1SDA073414R1 ABB E2.2N/MS 2500 3p F HR Switch Disconnector

1SDA073414R1 ABB E2.2N/MS 2500 3p F HR Switch Disconnector

ABB 1SDA073414R1 SACE Emax 2 E2.2N/MS 2500 three-pole fixed switch disconnector with horizontal rear terminals, a 2500 A rated uninterrupted current, 690 V AC operational voltage and 66 kA short-time withstand capability for high-current low-voltage switching and isolation.

SKU: 1SDA073414R1MPN: 1SDA073414R1
Price
List Price £9,316.05 ex VAT
Your Price (ex VAT) Save 25%
£6,987.04 25% OFF
You save £2,329.01 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £6,987.04
Trade pricing is personalised to your account

Manufacturer Lead Time

£6,987.04

Why Choose the ABB E2.2N/MS 2500 3p F HR Switch Disconnector?

The ABB E2.2N/MS 2500 3p F HR, order code 1SDA073414R1, is a high-current SACE Emax 2 switch disconnector designed for dependable switching and isolation in low-voltage electrical distribution systems. Built on ABB's E2.2 platform, this fixed three-pole device provides a 2500 A rated uninterrupted current and is suited to industrial, commercial and infrastructure switchboards where robust high-current isolation is required.

The E2.2N/MS configuration is a circuit-breaker-derived switch disconnector intended for switching and isolation rather than integral overcurrent protection. Its fixed construction with horizontal rear terminals (HR) supports direct integration with switchboard busbar arrangements, making it particularly suitable for main switching, feeder isolation and bus-section applications.

Rated for operation at up to 690 V AC, with a 1000 V AC insulation voltage, 12 kV impulse withstand voltage and rated short-time withstand current of 66 kA for 1 s and 50 kA for 3 s, the E2.2N/MS 2500 provides robust electrical performance for demanding low-voltage distribution installations.

Key Advantages

  • High 2500 A rated uninterrupted current for demanding low-voltage distribution systems.
  • Three-pole switch disconnector for three-phase switching and isolation duties.
  • 66 kA short-time withstand current for 1 s supports operation in high fault-level networks.
  • 50 kA short-time withstand current for 3 s provides strong short-time current withstand capability.
  • Rated for operation at up to 690 V AC.
  • Horizontal rear terminals support efficient connection to switchboard busbars.
  • Fixed installation provides a robust and straightforward switchboard configuration.
  • Based on ABB's modular SACE Emax 2 platform for integration into demanding power distribution systems.

Key Features

  • ABB SACE Emax 2 E2.2N/MS switch disconnector.
  • 2500 A rated uninterrupted current.
  • Three-pole configuration.
  • Fixed installation.
  • Horizontal rear terminals (HR).
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 66 kA rated short-time withstand current for 1 s.
  • 50 kA rated short-time withstand current for 3 s.
  • 2500 A AC-21 switching current at 400 V AC.
  • 2500 A AC-23 switching current at 400 V AC.
  • Electrical durability of 8000 cycles at ≤440 V AC.
  • Electrical durability of 7000 cycles at 500–690 V AC.
  • Mechanical durability of 20000 cycles.

High-Current Switching and Isolation for Power Distribution

Switch disconnectors provide a dependable means of making, carrying and isolating electrical circuits while overcurrent and short-circuit protection is provided elsewhere in the installation. In high-capacity low-voltage switchboards, air-circuit-breaker-derived switch disconnectors provide the mechanical robustness and current-carrying capability required for main isolation, feeder switching and busbar applications.

The ABB E2.2N/MS 2500 combines a 2500 A continuous-current rating with a 66 kA short-time withstand capability for 1 s. Its fixed three-pole construction and horizontal rear terminals make it well suited to switchboards requiring direct rear busbar connections, while its Emax 2 architecture provides dependable operation across demanding industrial and infrastructure installations.

Typical Applications

  • Main switchboard switching and isolation.
  • Industrial low-voltage power distribution systems.
  • High-current feeder switching and isolation.
  • Busbar and bus-section isolation.
  • Transformer secondary distribution switchboards.
  • Manufacturing and process plant electrical systems.
  • Commercial buildings and critical infrastructure.

Technical Specifications

Series SACE Emax 2
Order code / MPN 1SDA073414R1
EAN / GTIN 8015644772642
Product type Circuit-breaker switch disconnector
Product group Emax 2 Air Circuit Breaker
Frame E2.2
Performance level N/MS
Rated uninterrupted current (Iu) 2500 A
Rated current (In) 2500 A
Number of poles 3
Current type AC
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Rated short-time withstand current (Icw), 1 s 66 kA
Rated short-time withstand current (Icw), 3 s 50 kA
Rated permanent current, AC-21 at 400 V 2500 A
Rated permanent current, AC-23 at 400 V 2500 A
Short-circuit performance level N
Electrical durability at Ue ≤ 440 V 8000 cycles
Electrical durability at Ue 500–690 V 7000 cycles
Mechanical durability 20000 cycles
Power loss 267 W
Connecting capacity 1800 mm²
Main-circuit connection Bolted connection
Installation Fixed
Terminal configuration Horizontal rear terminals (HR)
Dimensions (W × H × D) 276 × 371 × 270 mm
Net weight 41 kg
Standard IEC

Frequently Asked Questions

What is the ABB 1SDA073414R1?

The ABB 1SDA073414R1 is an Emax 2 E2.2N/MS 2500 three-pole switch disconnector with fixed installation and horizontal rear terminals, designed for high-current low-voltage switching and isolation.

What is the rated current of the ABB E2.2N/MS 2500?

The E2.2N/MS 2500 has a rated uninterrupted current of 2500 A and is rated for operation at up to 690 V AC.

Is the ABB E2.2N/MS 2500 a circuit breaker or switch disconnector?

The 1SDA073414R1 is a circuit-breaker switch disconnector based on the ABB SACE Emax 2 platform. It is intended for switching and isolation and does not incorporate the electronic overcurrent protection trip unit found on protective Emax 2 air circuit breakers.

What is the short-time withstand current of the ABB 1SDA073414R1?

The E2.2N/MS 2500 has a rated short-time withstand current of 66 kA for 1 s and 50 kA for 3 s.

What does F HR mean on the ABB E2.2N/MS 2500?

The F designation identifies the fixed installation configuration, while HR identifies the horizontal rear terminal arrangement used for connection within the switchboard.

Trusted High-Current Switching from ABB

ABB SACE Emax 2 switch disconnectors combine high continuous-current capability, strong short-time withstand performance and flexible switchboard integration for demanding industrial, commercial and infrastructure low-voltage power distribution systems.