1SDA073540R1 ABB E4.2V/MS 2500 4p WMP Switch Disconnector

1SDA073540R1 ABB E4.2V/MS 2500 4p WMP Switch Disconnector

ABB 1SDA073540R1 SACE Emax 2 E4.2V/MS 2500 four-pole withdrawable air switch disconnector moving part rated at 2500 A and 690 V AC with 100 kA one-second short-time withstand capability for demanding low-voltage switching and isolation.

SKU: 1SDA073540R1MPN: 1SDA073540R1
Price
List Price £14,188.44 ex VAT
Your Price (ex VAT) Save 25%
£10,641.33 25% OFF
You save £3,547.11 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £10,641.33
Trade pricing is personalised to your account

Manufacturer Lead Time

£10,641.33

Why Choose the ABB E4.2V/MS 2500 4p WMP Switch Disconnector?

The ABB E4.2V/MS 2500 4p WMP, order code 1SDA073540R1, is a high-performance four-pole withdrawable air switch disconnector from the ABB SACE Emax 2 family, engineered for dependable high-current switching and electrical isolation in demanding low-voltage power distribution systems. Built on the Emax 2 E4.2 platform, it combines a substantial 2500 A continuous-current rating with the strong short-time withstand performance of the V version.

The E4.2V/MS is a switch-disconnector configuration intended primarily for switching and electrical isolation rather than automatic overcurrent protection. The 1SDA073540R1 is supplied as the withdrawable moving part for use with the appropriate Emax 2 fixed part, allowing the device to be disconnected for inspection, servicing and maintenance.

With a rated uninterrupted current of 2500 A, a rated operational voltage of 690 V AC and a rated short-time withstand current of 100 kA for 1 s, the E4.2V/MS is designed for demanding high-fault-level distribution systems. Its four-pole configuration supports comprehensive switching and isolation in suitable three-phase four-wire installations.

Key Advantages

  • High-capacity 2500 A air switch disconnector for demanding low-voltage distribution.
  • Four-pole configuration for comprehensive circuit switching and isolation.
  • 100 kA short-time withstand current for 1 s for high-fault-level installations.
  • 690 V AC rated operational voltage for industrial power systems.
  • Withdrawable moving-part construction supports convenient inspection and maintenance.
  • Built on the proven ABB SACE Emax 2 E4.2 platform.

Key Features

  • ABB SACE Emax 2 E4.2V/MS series.
  • 2500 A rated uninterrupted current.
  • 4-pole configuration.
  • 690 V AC rated operational voltage.
  • 100 kA Icw for 1 s.
  • 2500 A AC-21 current rating at 400 V.
  • 2500 A AC-23 current rating at 400 V.
  • Withdrawable moving-part construction.
  • Switch-disconnector design for high-current switching and isolation.
  • Designed for integration with the appropriate Emax 2 withdrawable fixed part.

Reliable High-Current Switching and Isolation

ABB Emax 2 /MS switch disconnectors are designed to provide dependable switching and electrical isolation of low-voltage power circuits. Unlike an automatic Emax 2 air circuit breaker equipped with a protection trip unit, the /MS configuration is intended primarily to establish, carry, interrupt and isolate the electrical path within a coordinated power distribution system.

The withdrawable E4.2V/MS architecture allows the moving part to be separated from its compatible fixed part, supporting efficient inspection, servicing and equipment replacement. Combined with its 2500 A current rating and 100 kA one-second short-time withstand capability, the 1SDA073540R1 is particularly suitable for demanding high-current low-voltage distribution assemblies.

Typical Applications

  • High-capacity main low-voltage distribution switchboards.
  • Industrial power distribution systems.
  • Data centres and critical infrastructure.
  • Commercial and utility electrical installations.
  • Four-pole circuit isolation and sectionalising.
  • OEM withdrawable switchgear and power distribution assemblies.

Technical Specifications

Series SACE Emax 2 E4.2
ABB order code 1SDA073540R1
Product type Air switch disconnector moving part
Rated uninterrupted current (Iu) 2500 A
Number of poles 4
Rated operational voltage (Ue) 690 V AC
Rated short-time withstand current (Icw), 1 s 100 kA
Rated current, AC-21 at 400 V 2500 A
Rated current, AC-23 at 400 V 2500 A
Performance level V
Installation Withdrawable
Device configuration Moving part
Power loss 743 W
EAN / GTIN 8015644773908
Standard IEC

Frequently Asked Questions

What is the ABB 1SDA073540R1 used for?

The ABB 1SDA073540R1 is an Emax 2 E4.2V/MS withdrawable air switch disconnector moving part designed for high-current switching and electrical isolation in demanding low-voltage power distribution systems.

What is the current rating of the ABB E4.2V/MS 2500?

The switch disconnector has a rated uninterrupted current of 2500 A.

What short-time current can the E4.2V/MS 2500 withstand?

The ABB E4.2V/MS 2500 has a rated short-time withstand current of 100 kA for 1 s.

What voltage is the ABB 1SDA073540R1 rated for?

The switch disconnector has a rated operational voltage of 690 V AC.

Is the ABB E4.2V/MS 2500 fixed or withdrawable?

The 1SDA073540R1 is the withdrawable moving part of the switch disconnector and is designed for use with the appropriate ABB Emax 2 fixed part.

Trusted ABB Power Distribution Technology

ABB SACE Emax 2 switch disconnectors combine robust high-current construction, exceptional short-time withstand capability and flexible withdrawable installation for demanding industrial, commercial and infrastructure low-voltage power distribution systems.