1SDA073551R1 ABB E6.2H/MS 6300 4p WMP Switch Disconnector

1SDA073551R1 ABB E6.2H/MS 6300 4p WMP Switch Disconnector

ABB 1SDA073551R1 SACE Emax 2 E6.2H/MS 6300 four-pole withdrawable air switch disconnector moving part rated at 6300 A and 690 V AC with 100 kA one-second short-time withstand capability for high-current low-voltage switching and isolation.

SKU: 1SDA073551R1MPN: 1SDA073551R1
Price
List Price £54,454.07 ex VAT
Your Price (ex VAT) Save 25%
£40,840.55 25% OFF
You save £13,613.52 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £40,840.55
Trade pricing is personalised to your account

Manufacturer Lead Time

£40,840.55

Why Choose the ABB E6.2H/MS 6300 4p WMP Switch Disconnector?

The ABB E6.2H/MS 6300 4p WMP, order code 1SDA073551R1, is a high-capacity four-pole withdrawable air switch disconnector from the ABB SACE Emax 2 family, engineered for dependable switching and electrical isolation in demanding low-voltage power distribution systems. Built on the Emax 2 E6.2 platform, it provides a substantial 6300 A rated uninterrupted current for high-power industrial and infrastructure installations.

The E6.2H/MS is a switch-disconnector configuration designed to satisfy isolation requirements rather than provide automatic overcurrent protection. The 1SDA073551R1 is the withdrawable moving part for use with a compatible Emax 2 fixed part, enabling convenient disconnection for inspection, servicing and maintenance while supporting high-current switchboard architectures.

With a rated operational voltage of 690 V AC and a rated short-time withstand current of 100 kA for 1 s, the E6.2H/MS is engineered for installations with demanding prospective fault levels. Its four-pole configuration and H performance level make it a robust switching and isolation solution for large low-voltage distribution systems.

Key Advantages

  • High-capacity 6300 A air switch disconnector for major low-voltage distribution systems.
  • Four-pole configuration for comprehensive circuit switching and isolation.
  • 100 kA short-time withstand current for 1 s for high-fault-level installations.
  • 690 V AC rated operational voltage for demanding industrial power systems.
  • Withdrawable moving-part construction supports efficient inspection and maintenance.
  • Built on the high-current ABB SACE Emax 2 E6.2 platform.

Key Features

  • ABB SACE Emax 2 E6.2H/MS series.
  • 6300 A rated uninterrupted current.
  • 4-pole configuration.
  • 50% rated neutral pole.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 100 kA Icw for 1 s.
  • 100 kA Icw for 3 s.
  • Withdrawable moving-part construction for compatible Emax 2 switchgear.

Reliable High-Current Switching and Isolation

ABB Emax 2 /MS switch disconnectors are designed to provide dependable switching and electrical isolation of low-voltage power circuits. Unlike an automatic Emax 2 air circuit breaker equipped with a protection trip unit, the /MS configuration is intended primarily to establish, carry, interrupt and isolate the electrical path within a coordinated power distribution system.

The withdrawable E6.2H/MS architecture allows the moving part to be separated from its compatible fixed part, supporting efficient inspection, servicing and equipment replacement. Combined with its 6300 A current rating and 100 kA short-time withstand capability, the 1SDA073551R1 provides a powerful switching and isolation solution for large-scale low-voltage distribution assemblies.

Typical Applications

  • High-capacity main low-voltage distribution switchboards.
  • Heavy industrial power distribution systems.
  • Data centres and critical infrastructure.
  • Large commercial and infrastructure installations.
  • High-current four-pole circuit isolation and sectionalising.
  • OEM withdrawable switchgear and power distribution assemblies.

Technical Specifications

Series SACE Emax 2 E6.2
ABB order code 1SDA073551R1
Product type Air switch disconnector moving part
Rated uninterrupted current (Iu) 6300 A
Number of poles 4
Neutral pole current 50% Iu
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Rated short-time withstand current (Icw), 1 s 100 kA
Rated short-time withstand current (Icw), 3 s 100 kA
Rated current, AC-21 at 400 V 6300 A
Rated current, AC-23 at 400 V 6300 A
Performance level H
Current type AC
Installation Withdrawable
Device configuration Moving part
Power loss 1550 W
Mechanical durability 12,000 cycles
Electrical durability 2,000 cycles
Net depth 383 mm
Net weight 134 kg
EAN / GTIN 8015644774011
Standard IEC

Frequently Asked Questions

What is the ABB 1SDA073551R1 used for?

The ABB 1SDA073551R1 is an Emax 2 E6.2H/MS withdrawable air switch disconnector moving part designed for high-current switching and electrical isolation in demanding low-voltage power distribution systems.

What is the current rating of the ABB E6.2H/MS 6300?

The switch disconnector has a rated uninterrupted current of 6300 A.

What short-time current can the E6.2H/MS 6300 withstand?

The device has a rated short-time withstand current of 100 kA for 1 s and 100 kA for 3 s.

What voltage is the ABB 1SDA073551R1 rated for?

The switch disconnector has a rated operational voltage of 690 V AC, a rated insulation voltage of 1000 V AC and a rated impulse withstand voltage of 12 kV.

Is the ABB E6.2H/MS 6300 fixed or withdrawable?

The 1SDA073551R1 is the withdrawable moving part of the switch disconnector and is designed for use with the appropriate ABB Emax 2 fixed part.

Trusted ABB Power Distribution Technology

ABB SACE Emax 2 switch disconnectors combine high-current capability, robust short-time withstand performance and flexible withdrawable construction for demanding industrial, commercial and infrastructure low-voltage power distribution systems.