Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA073495R1 E2.2B/MS 2000 three-pole withdrawable moving-part air switch disconnector with a 2000 A rated current, 690 V AC operational voltage and 42 kA 1-second short-time withstand capability for low-voltage power distribution and isolation.
£5,890.75
The ABB E2.2B/MS 2000 3p WMP, order code 1SDA073495R1, is a high-current three-pole withdrawable air switch disconnector from the ABB SACE Emax 2 range, designed for dependable switching and electrical isolation in low-voltage power distribution systems. Built on the E2.2 frame, this /MS device provides a substantial 2000 A rated uninterrupted current for industrial, commercial and infrastructure switchboards.
The E2.2B/MS combines its high continuous-current capacity with a rated short-time withstand current of 42 kA for 1 s. This enables the switch disconnector to withstand demanding fault-current conditions while appropriately coordinated protective equipment within the electrical installation provides automatic overload and short-circuit protection.
This model is supplied as the withdrawable moving part (WMP) of the Emax 2 switch-disconnector system. Its three-pole construction and 690 V AC rated operational voltage make it particularly suitable for switchboards where high-current switching, dependable isolation and convenient removal of the switching unit for servicing are required.
ABB SACE Emax 2 /MS switch disconnectors are designed to provide controlled switching and electrical isolation in low-voltage power distribution systems. Unlike an automatic circuit breaker equipped with an electronic protection trip unit, the /MS configuration is intended primarily for switching and isolation, with suitable protective devices elsewhere in the system providing the required automatic fault protection.
The withdrawable architecture allows the E2.2B/MS moving part to be separated from its corresponding fixed switchboard section, helping simplify inspection, servicing and equipment replacement. Combined with its 2000 A continuous-current rating and 42 kA 1-second short-time withstand capability, the 1SDA073495R1 provides a robust solution for high-current switchboards requiring dependable isolation and serviceable switchgear.
| Series | SACE Emax 2 |
|---|---|
| Order code | 1SDA073495R1 |
| EAN | 8015644773458 |
| Product type | Air switch disconnector |
| Frame | E2.2 |
| Performance level | B |
| Rated uninterrupted current (Iu) | 2000 A |
| Number of poles | 3 |
| Rated operational voltage (Ue) | 690 V AC |
| Rated short-time withstand current (Icw), 1 s | 42 kA |
| Installation | Withdrawable |
| Configuration | Moving part (WMP) |
| Product net width | 317 mm |
| Product net height | 425 mm |
| Product net depth | 383 mm |
| Product net weight | 48 kg |
| Power loss | 450 W |
| Conformity | IEC |
The ABB 1SDA073495R1 is an E2.2B/MS air switch disconnector designed for high-current switching and electrical isolation in low-voltage power distribution systems.
The E2.2B/MS 2000 has a rated uninterrupted current of 2000 A.
The E2.2B/MS 2000 has a rated short-time withstand current of 42 kA for 1 s.
WMP identifies the withdrawable moving part configuration, allowing the switching unit to be withdrawn from the corresponding fixed part of an Emax 2 switchboard installation.
The E2.2B/MS 2000 3p WMP has a rated operational voltage of 690 V AC.
ABB SACE Emax 2 switch disconnectors provide dependable high-current switching and electrical isolation for industrial, commercial and infrastructure power systems, with the E2.2B/MS platform combining withdrawable construction, robust fault-current withstand and serviceable operation for modern low-voltage switchboards.