ABB 1SDA073449R1 E2.2H/MS 1600 4p F HR is a 1600 A four-pole fixed SACE Emax 2 air switch-disconnector with rear horizontal terminals, 690 V AC operational voltage and an 85 kA one-second short-time withstand rating for demanding low-voltage switching and isolation applications.
£5,993.08
The ABB E2.2H/MS 1600 4p F HR, order code 1SDA073449R1, is a high-performance four-pole fixed air switch-disconnector from the ABB SACE Emax 2 range. Rated at 1600 A, it is designed for reliable switching and isolation in demanding low-voltage power distribution systems where four-pole disconnection and strong short-time withstand performance are required.
The E2.2H/MS is a switch-disconnector rather than an automatic circuit breaker equipped with an electronic protection release. Its H-performance construction provides a rated short-time withstand current of 85 kA for 1 s and 66 kA for 3 s, allowing the device to withstand substantial prospective fault currents while appropriately coordinated protective equipment provides automatic overload and short-circuit protection.
This version combines a fixed four-pole configuration with rear horizontal (HR) terminals for integration into high-current switchboards. With a rated operational voltage of 690 V AC, rated insulation voltage of 1000 V AC and 50/60 Hz operating frequency, the E2.2H/MS 1600 provides dependable isolation for industrial, commercial, infrastructure and critical power distribution applications.
The ABB Emax 2 E2.2H/MS is designed for electrical installations requiring dependable high-current switching and four-pole circuit isolation without integrated automatic overcurrent protection. Its combination of a 1600 A continuous current rating, 690 V AC operational voltage and short-time withstand ratings of 85 kA for 1 s and 66 kA for 3 s makes it well suited to coordinated power distribution systems with substantial prospective fault currents.
The fixed four-pole construction and rear horizontal terminals make the 1SDA073449R1 particularly suitable for integration into high-current low-voltage switchboards. Its AC-23A utilisation category, robust E2.2 frame and Emax 2 accessory architecture provide a versatile solution for switching and isolation across industrial facilities, infrastructure and critical electrical distribution systems.
| Series | SACE Emax 2 |
|---|---|
| Product group | Emax2 Air Circuit Breaker |
| Frame / type | E2.2H/MS |
| Order code / MPN | 1SDA073449R1 |
| EAN / GTIN | 8015644772994 |
| Product type | Air switch-disconnector |
| Rated uninterrupted current (Iu) | 1600 A |
| Number of poles | 4P |
| Current type | AC |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated frequency | 50/60 Hz |
| Rated short-time withstand current (Icw), 1 s | 85 kA |
| Rated short-time withstand current (Icw), 3 s | 66 kA |
| Utilisation category | AC-23A |
| Performance level | H |
| Protection release | None – switch-disconnector configuration |
| Installation | Fixed |
| Version | F |
| Terminal connection | Rear horizontal (HR) |
| Power loss | 136 W |
| Electrical durability at Ue ≤ 440 V | 12,000 cycles |
| Electrical durability at Ue 500–690 V | 10,000 cycles |
| Product net width | 366 mm |
| Product net height | 371 mm |
| Product net depth | 270 mm |
| Product net weight | 53 kg |
| Applicable standard | IEC 60947-3 |
The ABB 1SDA073449R1 is a 1600 A four-pole Emax 2 switch-disconnector designed for high-current switching and isolation duties in low-voltage electrical distribution systems.
The E2.2H/MS 1600 is a switch-disconnector. It provides switching and isolation without an integrated electronic protection release, so appropriately rated separate protective devices are required where automatic overload and short-circuit protection is needed.
The E2.2H/MS 1600 has a rated short-time withstand current of 85 kA for 1 s and 66 kA for 3 s, supporting use in demanding low-voltage distribution systems with high prospective fault currents.
F identifies the fixed installation version, while HR identifies the rear horizontal terminal arrangement. The 1SDA073449R1 is therefore a fixed E2.2 switch-disconnector with rear horizontal main terminals.
The ABB 1SDA073449R1 measures approximately 366 mm wide, 371 mm high and 270 mm deep, with a product net weight of approximately 53 kg.
ABB SACE Emax 2 switch-disconnectors combine high continuous-current capability, strong short-time withstand performance and robust switching architecture for dependable isolation in industrial, commercial, infrastructure and critical low-voltage power distribution systems.