ABB 1SDA074912R1 XT2S 125 is a fixed three-pole 60 A moulded case circuit breaker with front terminals, an Ekip Dip LS/I solid-state electronic release and a 35 kA interruption rating at 480 V AC for UL/CSA low-voltage applications.
£492.81
The ABB 1SDA074912R1, designated XT2S 125 Ekip LS/I In=60A 3p F F UL/CSA, is a fixed three-pole moulded case circuit breaker (MCCB) from the ABB SACE Tmax XT range. Built on the XT2S 125 frame, it has a rated current of 60 A and uses an Ekip Dip LS/I solid-state electronic trip unit for precise overload and short-circuit protection.
The Ekip LS/I release provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection. Electronic protection offers accurate and repeatable tripping characteristics, supporting effective coordination within industrial, commercial and OEM low-voltage distribution systems.
Designed for UL/CSA applications, the 1SDA074912R1 is supplied as a fixed three-pole breaker with front terminals. The XT2S performance level provides a UL interruption rating of 35 kA at 480 V AC, while ABB specifies a rated voltage of 600 V for this configuration.
The Ekip Dip LS/I release uses electronic current measurement to provide precise protection against the principal overcurrent conditions encountered in low-voltage distribution systems. Long-time protection responds to sustained overloads, short-time protection enables controlled response to short-circuit currents, and instantaneous protection provides rapid interruption of severe faults.
For the ABB 1SDA074912R1, these electronic protection functions are combined with a 60 A rated current and the XT2S interruption performance of 35 kA at 480 V AC. This makes the breaker suitable for applications requiring more sophisticated protection and coordination than a conventional fixed thermal-magnetic release can provide.
| Series | SACE Tmax XT |
|---|---|
| Product group | T-Max XT 250 Range |
| Frame / size | XT2S 125 |
| ABB order code | 1SDA074912R1 |
| Alternate catalogue number | XT2SU3060EFF000XXX |
| EAN / GTIN | 8015644788896 |
| Product type | Moulded case circuit breaker |
| Application | Low-voltage power distribution |
| Rated current (In) | 60 A |
| Frame rated current | 125 A |
| Number of poles | 3 |
| Trip unit | Ekip Dip LS/I solid-state electronic release |
| Protection functions | Long-time, short-time and instantaneous (LS/I) |
| Rated voltage | 600 V |
| Interruption rating | S – 35 kA at 480 V AC |
| Installation | Fixed |
| Main connection | Front terminals |
| Certification | UL |
| Country of origin | Italy |
| Customs tariff number | 85362090 |
The ABB 1SDA074912R1 is an XT2S 125 three-pole moulded case circuit breaker rated at 60 A with an Ekip Dip LS/I solid-state electronic release, fixed mounting and front terminals for UL/CSA applications.
The Ekip LS/I release provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection.
The XT2S performance level provides an interruption rating of 35 kA at 480 V AC for this UL configuration.
The breaker has a rated current of 60 A and is built on the XT2S 125 frame.
The breaker is supplied as a fixed three-pole unit with front terminals for integration into compatible low-voltage switchboards, panels and electrical equipment.
ABB SACE Tmax XT moulded case circuit breakers combine compact construction with advanced electronic protection, and the XT2S 125 Ekip LS/I 60 A provides precise long-time, short-time and instantaneous protection for demanding UL/CSA industrial, commercial and OEM low-voltage applications.