Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA073466R1 SACE Emax 2 E6.2X/MS 5000 four-pole fixed switch disconnector with horizontal rear terminals, a 5000 A rated uninterrupted current, 690 V AC operational voltage and 120 kA short-time withstand capability for very high-current low-voltage switching and isolation.
£28,562.09
The ABB E6.2X/MS 5000 4p FHR, order code 1SDA073466R1, is a high-performance SACE Emax 2 switch disconnector designed for switching and isolation in very high-current low-voltage electrical distribution systems. Built on ABB's E6.2 platform, this fixed four-pole device provides a 5000 A rated uninterrupted current and is engineered for demanding industrial, infrastructure and critical-power switchboards.
The E6.2X/MS configuration is a switch disconnector rather than a protective air circuit breaker equipped with an electronic trip unit. It is designed to make, carry and isolate high-current circuits while overload and short-circuit protection is provided separately within the installation. The X performance level provides an exceptional 120 kA rated short-time withstand current for 1 s, supporting applications with very high prospective fault currents.
The 1SDA073466R1 is supplied in a fixed four-pole configuration with horizontal rear terminals (HR). Rated for operation at up to 690 V AC, with a 1000 V AC insulation voltage and 12 kV impulse withstand voltage, it combines very high current-carrying capacity with robust short-time withstand performance and switchboard integration flexibility.
Switch disconnectors provide a dependable means of making, carrying and isolating electrical circuits while dedicated protective equipment elsewhere in the installation provides overload and short-circuit protection. In major low-voltage distribution systems, high short-time withstand capability is particularly important where substantial prospective fault currents can occur at main switchboards, transformer secondaries and high-capacity busbar systems.
The ABB E6.2X/MS 5000 combines a 5000 A continuous-current rating with a 120 kA short-time withstand capability for 1 s and 100 kA for 3 s. Its fixed four-pole construction, 50% neutral-pole rating and horizontal rear terminals make it particularly suitable for high-capacity switchboards requiring dependable isolation, very high short-time current withstand performance and efficient rear busbar integration.
| Series | SACE Emax 2 |
|---|---|
| Order code / MPN | 1SDA073466R1 |
| EAN / GTIN | 8015644773168 |
| Product type | Switch disconnector |
| Product group | Emax2 Air Circuit Breaker |
| Frame | E6.2 |
| Performance level | X/MS |
| Short-circuit performance level | X |
| Rated current (In) | 5000 A |
| Rated uninterrupted current (Iu) | 5000 A |
| Number of poles | 4 |
| Neutral pole current | 50% of Iu |
| Current type | AC |
| Rated operational voltage (Ue) | 690 V AC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated short-time withstand current (Icw), 1 s | 120 kA |
| Rated short-time withstand current (Icw), 3 s | 100 kA |
| Rated current, AC-21 at 400 V | 5000 A |
| Rated current, AC-23 at 400 V | 5000 A |
| Electrical durability at Ue ≤ 440 V | 3000 cycles |
| Electrical durability at Ue 500–690 V | 2000 cycles |
| Electrical operating frequency | 10 cycles per hour |
| Mechanical durability | 12000 cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Power loss | 483 W |
| Motor drive | Optional |
| Motor drive integrated | No |
| Voltage release | Optional |
| Interlockable | Yes |
| Main-circuit connection | Bolted connection |
| Installation | Fixed |
| Terminal configuration | Rear flat horizontal (HR) |
| Front-side degree of protection | IP30 |
| Dimensions (W × H × D) | 888 × 371 × 270 mm |
| Net weight | 125 kg |
| Standard | IEC |
The ABB 1SDA073466R1 is an Emax 2 E6.2X/MS 5000 four-pole switch disconnector with fixed installation and horizontal rear terminals, designed for very high-current low-voltage switching and isolation.
The E6.2X/MS 5000 has a rated uninterrupted current of 5000 A and a rated operational voltage of up to 690 V AC.
The E6.2X/MS 5000 provides a rated short-time withstand current of 120 kA for 1 s and 100 kA for 3 s, making it suitable for electrical distribution systems with very high prospective fault currents.
The 1SDA073466R1 is a switch disconnector based on the ABB SACE Emax 2 platform. It is intended for high-current switching and isolation rather than providing the integral electronic overcurrent protection associated with protective Emax 2 air circuit breakers.
The 4p designation identifies a four-pole device, F identifies the fixed installation configuration and HR identifies the horizontal rear terminal arrangement.
ABB SACE Emax 2 switch disconnectors combine very high continuous-current capability, exceptional short-time withstand performance and robust switchboard integration for demanding industrial, infrastructure and critical-power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.