1SDA080834R1 ABB XT1S 160 TMD 40-450 3p F F

1SDA080834R1 ABB XT1S 160 TMD 40-450 3p F F

ABB 1SDA080834R1 is a fixed three-pole SACE Tmax XT1S moulded case circuit breaker rated at 40 A with front terminals, an adjustable 28–40 A TMD thermal-magnetic release and a 450 A instantaneous short-circuit setting.

SKU: 1SDA080834R1Alt SKU: XT1S 160MPN: 1SDA080834R1
Price
List Price £356.89 ex VAT
Your Price (ex VAT) Save 25%
£267.67 25% OFF
You save £89.22 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £267.67
Trade pricing is personalised to your account

Manufacturer Lead Time

£267.67

Why Choose the ABB XT1S 160 TMD 40-450 3p F F Circuit Breaker?

The ABB XT1S 160 TMD 40-450 3p F F 1SDA080834R1 is a 3-pole moulded case circuit breaker (MCCB) from the ABB SACE Tmax XT range, designed for overload and short-circuit protection in low-voltage power distribution systems. Built on the compact XT1 160 frame, it combines a 40 A rated current with ABB's S short-circuit performance level.

Protection is provided by a TMD thermal-magnetic trip unit. The thermal overload setting is adjustable across 28–40 A, while the instantaneous magnetic short-circuit setting is 450 A, providing coordinated protection against sustained overloads and high-current faults.

The breaker is supplied in a fixed, 3-pole configuration with front terminals. It supports rated operational voltages up to 690 V AC and 500 V DC, with an ultimate short-circuit breaking capacity of 50 kA at 415 V AC, making it suitable for demanding industrial, commercial and OEM electrical distribution applications.

Key Advantages

  • Thermal-magnetic protection against overload and short-circuit conditions.
  • Adjustable thermal setting range of 28–40 A.
  • Instantaneous magnetic setting of 450 A.
  • 50 kA ultimate breaking capacity at 415 V AC.
  • Compact XT1 160 frame for space-efficient panel installation.
  • Fixed 3-pole construction for three-phase distribution systems.
  • Front terminals provide straightforward conductor access.
  • Designed to applicable IEC requirements for moulded case circuit breakers.

Key Features

  • ABB SACE Tmax XT1S moulded case circuit breaker.
  • 160 A rated uninterrupted current (Iu).
  • 40 A rated current (In).
  • TMD thermal-magnetic release.
  • Thermal setting range: 28–40 A.
  • Instantaneous short-circuit setting: 450 A.
  • 3-pole configuration.
  • Fixed circuit breaker version.
  • Front terminal connections.
  • Rated operational voltage up to 690 V AC / 500 V DC.
  • Rated insulation voltage of 800 V.
  • Rated impulse withstand voltage of 8 kV.

Thermal-Magnetic Protection for Low-Voltage Distribution

The TMD thermal-magnetic trip unit combines two complementary protection functions. Its thermal element responds to sustained overload conditions and can be adjusted between 28 A and 40 A, allowing the overload protection level to be matched to the requirements of the connected circuit.

For high-current short circuits, the magnetic element provides rapid operation at an instantaneous setting of 450 A. Combined with the XT1S breaking performance and compact XT1 frame, this makes the 1SDA080834R1 suitable for protecting feeders, distribution circuits and industrial electrical loads where reliable fault interruption is required.

Typical Applications

  • Industrial low-voltage distribution boards.
  • Commercial electrical distribution systems.
  • Three-phase feeder protection.
  • Machinery and industrial control panels.
  • OEM electrical equipment.
  • Switchboards and distribution enclosures.
  • Transformer, generator and installation protection applications.

Technical Specifications

Series SACE Tmax XT
Product group T-Max XT 250 Range
Order code 1SDA080834R1
Alternate catalogue number XT1SE3040AFF000XXX
Product type Moulded case circuit breaker (MCCB)
Frame size XT1
Short-circuit performance level S
Rated current (In) 40 A
Rated uninterrupted current (Iu) 160 A
Trip unit TMD thermal-magnetic
Thermal setting range 28–40 A
Instantaneous short-circuit setting 450 A
Number of poles 3
Version Fixed
Terminal connection Front
Current type AC/DC
Rated operational voltage 690 V AC / 500 V DC
Rated insulation voltage (Ui) 800 V
Rated impulse withstand voltage (Uimp) 8 kV
Ultimate breaking capacity (Icu) at 380 V AC 50 kA
Ultimate breaking capacity (Icu) at 415 V AC 50 kA
Service breaking capacity (Ics) at 380 V AC 50 kA
Service breaking capacity (Ics) at 415 V AC 37.5 kA
Service breaking capacity (Ics) at 440 V AC 25 kA
Service breaking capacity (Ics) at 500 V AC 18 kA
Dimensions (W × H × D) 76.2 × 130 × 70 mm
Net weight approx. 1 kg
Mechanical endurance 25,000 operations
Electrical endurance 8,000 operations
Country of origin Italy
EAN / UPC 8015644873622

Frequently Asked Questions

What is the rated current of the ABB 1SDA080834R1?

The ABB 1SDA080834R1 has a rated current of 40 A and uses the XT1 frame, which has a rated uninterrupted current of 160 A.

What protection does the XT1S 160 TMD 40-450 provide?

It uses a TMD thermal-magnetic trip unit, providing adjustable thermal overload protection and instantaneous magnetic short-circuit protection.

What are the protection settings of the ABB 1SDA080834R1?

The thermal overload setting is adjustable from 28–40 A, while the instantaneous magnetic short-circuit setting is 450 A.

What is the breaking capacity of the ABB XT1S 1SDA080834R1?

The breaker has an ultimate short-circuit breaking capacity (Icu) of 50 kA at 380 V AC and 50 kA at 415 V AC. Breaking capacity varies according to the applied voltage.

How is the ABB 1SDA080834R1 installed?

The 1SDA080834R1 is a fixed, 3-pole circuit breaker with front terminals, designed for installation in compatible low-voltage switchboards, distribution panels and electrical assemblies.

Trusted ABB Circuit Protection

ABB SACE Tmax XT moulded case circuit breakers combine compact construction, dependable thermal-magnetic protection and strong short-circuit performance, making them a proven choice for industrial, commercial and OEM low-voltage electrical distribution systems.