Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA073508R1 E6.2H/MS 4000 three-pole withdrawable moving-part air switch disconnector with a 4000 A rated current, 690 V AC operational voltage and 100 kA 1-second short-time withstand capability for high-current low-voltage power distribution and isolation.
£16,371.29
The ABB E6.2H/MS 4000 3p WMP, order code 1SDA073508R1, is a high-current three-pole withdrawable air switch disconnector from the ABB SACE Emax 2 range. Designed for demanding low-voltage power distribution systems, it provides a substantial 4000 A rated uninterrupted current for major industrial, commercial and infrastructure switchboards.
Built on the E6.2 frame with ABB's H performance level, the E6.2H/MS provides a rated short-time withstand current of 100 kA for 1 s. This high withstand capability makes it suitable for installations with significant prospective fault currents, while appropriately coordinated protective equipment elsewhere in the electrical system provides automatic overload and short-circuit protection.
This model is supplied as a withdrawable moving part (WMP) in a three-pole configuration. With a rated operational voltage of 690 V AC, the 1SDA073508R1 combines high-current switching capability with the maintainability and service flexibility of a withdrawable Emax 2 installation.
ABB SACE Emax 2 /MS switch disconnectors are engineered for controlled switching and electrical isolation in low-voltage power distribution systems. Unlike an automatic circuit breaker equipped with a protection trip unit, the /MS configuration performs the switching and isolation function while appropriately coordinated protective devices elsewhere in the installation provide the required automatic fault protection.
The withdrawable architecture allows the E6.2H/MS moving portion to be separated from the corresponding fixed switchboard part, supporting inspection, servicing and equipment replacement. Combined with its 4000 A continuous-current capacity and 100 kA 1-second short-time withstand capability, the 1SDA073508R1 is particularly suited to major switchboards where high current capacity, robust fault withstand and serviceable isolation are essential.
| Series | SACE Emax 2 |
|---|---|
| Order code | 1SDA073508R1 |
| EAN | 8015644773588 |
| Product type | Air switch disconnector |
| Frame | E6.2 |
| Performance level | H |
| Rated uninterrupted current (Iu) | 4000 A |
| Number of poles | 3 |
| Rated operational voltage (Ue) | 690 V AC |
| Rated short-time withstand current (Icw), 1 s | 100 kA |
| Installation | Withdrawable |
| Configuration | Moving part (WMP) |
| Power loss | 544 W |
| Conformity | IEC |
The ABB 1SDA073508R1 is an E6.2H/MS air switch disconnector designed for high-current switching and electrical isolation in demanding low-voltage power distribution systems.
The E6.2H/MS 4000 has a rated uninterrupted current of 4000 A.
The E6.2H/MS 4000 has a rated short-time withstand current of 100 kA for 1 s, providing high fault-current withstand performance for demanding distribution systems.
WMP identifies the withdrawable moving part configuration, allowing the switching unit to be withdrawn from the corresponding fixed part of an Emax 2 switchboard installation.
The E6.2H/MS 4000 3p WMP has a rated operational voltage of 690 V AC.
ABB SACE Emax 2 switch disconnectors provide dependable high-current switching and electrical isolation for industrial, commercial and infrastructure power systems, with the E6.2H/MS platform combining 4000 A capacity, withdrawable construction and 100 kA short-time withstand performance for demanding low-voltage switchboards.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.