ABB 1SDA073414R1 SACE Emax 2 E2.2N/MS 2500 three-pole fixed switch disconnector with horizontal rear terminals, a 2500 A rated uninterrupted current, 690 V AC operational voltage and 66 kA short-time withstand capability for high-current low-voltage switching and isolation.
£6,987.04
The ABB E2.2N/MS 2500 3p F HR, order code 1SDA073414R1, is a high-current SACE Emax 2 switch disconnector designed for dependable switching and isolation in low-voltage electrical distribution systems. Built on ABB's E2.2 platform, this fixed three-pole device provides a 2500 A rated uninterrupted current and is suited to industrial, commercial and infrastructure switchboards where robust high-current isolation is required.
The E2.2N/MS configuration is a circuit-breaker-derived switch disconnector intended for switching and isolation rather than integral overcurrent protection. Its fixed construction with horizontal rear terminals (HR) supports direct integration with switchboard busbar arrangements, making it particularly suitable for main switching, feeder isolation and bus-section applications.
Rated for operation at up to 690 V AC, with a 1000 V AC insulation voltage, 12 kV impulse withstand voltage and rated short-time withstand current of 66 kA for 1 s and 50 kA for 3 s, the E2.2N/MS 2500 provides robust electrical performance for demanding low-voltage distribution installations.
Switch disconnectors provide a dependable means of making, carrying and isolating electrical circuits while overcurrent and short-circuit protection is provided elsewhere in the installation. In high-capacity low-voltage switchboards, air-circuit-breaker-derived switch disconnectors provide the mechanical robustness and current-carrying capability required for main isolation, feeder switching and busbar applications.
The ABB E2.2N/MS 2500 combines a 2500 A continuous-current rating with a 66 kA short-time withstand capability for 1 s. Its fixed three-pole construction and horizontal rear terminals make it well suited to switchboards requiring direct rear busbar connections, while its Emax 2 architecture provides dependable operation across demanding industrial and infrastructure installations.
| Series | SACE Emax 2 |
|---|---|
| Order code / MPN | 1SDA073414R1 |
| EAN / GTIN | 8015644772642 |
| Product type | Circuit-breaker switch disconnector |
| Product group | Emax 2 Air Circuit Breaker |
| Frame | E2.2 |
| Performance level | N/MS |
| Rated uninterrupted current (Iu) | 2500 A |
| Rated current (In) | 2500 A |
| Number of poles | 3 |
| Current type | AC |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated short-time withstand current (Icw), 1 s | 66 kA |
| Rated short-time withstand current (Icw), 3 s | 50 kA |
| Rated permanent current, AC-21 at 400 V | 2500 A |
| Rated permanent current, AC-23 at 400 V | 2500 A |
| Short-circuit performance level | N |
| Electrical durability at Ue ≤ 440 V | 8000 cycles |
| Electrical durability at Ue 500–690 V | 7000 cycles |
| Mechanical durability | 20000 cycles |
| Power loss | 267 W |
| Connecting capacity | 1800 mm² |
| Main-circuit connection | Bolted connection |
| Installation | Fixed |
| Terminal configuration | Horizontal rear terminals (HR) |
| Dimensions (W × H × D) | 276 × 371 × 270 mm |
| Net weight | 41 kg |
| Standard | IEC |
The ABB 1SDA073414R1 is an Emax 2 E2.2N/MS 2500 three-pole switch disconnector with fixed installation and horizontal rear terminals, designed for high-current low-voltage switching and isolation.
The E2.2N/MS 2500 has a rated uninterrupted current of 2500 A and is rated for operation at up to 690 V AC.
The 1SDA073414R1 is a circuit-breaker switch disconnector based on the ABB SACE Emax 2 platform. It is intended for switching and isolation and does not incorporate the electronic overcurrent protection trip unit found on protective Emax 2 air circuit breakers.
The E2.2N/MS 2500 has a rated short-time withstand current of 66 kA for 1 s and 50 kA for 3 s.
The F designation identifies the fixed installation configuration, while HR identifies the horizontal rear terminal arrangement used for connection within the switchboard.
ABB SACE Emax 2 switch disconnectors combine high continuous-current capability, strong short-time withstand performance and flexible switchboard integration for demanding industrial, commercial and infrastructure low-voltage power distribution systems.