ABB 1SDA073463R1 E6.2H/MS 4000 4p F HR is a 4000 A four-pole fixed SACE Emax 2 air switch-disconnector with orientable rear horizontal terminals, operation up to 690 V AC and a 100 kA one-second short-time withstand rating for demanding low-voltage switching and isolation.
£17,496.84
The ABB E6.2H/MS 4000 4p F HR, order code 1SDA073463R1, is a high-capacity four-pole fixed air switch-disconnector from the ABB SACE Emax 2 range. Rated at 4000 A, it is engineered for dependable high-current switching and isolation in demanding low-voltage power distribution systems.
The E6.2H/MS is a switch-disconnector rather than an automatic circuit breaker fitted with an electronic protection release. Its H-performance construction provides a rated short-time withstand current of 100 kA for 1 s, making it suitable for installations with very high prospective fault currents when coordinated with appropriately rated upstream or downstream protective devices.
This version combines a fixed four-pole configuration with orientable rear horizontal (HR) terminals for integration into high-current switchboards. With a rated operational voltage of up to 690 V AC, the E6.2H/MS 4000 provides robust switching and isolation for industrial plants, transformer distribution, infrastructure, data centres and other critical low-voltage power systems.
The ABB Emax 2 E6.2H/MS is designed for applications requiring dependable high-current switching and circuit isolation without integrated automatic overcurrent protection. Its combination of a 4000 A continuous current rating, operation at up to 690 V AC and 100 kA one-second short-time withstand capability makes it particularly suited to coordinated distribution systems with high prospective fault currents.
The fixed four-pole construction and orientable rear horizontal terminals make the 1SDA073463R1 suitable for integration into substantial low-voltage switchboards and busbar systems. Optional motor operation and voltage-release accessories also allow the switching arrangement to be adapted to applications requiring electrical control, while fault protection can be provided by separately coordinated protective equipment.
| Series | SACE Emax 2 |
|---|---|
| Product group | Emax2 Air Circuit Breaker |
| Frame / type | E6.2H/MS |
| Order code / MPN | 1SDA073463R1 |
| EAN / GTIN | 8015644773137 |
| Product type | Air switch-disconnector |
| Rated uninterrupted current (Iu) | 4000 A |
| Number of poles | 4P |
| Maximum rated operational voltage (Ue) | 690 V AC |
| Rated short-time withstand current (Icw), 1 s | 100 kA |
| Rated operational current, AC-21 at 400 V AC | 4000 A |
| Rated operational current, AC-23 at 400 V AC | 4000 A |
| Performance level | H |
| Protection release | None – switch-disconnector configuration |
| Installation | Fixed |
| Version | F |
| Terminal arrangement | Rear horizontal (HR) |
| Rear terminals | Orientable |
| Main-circuit connection | Bolt connection |
| Operating element | Push button |
| Interlockable | Yes |
| Integrated motor drive | No |
| Optional motor drive | Yes |
| Optional voltage release | Yes |
| Front-side degree of protection | IP30 |
| Auxiliary contacts supplied in listed configuration | 0 normally open, 0 normally closed, 0 change-over |
| Applicable switch-disconnector standard | IEC 60947-3 |
The ABB 1SDA073463R1 is a 4000 A four-pole Emax 2 switch-disconnector designed for high-current switching and isolation in demanding low-voltage electrical distribution systems.
The E6.2H/MS 4000 is a switch-disconnector. It provides switching and isolation without an integrated electronic overcurrent protection release, so appropriately coordinated protective devices are required where automatic overload and short-circuit protection is needed.
The E6.2H/MS 4000 has a rated short-time withstand current of 100 kA for 1 s, making it suitable for coordinated low-voltage systems with very high prospective fault currents.
F identifies the fixed installation version, while HR identifies the rear horizontal terminal arrangement. ABB specifies the E6.2H/MS fixed version with orientable rear terminals.
Yes. The ABB 1SDA073463R1 supports an optional motor drive for electrically operated switching applications. A voltage release is also available as an optional configuration accessory.
ABB SACE Emax 2 switch-disconnectors combine high continuous-current capability, strong short-time withstand performance and flexible switching architecture for dependable isolation in industrial, infrastructure and critical low-voltage power distribution systems.
We use cookies