415 V AC. Its service short-circuit breaking capacity (Ics) at the same voltage is 37.5 kA.

Is the ABB 1SDA080849R1 a four-pole circuit breaker?

Yes. The 1SDA080849R1 is a fixed 4-pole moulded case circuit breaker with front terminals, making it suitable for compatible three-phase and neutral distribution applications requiring four-pole switching and protection.

Trusted ABB Circuit Protection

ABB SACE Tmax XT moulded case circuit breakers combine compact construction, dependable thermal-magnetic protection and strong short-circuit performance, making them a proven choice for industrial, commercial and OEM low-voltage electrical distribution systems.