ABB 1SDA075197R1 XT4S 250 is a three-pole fixed UL/CSA moulded case circuit breaker with front terminals, a 100 A TMA thermomagnetic release, 70–100 A adjustable overload protection and 500–1000 A adjustable instantaneous short-circuit protection.
£522.77
The ABB XT4S 250 TMA 100 500..1000 3p F F UL/CSA, order code 1SDA075197R1, is a three-pole moulded case circuit breaker designed for dependable overload and short-circuit protection in low-voltage electrical distribution systems. Part of the ABB SACE Tmax XT / T-Max XT 250 Range, it combines the compact XT4 frame with an adjustable thermomagnetic release for industrial and commercial power distribution applications.
The breaker incorporates an ABB TMA thermomagnetic release with a nominal setting of 100 A. Its overload protection is adjustable from 70–100 A, while the instantaneous magnetic short-circuit release can be adjusted from 500–1000 A, allowing protection settings to be matched to the requirements of the connected circuit.
This XT4S configuration features a three-pole fixed construction with front terminals and is designed for operation on systems up to 600 V AC. The S-performance XT4 provides a short-circuit breaking capacity of 35 kA, making the 1SDA075197R1 a practical UL/CSA solution for switchboards, distribution panels, machinery and other demanding electrical installations.
The TMA thermomagnetic release provides adjustable protection against both overload and short-circuit conditions. Its thermal element can be set between 70 and 100 A, allowing the breaker to be coordinated with the protected conductors and load, while the magnetic element provides rapid fault interruption with an adjustable 500–1000 A instantaneous trip range.
The ABB Tmax XT4 platform combines compact dimensions with flexible protection and installation options. The fixed three-pole construction and front-terminal arrangement of the 1SDA075197R1 make it suitable for integration into switchboards, distribution assemblies, machinery panels and other low-voltage installations.
| Series | SACE Tmax XT / T-Max XT 250 Range |
|---|---|
| ABB order code | 1SDA075197R1 |
| Extended product type | XT4S 250 TMA 100 500..1000 3p F F UL/CSA |
| Product type | Moulded case circuit breaker |
| Frame size | XT4 |
| Frame designation | XT4S 250 |
| Performance level | S |
| Trip unit | TMA thermomagnetic |
| Trip-unit rating | 100 A |
| Overload release adjustment | 70–100 A |
| Instantaneous short-circuit release adjustment | 500–1000 A |
| Number of poles | 3 |
| Rated voltage | up to 600 V AC |
| Short-circuit breaking capacity | 35 kA |
| Mounting type | Fixed |
| Terminal type | Front terminals |
| Main-circuit connection | Bolt connection |
| Degree of protection | IP20 |
| Certification | UL / CSA |
| EAN | 8015644791742 |
It is a three-pole moulded case circuit breaker designed to provide adjustable overload and short-circuit protection in low-voltage electrical distribution systems.
The TMA thermomagnetic release has a nominal rating of 100 A, with its overload protection adjustable from 70–100 A.
It identifies the adjustable instantaneous magnetic short-circuit trip range of 500–1000 A.
The XT4S is the S-performance version of the Tmax XT4 and provides a short-circuit breaking capacity of 35 kA.
This model is a fixed three-pole circuit breaker with front terminals, designed for installation in compatible switchboards, distribution panels and industrial electrical assemblies.
ABB SACE Tmax XT moulded case circuit breakers provide compact and dependable protection for industrial and commercial electrical distribution systems, with adjustable thermomagnetic releases offering flexible overload and short-circuit protection for demanding applications.