1SDA073422R1 ABB E4.2H/MS 4000 3p FHR Switch Disconnector

1SDA073422R1 ABB E4.2H/MS 4000 3p FHR Switch Disconnector

ABB 1SDA073422R1 Emax 2 E4.2H/MS 4000 is a 4000 A three-pole fixed switch disconnector with rear horizontal terminals, a 690 V AC operational rating and an 85 kA short-time withstand current for 1 second.

SKU: 1SDA073422R1MPN: 1SDA073422R1
Price
List Price £19,216.78 ex VAT
Your Price (ex VAT) Save 25%
£14,412.59 25% OFF
You save £4,804.20 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £14,412.59
Trade pricing is personalised to your account

Manufacturer Lead Time

£14,412.59

Why Choose the ABB E4.2H/MS 4000 3p FHR Switch Disconnector?

The ABB E4.2H/MS 4000 3p FHR, order code 1SDA073422R1, is a high-current fixed SACE Emax 2 switch disconnector designed for dependable switching and isolation in demanding low-voltage power-distribution systems. Based on ABB's E4.2 frame, this three-pole unit combines a substantial 4000 A rated uninterrupted current, H performance level and fixed construction for major industrial, infrastructure and commercial switchboards.

The E4.2H/MS is a switch-disconnector rather than an Emax 2 air circuit breaker equipped with an Ekip electronic protection release. Its primary role is switching and isolation within a suitably protected electrical system, allowing high-current feeders, busbar sections and other distribution circuits to be disconnected while associated protective devices provide the required overcurrent and short-circuit protection.

The H-performance E4.2/MS configuration provides a rated short-time withstand current of 85 kA for 1 s. The 1SDA073422R1 is a fixed three-pole version with rear horizontal terminals (FHR), a rated operational voltage of 690 V AC and IP30 frontal protection, providing a robust isolation solution for high-capacity low-voltage switchboards.

Key Advantages

  • Very high 4000 A rated uninterrupted current for major low-voltage distribution systems.
  • Three-pole configuration for three-phase switching and isolation.
  • H performance level provides enhanced short-time current withstand capability.
  • 85 kA short-time withstand current for 1 s supports demanding high-fault-level switchboards.
  • Fixed installation provides a robust permanent switchboard arrangement.
  • Rear horizontal terminals support practical integration with high-current switchboard busbars.
  • Suitable for operation at up to 690 V AC.

Key Features

  • ABB SACE Emax 2 E4.2H/MS series.
  • 4000 A rated uninterrupted current.
  • 3-pole configuration.
  • Switch-disconnector function.
  • H performance level.
  • Fixed mounting version.
  • Rear horizontal main-circuit terminals.
  • Bolted main-circuit connection.
  • Rated operational voltage: 690 V AC.
  • 85 kA rated short-time withstand current for 1 s.
  • IP30 frontal degree of protection.
  • Suitable for use as a main switch.
  • Optional motor operating mechanism and voltage release.
  • Designed for switching and isolation without an integral Ekip electronic protection trip unit.

High-Performance Switching and Isolation for Major Distribution Systems

Switch disconnectors provide a defined means of switching and isolating electrical circuits while operating alongside dedicated protective devices within the distribution system. The ABB E4.2H/MS 4000 combines a substantial 4000 A continuous-current rating with the robust SACE Emax 2 architecture, making it suitable for major switchboard positions where dependable high-current isolation is required without an integral electronic overcurrent trip unit.

Its H performance level provides an 85 kA short-time withstand current for 1 s, enabling the switch disconnector to withstand substantial fault current for the specified duration while the associated protective system operates. Combined with fixed construction and rear horizontal terminals, the 1SDA073422R1 provides a practical solution for high-capacity industrial, infrastructure and critical-power distribution assemblies.

Typical Applications

  • Main and sectional isolation in high-current low-voltage switchboards.
  • Industrial power-distribution systems.
  • Transformer secondary distribution assemblies.
  • Manufacturing and process-industry switchboards.
  • Commercial and infrastructure electrical distribution.
  • Utility and critical-power distribution systems.
  • Generator and auxiliary power-distribution switchboards.
  • Three-phase feeders requiring fixed 4000 A switching and high short-time withstand capability.

Technical Specifications

Series SACE Emax 2 E4.2
ABB order code 1SDA073422R1
EAN 8015644772727
Product type Switch disconnector
Frame E4.2
Performance level H
Rated uninterrupted current (Iu) 4000 A
Rated current, AC-21 at 400 V 4000 A
Rated current, AC-23 at 400 V 4000 A
Number of poles 3
Installation Fixed
Terminal arrangement Rear horizontal (FHR)
Main-circuit connection Bolted connection
Rated operational voltage (Ue) 690 V AC
Rated short-time withstand current (Icw), 1 s 85 kA
Frontal degree of protection IP30
Operating mechanism Push-button
Main-switch function Yes
Lockable Yes
Optional voltage release Yes
Optional motor operating mechanism Yes
Integrated motor operating mechanism No
Integral electronic trip unit No
Power loss 465 W
Dimensions (W × H × D) 384 × 371 × 270 mm
Net weight 56 kg
Country of origin Italy

Frequently Asked Questions

What is the ABB 1SDA073422R1?

The ABB 1SDA073422R1 is a SACE Emax 2 E4.2H/MS fixed three-pole switch disconnector rated at 4000 A and equipped with rear horizontal main-circuit terminals.

Is the ABB E4.2H/MS 4000 a circuit breaker or switch disconnector?

It is a switch disconnector. The E4.2H/MS configuration is intended for switching and isolation rather than providing the integral electronic overcurrent protection associated with Emax 2 air circuit breakers fitted with Ekip trip units.

What is the short-time withstand current of the ABB 1SDA073422R1?

The E4.2H/MS 4000 has a rated short-time withstand current of 85 kA for 1 s, supporting use in high-current distribution systems with substantial prospective fault levels.

What does FHR mean on the ABB E4.2H/MS 4000?

The FHR configuration denotes a fixed Emax 2 switch disconnector with rear horizontal terminals, providing a rear-facing main-circuit connection suitable for integration with switchboard busbars.

Is the ABB 1SDA073422R1 fixed or withdrawable?

The 1SDA073422R1 is a fixed-mounting switch disconnector intended for permanent installation within the switchboard rather than use as a withdrawable moving part.

Trusted Switching and Isolation for High-Current Distribution

ABB SACE Emax 2 switch disconnectors combine robust high-current switching, substantial short-time current withstand and practical switchboard connection arrangements to provide dependable isolation for demanding low-voltage power-distribution systems.